BACnet Wiring

Acutherm Advantage Diffusers, when selected with the 
optional BACnet interface, have the option of using supplied 
35’ CAT 5 cables to run BACnet MS/TP, or field supplied cable 
hardwired into a pluggable terminal block (see next page if 
using hardwired BACnet connections). The RJ-45 jacks for 
use with the supplied BACnet cables are directly tied to the 
pluggable terminal block, and so any combination of supplied 
cables and hardwired connections can be used on a single 
network segment. 

BACnet networks must be run in a daisy chain configuration, 
meaning there is only one main cable and each network device 
is connected directly along its path, with no more than 30 
devices per segment, and MS/TP segment lengths must not 
exceed 1 050 feet. 

termination

 

BACnet MS/TP networks must be terminated to ensure proper 
operation. A network should be terminated twice, once at 
the beginning and once at the end. Termination helps reduce 
reflections and noise. The terminating can be done with a 100 
ohm resistor across the + and - lines. Advantage Diffusers 
have the option for enabling termination via a DIP switch or by 
a software menu selection. Turning on termination via software 
will enable the resistor across the lines and also turn on a 
green LED labeled “TRM”. 

tech tip:

 The BACnet MS/TP to IP Router has built in 

termination and it is enabled by default (since the router is 
typically the beginning of the entire MS/TP network). Now you 
only have to go and find/terminate that last device.  

MAster JuCtiOn BrACKet   

eleCtriCAl nOise eXAMPle   

electrical noise

 

Electrical noise can affect both analog signal and digital communications such as BACnet. Therefore do not route high voltage 
lines next to the BACnet network! Avoid noisy electrical sources such as:
•  Variable Frequency Drives
•  High current power lines (main panel feeds)
•  Fluorescent light fixtures
If you must pass near noisy electrical lines cross at right angles. This will help reduce the amount of noise coupled to the network 

wires.

8 7 6 5 4 3 2 1

NET

IN

NET

OUT

BACnet to

next device

BACnet from

previous device

RX

TX

FAULT

Prodigy Master Top View of 

circuit board mounting bracket

DIP switches for 

MAC address 

and termination

RJ - 45

Jacks

HIGH VOLTAGE/ 

CURRENT LINE

BACNET NETWORK

Содержание acutherm Advantage

Страница 1: ...v200 Issue Date 01 29 21 2021 Acutherm All rights reserved MANUAL INSTALLATION Advantage Advantage Digital VAV Diffusers...

Страница 2: ...nformation Menu LCD Stats only 14 Service Menu LCD Stats only 15 Balancing Menu 16 VVT Menu Pressure Dependant Mode 17 Setpoint Menu Setpoint Limits and Temperature Units 18 Input Menu Supply Air Temp...

Страница 3: ...ing Notify carrier if external damage exists Submit all claims for shipping damage to the carrier 2 Move diffusers in cartons to installation area Note any unit identification 3 Remove cardboard box a...

Страница 4: ...ntage Diffuser require field connection of primary power supply and grounding Secondary power supply will be factory connected to pluggable 24 VAC PWR terminal block See Mounting Installation instruct...

Страница 5: ...gth may be extended by using a CC cable connector for longer runs A maximum of five ADVD can be supported by one Advantage Master ADVM Each ADVD draws 3 0 VA APM PPM 115 277 POWER SUPPLY ONE OUTPUT JA...

Страница 6: ...parameters of the diffuser NOTE When using the Room Sensor or Dial Thermostat order a LCD SET minimum of one per project to configure the diffuser Thermostat Adjustment VAV Cooling VAV Heating Connec...

Страница 7: ...override open command using the menus availble on the LCD thermsotat Service Menu Balanacing Dpr Override Goto Full Open see Balancing Menu page 16 or if the Advantage is on a BACnet network setting...

Страница 8: ...not specified Pulse Delay Modulation Reheat relay is on for a minimum of 2 minutes when required OFF Cycle is proportional to heating requirement Suitable for hydronic systems where entire system is...

Страница 9: ...or for longer runs Fig 6 page 3 CS Cable Splitters used to daisy chain power between masters Fig 6 page 3 Power switch with indicator LED Installation Instructions 1 Turn off power switch Remove cover...

Страница 10: ...r the PLD Advantage Linear Diffuser The Advantage Pressure Relief Collar PRC slips over the Advantage inlet to provide a simple and inexpensive method to control duct static pressure The PRC s dual sh...

Страница 11: ...ensing All master units have a temperature sensor located near the inlet for automatic heating cooling changeover For automatic changeover the Advantage uses a dynamic neutral mode for optimal use of...

Страница 12: ...Thermostat is powered from the controller Measures room temperature Set point can be adjusted from a hidden dial on the back of the T Stat using a small flat head screw driver Set point limits can be...

Страница 13: ...er the BACnet network The LCD Thermostat with Motion Sensor can be used as a balancing tool for the Intelligent Controller system by simply connecting the RJ 45 cable to the back of the thermostat Thi...

Страница 14: ...rtion of the thermostat firs and then snapping the bottom half in 3 All thermostats will come equipped with a 0 050 Allen key for the set screw at the bottom 1 25 32 Wall Fasteners by others Surface M...

Страница 15: ...crease push buttons for day set point adjustment DAY SETPOINT 75 0 F DAY SETPOINT SAVING CONTROLLER LCD THERMOSTAT STANDARD MODEL Displays firmware version of thermostat LCD THERMOSTAT VERSION X XX LO...

Страница 16: ...is present LCD will display No Probe If supply probe present LCD will display temperature DAMPER POS 50 Damper Position This indicates the current position of the damper in percent Range is 0 100 100...

Страница 17: ...tpoint Setup of Setpoint limits day minimum maximum F C selection See page 18 INPUT Input Shows supply air temperature reading Shows if VAV and BACnet modules are attached See page 19 OUTPUT Output Al...

Страница 18: ...damper full close PRESS MENU TO EXIT Exit This will exit the info menu if you select Yes Note Info menu will automatically time out after 60 seconds Balancing Menu Scroll through with Up and Down butt...

Страница 19: ...AT MIN 0 Heat Min Flow Heat Min Flow in Range 0 100 Default 0 DPR HEAT MAX 100 Heat Max Flow Heat Max Flow in Range 0 100 Default 100 DPR NEUTRAL 0 Neutral Flow Sets the neutral flow Range 0 100 Defau...

Страница 20: ...is heating setpoint when unoccupied Range 10 0 F 100 0 F Default 62 0 F NITE COOL SET 83 0 F Night Cool Setpoint Advantage will maintain this cooling setpoint when unoccupied Range 10 0 F 100 0 F Defa...

Страница 21: ...Switch set SAT temperature to enable heating Cold Switch set SAT temperature to enable cooling Neutral Mode Force Cool Locks the diffuser in the cooling mode Neutral Mode Force Heat Locks the diffuser...

Страница 22: ...hts When using Motion T Stat output controls room lights USED AS FORCE OFF Force Off Output de energized at all times USED AS FORCE ON Force On Output energized at all times REHEAT TYPE ON OFF Reheat...

Страница 23: ...tputs this voltage on Auxiliary Analog pin when there is a maximum call for cooling Default 10 0 VDC AUX HEAT MIN 0 0 VDC Auxiliary Heat min Voltage Outputs this voltage on Auxiliary Analog pin when t...

Страница 24: ...e only read on startup See Device Instance below and Addressing on page 29 30 DEVICE INST 101 Device Instance This is the software BACnet address MUST be unique on your building site Range 1 4 194 303...

Страница 25: ...low or Skys SOUND OPTIONS LIMITS ONLY Thermostat Sound Limits Only stat will beep when user tries to exceed a limit default All off beeper disabled All on stat will beep when user exceed a limit or st...

Страница 26: ...application model Square Round Swirl or Linear PRESS MENU TO EXIT CO2 Settings Menu Menu item will only appear if thermostat with CO2 sensor connected See thermostat with CO2 for more details Advanta...

Страница 27: ...r is a 35 foot plenum rated network cable to simplify installation in the field Local addresses can be set at each Advantage diffuser using the on board DIP switches The media access control MAC addre...

Страница 28: ...duce reflections and noise The terminating can be done with a 100 ohm resistor across the and lines Advantage Diffusers have the option for enabling termination via a DIP switch or by a software menu...

Страница 29: ...twisted pairs one for and one for NET COM Twisted pair and reference or 3 conductor Low capacitance 17pF or less Plenum rated FT6 CMP ratings 100 120 ohm Balanced CAT5 CAT5E CAT6 network cable has ex...

Страница 30: ...Service Menu Hold down the Menu button on the LCD Thermostat for 5 seconds until prompted for a passcode use and to enter the passcode DOWN UP UP DOWN The screen will now display Service Menu Applica...

Страница 31: ...t the same speed Price controllers are defaulted to a baud rate of 76800 but can be changed to 38400 19200 or 9600 For a network segment with all Acutherm controllers including Acutherm PRTU systems i...

Страница 32: ...is obtained NOTE Each device on a network segment must be set to run at the same speed or baud rate Description Default Value Factory Notes Mac Address 6 Value limited to 1 99 Tier 1 x100 58 Value lim...

Страница 33: ...Varies allow at least 5 minutes COLD Supply Air Temperature 2 F 1 C cooler than Room Temperature Adjust setpoint for maximum cooling ADV with Thermostat Adjustment setpoint dial Damper moves towards m...

Страница 34: ...some power cables to another jack Faulty Cable or Connector First Disconnect all cables and connectors originating from problem outlet Next Reconnect first C35 cable only If Red fault LED lights cabl...

Страница 35: ...ule supports 9600 19200 38400 76800 baud rates 2x RJ45 connections Green Transmit LED Red Receive LED MAC address settable through DIP switches or LCD thermostat Device Instance settable through LCD t...

Страница 36: ...ve Suite 280 Dublin CA 94568 USA Tel 1 510 785 0510 Send your questions to info acutherm com This document contains the most current product information as of this printing For the most up to date pro...

Отзывы: