MANUAL 

– INSTALLATION & SERVICE

Fan Filter Unit - High Efficiency

FFU-HE Series

v200 

 Issue Date: 02/19/16

© 2016 Price Industries Limited. All rights reserved.

Содержание FFU-HE Series

Страница 1: ...MANUAL INSTALLATION SERVICE Fan Filter Unit High Efficiency FFU HE Series v200 Issue Date 02 19 16 2016 Price Industries Limited All rights reserved ...

Страница 2: ...ench Top Replaceable Filter BTR 23 Filter Motor Indicator LED ML FL RSR 25 Filter Motor Indicator LED FL ML BTR 27 Motor Filter Indicator BAS MBAS FBAS 31 Service Cleaning of Pre Filter 32 Service Removal and Replacement of RSR Filter 33 Service Removal and Replacement of BTR Filters 34 Service Changing Motors in the Field 35 Top Access Motor Blower Assembly 35 Room Side accessible Motor Blower As...

Страница 3: ... Use this unit only in the manner intended by the manufacturer If you have any questions contact the manufacturer In the United States 2975 Shawnee Ridge Court Suwanee Georgia USA 30024 Ph 770 623 8050 Fax 770 623 6404 In Canada International Export Sales Office 638 Raleigh Street Winnipeg Manitoba Canada R2K 3Z9 Ph 204 669 4220 Fax 204 663 2715 D Before servicing or cleaning unit switch power off...

Страница 4: ...lters can occur during installation or during leak qualification testing The filters supplied by Price have been 100 tested and certified by the manufacturer to be free of defects and leaks Price cannot accept responsibility for damage that occurs after shipment whether through transit handling or installation and will not replace filters under our standard warranty If units are to be ducted read ...

Страница 5: ...01655 CONFORMS TO UL STD 507 CERTIFIED TO CSA STD C22 2 NO 113 SERIAL MODEL H P VOLTS PH CYC x Manufactured By AMPS MAX OVERCURRENT PROT MOP MIN CIRCUIT AMPACITY MCA 045451 001 REV C R P M MOTOR THERMALLY PROTECTED TESTED TO 1 2 w g MAX OPERATING STATIC PRESSURE INSTALL FAN AT LEAST 7 FT ABOVE THE FLOOR AVERTISSEMENT COUPER LES SOURCES POWER SUPPLIES BEFORE SERVICING WARNING DISCONNECT ALL REMOTE ...

Страница 6: ...ily load the filter Sample line string for Room Side Replaceable filter FFU HE 24 48 RSR BC ECM 115 10 CT HEPA ECMDX WK DSW PC TMB ML FL WPF PL AL PL MILL STEP 1 Remove FFU from shipping carton and inspect for any damage NOTE Ensure the HEPA ULPA filter has been safely stored in a vertical position per carton label until ready for use STEP 2 If unit is Bench Top Replaceable BTR refer to page 23 fo...

Страница 7: ...nit STEP 6 Adjust and level the unit so that it rests on the tees and there is adequate compression on the gasket to warrant a tight seal Ensure that ceiling grid is properly gasketed sealed to prevent infiltration of unfiltered air from the ceiling plenum into the room side Above steps are manufacturer s suggested hanging techniques always make sure to follow all local building codes including se...

Страница 8: ...HE 24 48 RSR BC ECM 115 10 CT HEPA ECMDX WK DSW PC TMB ML FL WPF PL AL PL MILL Speed Controller Page Reference PSCSC WK 7 ECMSC WK 9 ECMDX WK 13 BFC 16 NOTE Depending on unit ordered speed controller will be mounted on the unit itself or if a wall kit option was selected shipped loose for field installation FAN FILTER UNIT HIGH EFFICIENCY INSTALLATION SERVICE INSTRUCTIONS 6 FAN FILTER UNIT HIGH EF...

Страница 9: ...ls faceplate to the electrical box using the screws provided STEP 11A Wire the unit according to appropriate wiring diagram If Power Cord PC option is selected simply insert plug end into electrical socket Sample line string below FFU HE 24 48 RSR BC ECM 115 10 CT HEPA ECMSC DSW PC TMB ATS ML FL WPF PL AL F AL PL B12 F B12 NOTE Wiring should be carried out by a certified electrician and meet natio...

Страница 10: ...efer to Technical Note Balancing Ducted Units on page 44 of this manual FAN FILTER UNIT HIGH EFFICIENCY INSTALLATION SERVICE INSTRUCTIONS Speed Controller Adjustment 8 FAN FILTER UNIT HIGH EFFICIENCY Manual priceindustries com ...

Страница 11: ...e the unit according to appropriate wiring diagram If Power Cord PC option is selected simply insert plug end into electrical socket Sample line string below FFU HE 24 48 RSR BC ECM 115 10 CT HEPA ECMSC DSW PC TMB ATS ML FL WPF PL AL F AL PL B12 F B12 NOTE Wiring should be carried out by a certified electrician and meet national and local electrical codes STEP 12B If using RSR filter refer to page...

Страница 12: ...115 VDC CFM 201 250 240 VDC CFM 204 252 277 VDC CFM 238 262 RSR Filters with FC Wheel 24 x24 FFU HE Voltage Equation 115 VDC CFM 104 100 240 VDC CFM 104 100 277 VDC CFM 74 98 24 x36 FFU HE Voltage Equation 115 VDC CFM 179 178 240 VDC CFM 179 179 277 VDC CFM 172 172 24 x48 FFU HE Voltage Equation 115 VDC CFM 235 237 240 VDC CFM 255 241 277 VDC CFM 219 234 FAN FILTER UNIT HIGH EFFICIENCY INSTALLATIO...

Страница 13: ...gnal The VDC equations are based on a 1 5 Volt scale The BAS input voltage is a 2 10 VDC scale and therefore VDC calculated for a given CFM using the equation must be doubled to achieve that CFM using the BAS input BAS Voltage Response Notes 0 1 VDC Local control mode using push buttons Local setpoint can be adjusted from 0 100 using push buttons 1 2 VDC Motor Off Recommended sending a 1 5 VDC sig...

Страница 14: ... at the unit face using a flow hood Adjust the POT DIAL or BAS input signal to reach desired airflow as required NOTE If unit is ducted please refer to Technical Note Balancing Ducted Units on page 44 of this manual POTENTIOMETER DIAL ADJUST GREEN STATUS LED MUST BE BLINKING CODE 1 THRU 4 Speed Controller Adjustment 12 FAN FILTER UNIT HIGH EFFICIENCY Manual priceindustries com ...

Страница 15: ...al box for wall mounted speed controller NOTE Wall kit must be mounted horizontally as shown above STEP 9C Wire unit according to wiring diagram found on page 58 and 60 Motor speed controller will have color coded wires and must be wired to the matching colors on the wall mounted portion NOTE 24VAC and COMMON will need to be run from the terminal block in the control box to the terminals listed 24...

Страница 16: ... the space is clean free of debris and that ducts are cleaned and ready for operation prior to installation of filter STEP 13C Wire unit according to wiring diagram found on page 58 and 60 STEP 14C Ensure proper Voltage is hooked up and turn unit on NOTE ECMDX Speed Controllers have multiple modes which are listed below Display Mode Range L SEt Local Setpoint Manual speed adjust mode use UP DOWN t...

Страница 17: ...ng on field variables NOTE The BAS signal will override the local setpoint using a remote 0 10 VDC signal If the BAS signal drops below 1 VDC local control via the up down buttons is restored The ECMDX speed controller can be controlled using multiple strategies these are outlined in the chart below BAS Voltage Response Notes 0 1 VDC Local control mode using push buttons Local setpoint can be adju...

Страница 18: ...lectrical socket Sample line string below FFU HE 24 48 RSR BC ECM 115 10 CT HEPA ECMSC DSW PC TMB ATS ML FL WPF PL AL F AL PL B12 F B12 NOTE Wiring should be carried out by a certified electrician and meet national and local electrical codes STEP 11D If using RSR filter refer to page 21 for installation instructions NOTE Ensure that the space is clean free of debris and that ducts are cleaned and ...

Страница 19: ...airflow Any changes to the airflow will require the filter status to be reset STEP 16D To calibrate clean filter pressure drop scroll scroll through the Service Menus until reaching Filter select this menu by pressing the Enter Menu button far right STEP 17D Scroll through the Filter menu until reaching Reset Filter select by pressing the Enter Menu button Price FFU HE FE Points List 17 priceindus...

Страница 20: ...tatic pressure STEP 18D Press the Enter Menu button to confirm reset of filter this will begin calibration This will take approximately 2 minutes After filter calibration is complete LCD will display RESET COMPLETED NOTE If unit is ducted please refer to Technical Note Balancing Ducted Units on page 44 of this manual Calibration Screen Filter Reset Screen 18 FAN FILTER UNIT HIGH EFFICIENCY Manual ...

Страница 21: ...ffusers perforated face by turning quarter turn fasteners holding face in place FFU HE 24 48 RSR BC ECM 115 10 CT HEPA ECMDX WK DSW PC TMB ATS ML FL WPF PL AL F AL PL B12 F B12 NOTE Safety cables will be attached to the diffuser face but care should be taken to ensure that diffuser face does not swing and injure anyone If unit is bench top removable BTR proceed to next step STEP 2 Remove threaded ...

Страница 22: ... required to verify flow and concentration The following table outlines a few possible problems that may be encountered during leakage testing This chart is intended as a quick troubleshooting guide and is not exhaustive All local and applicable codes should be followed Problem Possible Cause Solution Leakage at the perimeter of the filter Improper filter installation Gently remove the filter veri...

Страница 23: ...ak qualification testing The filters supplied by Price have been 100 tested and certified by the manufacturer to be free of defects and leaks Price cannot accept responsibility for damage that occurs after shipment whether through transit handling or installation and will not replace filters under our standard warranty STEP 2 STEP 4 STEP 1 STEP 3 Remove filter from box using handles Place unit on ...

Страница 24: ...d to tighten and using one may cause damage to filter gel seal Ensure HEPA filter outer frame is in contact with horizontal knife edge of frame Note that diffuser knife edge cannot bottom out in HEPA filter gel seal Using the alignment guides raise the filter into place ensuring filter gel seal channel seat into knife edge of plenum NOTE Do not bottom out gel seal in plenum knife edge The gel seal...

Страница 25: ...nt whether through transit handling or installation and will not replace filters under our standard warranty NOTE If ordered with Filter or Motor LED Indicator ML FL refer to LED installation instructions which must be done at same time as filter installation FFU HE 24 48 BTR BC ECM 115 10 CT HEPA ECMDX WK DSW PC TMB ML FL WPF PL AL PL MILL STEP 2 STEP 1 Place filter box on floor careful to set bo...

Страница 26: ...reful to not damage the filter media Attach filter to top cap assembly by hooking and securing latches Gasket may need to be compressed to grab channel with latch FAN FILTER UNIT HIGH EFFICIENCY INSTALLATION SERVICE INSTRUCTIONS 24 FAN FILTER UNIT HIGH EFFICIENCY Manual priceindustries com ...

Страница 27: ...eeded calbirated setting factory set at 1 5x clean filter pressure Motor LED ML Green None Indicates normal motor operation when the static pressure is above 0 2 w g Red Troubleshoot Motor Indicates motor is not in operation and that unit static pressure is below 0 2 w g Calibration Filter LED will come factory set to activate at the pressure drops listed in the Table below Filter Pressure 90fpm i...

Страница 28: ...1 8 approximately NOTE Maximum available pressure setting is 1 0 w g Do not exceed 4 turns total Necessary STEP 3 Turn screw clockwise the number of turns calculated above You will need a 1 5mm hex Allen wrench STEP 4 To check filter pressure set point and or to fine tune insert Magnehelic gauge into the static pressure port located along knife edge of diffuser diffuser face must be removed to acc...

Страница 29: ...n filter pressure Yellow Change Filter Indicates filter pressure drop has exceeded calbirated setting factory set at 1 5x clean filter pressure Motor LED ML Green None Indicates normal motor operation when the static pressure is above 0 2 w g Red Troubleshoot Motor Indicates motor is not in operation and that unit static pressure is below 0 2 w g Installation STEP 1 Remove BTR filter from box by f...

Страница 30: ...atic Presure Port Remove Threaded Standoff STEP 3 Remove well nut in center port of BTR filter STEP 4 Remove threaded standoff and lock washer from LED cable assembly THREADED STANDOFF LOCK WASHER RUBBER WASHER METAL WASHER LED 28 FAN FILTER UNIT HIGH EFFICIENCY Manual priceindustries com ...

Страница 31: ... protect the LED light from breaking STEP 6 Put lock washer and threaded standoff back on cable and tighten to LED FAN FILTER UNIT HIGH EFFICIENCY INSTALLATION SERVICE INSTRUCTIONS Installed LED on Filter Face Filter Resting on Lumber Threaded Standoff through Filter Channel 29 priceindustries com FAN FILTER UNIT HIGH EFFICIENCY Manual ...

Страница 32: ...to BTR Filter Instructions found on page 23 for proper filter installation STEP 9 Refer to wiring diagram located in control box to connect LED leads to terminal block NOTE If unit has BFC speed controller LED leads will need to be connected to the BFC controller instead of the terminal block Calibration Refer to page 18 for filter calibration 30 FAN FILTER UNIT HIGH EFFICIENCY Manual priceindustr...

Страница 33: ...tor is not operating Filter BAS FBAS Change Filter Closes a dry contact to let the BAS signal pass through when the static pressure is greater than the calibrated pressure drop factory set at 1 5x clean filter Unit will come factory calibrated no additional field modifications are required Wire unit terminal block according to wiring diagrams found starting on page 51 of this manual NOTE Wiring sh...

Страница 34: ...irt dust and debris that may be present in the unit s external environment STEP 1 Gain access to the top of the unit by removing adjacent ceiling or access panel STEP 2 Bend up pre filter retaining clips and remove the pre filter non ducted or remove filter access door ducted Reference the below figures for further details Non Ducted Unit Removal of Pre filter Ducted Unit STEP 3 Clean pre filter b...

Страница 35: ...swing and injure anyone STEP 2 Remove filter by loosening cam latch bolts filter retainer clips by turning counter clockwise using your hands STEP 3 Turn all cam latch filter retainers to the open position STEP 4 Remove filter by handling frame do not touch filter media if re using filter NOTE Extreme caution should be taken when removing the filter if the filter is to be reinstalled Touch the fil...

Страница 36: ... has been selected It is recommended to rest the filter frame on 2x4 lumber to protect the LED light STEP 2 Unhook latches attaching bench top replaceable filter to fan filter body STEP 3 Remove filter by handling frame do not touch filter media if re using filter NOTE Extreme caution should be taken when removing the filter if the filter is to be reinstalled Touch the filter by the frame only nev...

Страница 37: ...ype of maintenance on the FFU HE be careful to reduce as much as possible the potential for introducing the internals of the unit to dirt dust and debris that may be present in the unit s external environment STEP 1 Gain access to the top of the unit by removing adjacent ceiling or access panel STEP 2 Bend up pre filter retaining clips and remove the pre filter non ducted or remove the duct collar...

Страница 38: ...ly using a 7 16 socket wrench or equivalent STEP 6 Remove motor blower assembly STEP 7 Inspect and or replace parts STEP 8 Replace with the new motor blower assembly and reassemble by reversing the above steps NOTE For information on how to order replacement motor blowers contact your local Price Sales Representative Visit Price s website http www priceindustries com contact reps dealers to locate...

Страница 39: ...reduce as much as possible the potential for introducing the internals of the unit to dirt dust and debris that may be present in the unit s external environment STEP 1 Remove diffuser perforated face by turning quarter turn fasteners holding face in place NOTE Safety cables will be attached to the diffuser face but care should be taken to ensure that diffuser face does not swing and injure anyone...

Страница 40: ... media as it can damage the filter STEP 5 Remove the nuts securing the blower housing using a 7 16 socket wrench or equivalent NOTE A 7 16 ratchet with extension is recommended for ease of access for unfastening FAN FILTER UNIT HIGH EFFICIENCY INSTALLATION SERVICE INSTRUCTIONS 2x2 FC Blower Housing BC Wheel Housing 2x3 and 2x4 FC Blower Housing NUTS LOCATED ON TOP OF BLOWER HOUSING NUTS LOCATED ON...

Страница 41: ...s holding motor blower assembly in place STEP 8 Drop motor blower assembly out of unit Be careful as wire connection are still in place STEP 9 Disconnect plug and play connection connecting wires from motor to control box Removal of 2x2 Motor Blower Housing Removal of Motor Blower Housing 39 priceindustries com FAN FILTER UNIT HIGH EFFICIENCY Manual ...

Страница 42: ...asn t changed applicable speed controller found on pages X X NOTE For information on how to order replacement motor blowers contact your local Price Sales Representative Visit Price s website http www priceindustries com contact reps dealers to locate your local Representative Plug and Play Connections FAN FILTER UNIT HIGH EFFICIENCY INSTALLATION SERVICE INSTRUCTIONS 40 FAN FILTER UNIT HIGH EFFICI...

Страница 43: ...face in place NOTE Safety cables will be attached to the diffuser face but care should be taken to ensure that diffuser face does not swing and injure anyone Step 2 Remove gasketed bolt STEP 3 Insert pressure measuring gauge eg Magnehelic to read pressure drop across filter Hole size is 5 16 NOTE Static Pressure Port can also be used as a test port for sample aerosol concentrations upstream of the...

Страница 44: ...care should be taken to ensure that diffuser face does not swing and injure anyone STEP 1 Remove gasketed bolt located along center channel of BTR filter There are two ports located on the face either can be used STEP 3 Insert pressure measuring gauge eg Magnehelic to read pressure drop across filter Hole size is 5 16 NOTE Static Pressure Port can also be used as a test port for sample aerosol con...

Страница 45: ...balancing and the FFU HE is installed and running Similarly the FFU HE should be bench set by using a flow hood and adjusting the speed controller as required to the same balanced primary airflow rate before the FFU HE is mated with the duct Alternatively the Balancing Ducted Units Technical Note can also be followed on page 44 of this manual To prevent a high static pressure build up at the FFU H...

Страница 46: ...nits with ECM units with constant airflow program If removing the FFU HE from the duct is not possible follow the below instructions for balancing STEP 1 Install an air pressure measurement device i e Pitot tube in the inlet of the FFU HE STEP 2 Power up FFU HE and set the speed controller to approximately 75 of maximum set point STEP 3 Power upstream airflow control device and set airflow to the ...

Страница 47: ...ariable speed control for higher blower output 3 Check power for proper voltage amerage and distribution frequency 4 Replace HEPA ULPA filter if the veloicty remains low High Air Velocity 1 Adjust variable speed control for lower blower output Non Laminar Flow and or Excessive Contamination 1 Ensure that no large obstructions are upstream of airlfow pattern 2 Determine that no other air moving dev...

Страница 48: ...troller 1 Deluxe Wall Mounted Speed Control for ECM Motor 232953 400 ECMDX Motor Cable 1 Wall Mounted Remote for ECM Motor 019186 006 ECMDX Wall Cable 1 ECMDX BFC Speed Control 2 ft 019186 004 ECM Power Cable 1 Power Cable Harness 115V 0191487 003 240V 277V 019187 004 Transformer Quantity Description Price Part Number 115V 1 Transformer 120 24 50VA FT MT 019436 001 208 240V 1 Transformer 208 240V ...

Страница 49: ...0 ECMDX Motor Cable 1 Wall Mounted Remote for ECM Motor 019186 006 ECMDX Wall Cable 1 ECMDX BFC Speed Control 2 ft 019186 004 ECM Power Cable 1 Power Cable Harness 115V 0191487 003 240V 277V 019187 004 Transformer Quantity Description Price Part Number 115V 1 Transformer 120 24 50VA FT MT 019436 001 208 240V 1 Transformer 208 240V 24V 50VA FT MT 019436 011 277V 1 Transformer 277 24V 50VA FT MT 019...

Страница 50: ...erence Manuals BACnet Wiring Guidelines Deluxe ECM Speed Controller ECM Motor Troubleshooting Manual BFC Speed Controller NOTE Above manuals can be found on the Price Industries website at priceindustries com 48 FAN FILTER UNIT HIGH EFFICIENCY Manual priceindustries com ...

Страница 51: ...ow Controller Wall Kit 18 None WK Wall Mounted Speed Controller Disonnect 20 None DSW Disconnect Switch Power Cord 22 None PC Power Cord Power Cord 22 None PC Power Cord Motor Blower Access 24 TMB Top Access Motor Blower Assembly RMB Room Side Accessible Mo tor Blower Assembly Aerosol Test System 26 None ATS Aerosol Test System Motor Status 28 None ML Motor Status LED MBAS Motor Status BAS Signal ...

Страница 52: ...FAN FILTER UNIT HIGH EFFICIENCY INSTALLATION SERVICE INSTRUCTIONS WIRING DIAGRAM FFU HE LED FL WIRING DIAGRAM FFU HE LED ML 50 FAN FILTER UNIT HIGH EFFICIENCY Manual priceindustries com ...

Страница 53: ...FAN FILTER UNIT HIGH EFFICIENCY INSTALLATION SERVICE INSTRUCTIONS WIRING DIAGRAM FFU HE LED FBAS WIRING DIAGRAM FFU HE LED MBAS 51 priceindustries com FAN FILTER UNIT HIGH EFFICIENCY Manual ...

Страница 54: ...FAN FILTER UNIT HIGH EFFICIENCY INSTALLATION SERVICE INSTRUCTIONS WIRING DIAGRAM FFU HE LED ML FL WIRING DIAGRAM FFU HE LED FL FBAS 52 FAN FILTER UNIT HIGH EFFICIENCY Manual priceindustries com ...

Страница 55: ...FAN FILTER UNIT HIGH EFFICIENCY INSTALLATION SERVICE INSTRUCTIONS WIRING DIAGRAM FFU HE LED MBAS FL WIRING DIAGRAM FFU HE LED FL FBAS 53 priceindustries com FAN FILTER UNIT HIGH EFFICIENCY Manual ...

Страница 56: ...FAN FILTER UNIT HIGH EFFICIENCY INSTALLATION SERVICE INSTRUCTIONS WIRING DIAGRAM FFU HE LED ML MBAS WIRING DIAGRAM FFU HE LED MBAS FBAS 54 FAN FILTER UNIT HIGH EFFICIENCY Manual priceindustries com ...

Страница 57: ...FAN FILTER UNIT HIGH EFFICIENCY INSTALLATION SERVICE INSTRUCTIONS WIRING DIAGRAM FFU HE LED ML FL FBAS WIRING DIAGRAM FFU HE LED ML MBAS FL 55 priceindustries com FAN FILTER UNIT HIGH EFFICIENCY Manual ...

Страница 58: ...ILTER UNIT HIGH EFFICIENCY INSTALLATION SERVICE INSTRUCTIONS WIRING DIAGRAM FFU HE LED ML MBAS FL FBAS WIRING DIAGRAM FFU HE LED ML MBAC FL FBAC 56 FAN FILTER UNIT HIGH EFFICIENCY Manual priceindustries com ...

Страница 59: ...IT HIGH EFFICIENCY INSTALLATION SERVICE INSTRUCTIONS WIRING DIAGRAM FFU 115 277V 1ø PSC STANDARD MOTOR WIRING DIAGRAM FFU 208 240V 1ø MOTOR STANDARD PSC 57 priceindustries com FAN FILTER UNIT HIGH EFFICIENCY Manual ...

Страница 60: ...ATION SERVICE INSTRUCTIONS WIRING DIAGRAM FFU HE 115 277V 1ø ECM MOTOR STANDARD ECM SPEED CONTROL ECMSC WIRING DIAGRAM FFU HE 115 277V 1ø ECM MOTOR DELUXE ECM SPEED CONTROL ECMDX 58 FAN FILTER UNIT HIGH EFFICIENCY Manual priceindustries com ...

Страница 61: ...STALLATION SERVICE INSTRUCTIONS WIRING DIAGRAM FFU HE 115 277V 1ø ECM MOTOR BACNET FLOW CONTROL BFC WIRING DIAGRAM FFU HE 240VV 1ø ECM MOTOR STANDARD ECM SPEED CONTROL ECMSC 59 priceindustries com FAN FILTER UNIT HIGH EFFICIENCY Manual ...

Страница 62: ...STALLATION SERVICE INSTRUCTIONS WIRING DIAGRAM FFU HE 240VV 1ø ECM MOTOR DELUXE ECM SPEED CONTROLLER ECMDX WIRING DIAGRAM FFU HE 240VV 1ø ECM MOTOR BACNET FLOW CONRTOLLER BFC 60 FAN FILTER UNIT HIGH EFFICIENCY Manual priceindustries com ...

Страница 63: ...place defective product at its option but will not be responsible for labour or material charges in replacing product or consequential damages Any installation not conforming with the Company s specifications manuals bulletins or instructions or any misuse or any modification not authorized by the Company voids this warranty This warranty is in lieu of all Provincial State and Federal statutory wa...

Страница 64: ...is document contains the most current product information as of this printing For the most up to date product information please go to priceindustries com 2016 Price Industries Limited All rights reserved ...