FAN FILTER UNIT - HIGH EFFICIENCY
INSTALLATION & SERVICE INSTRUCTIONS
STEP 3:
Raise the unit through ceiling grid at an angle until entire unit is above the ceiling grid
STEP 4:
Lower unit onto the backside of the tees.
STEP 5:
Secure the unit to the overhead structure using the eyebolts located on the back of the unit.
STEP 6:
Adjust and level the unit so that it rests on the tees and there is adequate compression on the gasket to warrant a tight
seal.
Ensure that ceiling grid is properly gasketed/sealed to prevent infiltration of unfiltered air from the ceiling plenum into the room side.
Above steps are manufacturer's suggested hanging techniques, always make sure to follow all local building codes, including
seismic, where applicable.
Unit Eyebolts for Mounting
5
priceindustries.com | FAN FILTER UNIT - HIGH EFFICIENCY - Manual