AdvAntAge - digitAl vAv diffusers
PRODUCT OVERVIEW & INSTALLATION INSTRUCTIONS
5
acutherm.com
|
ACUTHERM ADVANTAGE - Manual
AdvAntAge series drOne
Advantage Series Drone Unit
Drone units contain actuators and
control circuitry to respond to signals
from the master unit. The damper
mechanism is synchronous with the
master unit. Up to five drones can be
supported by one master.
The geometry of the Master and
Drone do not need match. The four
different Advantage geometries (square,
round, swirl, and linear slot) can be
interchanged between Master and
Drone.
Balancing
To correctly balance a VAV diffuser, set the maximum flow, the diffuser must be in the 100% open position. The Advantage diffuser
may be opened to 100% by:
• Accessing the override open command using the menus availble on the LCD thermsotat
>Service Menu >Balanacing >Dpr Override >Goto Full Open (see Balancing Menu page 16)
• or, if the Advantage is on a BACnet network, setting AV25 to 6 (Damper Open 100%)
Maximum flow from the diffuser can also be limited by accessing the maximum damper position by:
• Accessing the damper maximum settings using the menus availble on the LCD thermsotat
>Service Menu >VVT >Dpr Cool Max or >Dpr Heat Max (see VVT Menu page 17)
• or, if the Advantage is on a BACnet network, setting AV22 Cool Max and AV24 Heat Max
To set the minimum flow from the diffuser, limit the minimum damper position by:
• Accessing the damper minimum settings using the menus availble on the LCD thermsotat
>Service Menu >VVT >Dpr Cool Min or >Dpr Heat Min (see VVT Menu page 17)
• or, if the Advantage is on a BACnet network, setting AV21 Cool Min and AV23 Heat Min
DRONE 3
DRONE 2
DRONE 1
MASTER
DRONE 5
DRONE 4