AdvAntAge - digitAl vAv diffusers
MAINTENANCE
33
acutherm.com
|
ACUTHERM ADVANTAGE - Manual
Advantage specifications
specifications
Advantage Master (ADVM)
Power supply
24 VAC (+-10%) 60Hz; Class 2
Power Consumption
3 VA for diffuser (+ Advantage Drones and any reheat load)
electrical Connection
2 position pluggable terminal block OR RJ12 jack from Power Module
Certification
ETL listed
Outputs
1 Binary Triac zero crossing output at 24 VAC (thermally protected) 12VA maximum
2x RJ12 jacks for Advantage Drone units (maximum 6 total per master)
input
1x RJ45 Thermostat jack (works with Price line of thermostats and Advantage ADVM jumper)
Communication
BACnet Master MS/TP module supports 9600/19200/38400/76800 baud rates, 2x RJ45 connections,
Green Transmit LED, Red Receive LED, MAC address settable through DIP switches or LCD thermostat,
Device Instance settable through LCD thermostat, or LINKER service tool.
Proportional Band
2.0°F (or 1.0°C) cooling and heating (adjustable via LCD thermostat or LINKER service tool)
Processor
8-bit 128kB flash based microcontroller with EEPROM
temperature sensors
10k NTC supply air temperature thermistor, 10k NTC Thermostat thermistor
temperature sensor range
-40°F - +175°F (-40.0°C - + 79.4°C)
Advantage drone specifications
Power supply
24 VAC (+-10%) 60Hz; Class 2 (supplied by Advantage Master via RJ12 cable (C35))
Power Consumption
3 VA
electrical Connection
RJ12 jack
Certification
ETL listed
Outputs
2x Binary 24 VAC for Damper Motor supplied via RJ12 (C35)
input
2 – 10 VDC signal (supplied by Advantage Master)