![Princeton GTIB-30 Скачать руководство пользователя страница 42](http://html1.mh-extra.com/html/princeton/gtib-30/gtib-30_installation-manual_1603033042.webp)
GTIB-30 Installation Manual-UL
42
4411-0011, Rev 2.0
4.5 Wire Sizing and Ratings
All wiring installed in the system must be rated for 600VAC, including control and
signal wiring.
Installation to Code:
The following instructions are merely a guide for proper
installation. The National Electric Codes (NEC), local codes, and similar standards
outline detailed requirements for safe installation of electrical equipment. Installation
must comply with specifications for wire types, conductor sizes, electrical and
thermal insulation, branch circuit protection, grounding, and disconnect devices.
Princeton Power Systems cannot assume responsibility for compliance or
noncompliance to any national or local code. Princeton Power Systems cannot
assume responsibility for personal injury and/or equipment damage exists if codes are
ignored or misapplied during installation.
4.5.1 Power Conductor Sizing and Ratings
All AC and DC power and earth wiring, including grid port, load port, and DC port,
should meet the following specifications:
Table 4: Minimum power port wire requirements
Voltage Rating
600 Volts or greater per NEC
Temperature Class
90°C or greater per NEC
Gauge
DC: copper, 3 AWG (6 AWG Earth GND)
AC - 208V: copper,6 AWG (10AWG Earth GND)
AC - 480V: copper, 8 AWG (10AWG Earth GND)
Also refer to Section 4.7 for ground wire requirements.
4.5.2 Control Wire Sizing and Ratings
The tables in this section provide a guideline for wire types that should be used for
the different types of signal and control wiring.
Note: Class 1 wiring methods are to be used for all field wiring connections to a
class 2 circuit.
4.5.2.1
Analog, Digital I/O and temperature sensor wiring
Refer to Sections 4.13.1 and 4.13.2 for more information.
Table 5: User I/O wire requirements
Voltage Rating
600 Volts
Temperature Class
75°C or greater
Gauge
Copper Stranded: 22 - 18AWG
Cable type
Shielded twisted pair recommended
Содержание GTIB-30
Страница 1: ...Clean power made simple GTIB 30 Installation Manual ...
Страница 2: ...www princetonpower com 4411 0011 Rev 2 0 April 1st 2014 ...
Страница 11: ...About this Manual 4411 0011 Rev 2 0 xi This page intentionally left blank ...
Страница 15: ...Contents 4411 0011 Rev 2 0 15 This page intentionally left blank ...
Страница 16: ...1 Introduction ...
Страница 18: ...2 System Overview and Configurations ...
Страница 31: ...3 Pre Installation ...
Страница 36: ...GTIB 30 Installation Manual UL 36 4411 0011 Rev 2 0 This page intentionally left blank ...
Страница 37: ...4 Wiring Instructions ...
Страница 56: ...GTIB 30 Installation Manual UL 56 4411 0011 Rev 2 0 This page intentionally left blank ...
Страница 57: ...5 Commissioning Sequences ...
Страница 61: ...GTIB 30 Installation Manual UL 4411 0011 Rev 2 0 61 This page intentionally left blank ...
Страница 62: ...A GTIB 30 kW Specifications ...
Страница 65: ...GTIB 30 Installation Manual UL 4411 0011 Rev 2 0 65 This page intentionally left blank ...
Страница 66: ...B Return Material Authorization Contact and Product Information ...
Страница 69: ...GTIB 30 Installation Manual UL 4411 0011 Rev 2 0 69 This page intentionally left blank ...