AdvAntAge - digitAl vAv diffusers
DISPLAY NAVIGATION
17
acutherm.com
|
ACUTHERM ADVANTAGE - Manual
vvt Menu
Pressure Dependent Mode
Scroll through with
Up
and
Down
buttons, press
Menu
button to apply your changes *---wait---* will display as changes are applied.
vvt
dPr. COOl Min*
0%
Cool Min flow
· Cool Min Flow in %
· Range: 0-100% Default: 0%
dPr. COOl MAX.*
100%
Cool Max flow
· Cool Min Flow in %
· Range: 0-100% Default: 100%
dPr. HeAt Min*
0%
Heat Min flow
· Heat Min Flow in %
· Range 0-100% Default: 0%
dPr.HeAt MAX*
100%
Heat Max flow
· Heat Max Flow in %
· Range 0-100% Default: 100%
dPr. neutrAl
0%
neutral flow
· Sets the neutral flow
· Range 0-100% Default: 0%
unOCC dPr POs*
0%
unocc dpr Pos
· When Advantage is unoccupied damper will ‘rest’ at this position
· Range: 0-100% Default: 0%
inlet siZe*
10 inCHes
inlet size
· Size of the diffuser inlet (factory set)
Press Menu
tO eXit
exit –
This will exit the info menu if you select Yes
Note: Info menu will automatically time out after 60 seconds
*
Also available over BACnet network if diffuser has BACnet option installed.