FAN FILTER UNIT - HIGH EFFICIENCY
INSTALLATION & SERVICE INSTRUCTIONS
STEP 15D:
Check airflow using flow hood and adjust ECM Setpoint as required until desired airflow is reached.
NOTE:
Before proceeding to next step, ensure unit is operating at desired airflow. Any changes to the airflow will require the filter
status to be reset.
STEP 16D:
To calibrate clean filter pressure drop, scroll, scroll through the ‘Service Menus’ until reaching ‘Filter’, select this menu
by pressing the ‘Enter/Menu’ button (far right).
STEP 17D:
Scroll through the ‘Filter’ menu until reaching ‘Reset Filter’ select by pressing the ‘Enter/Menu’ button.
Price FFU-HE-FE Points List
17
priceindustries.com | FAN FILTER UNIT - HIGH EFFICIENCY - Manual