6. Inspection, maintenance and desludging
Premier Tech
28 / 64
Solido SMART
DOKK5110E 15.04.2020
6.5
Evaluation of sludge level SSV90norm and recommendation for
desludging
For proper evaluation of SSV90
norm
sludge level calculate according to this formula:
SSV90
norm
= 0,95 x SSV30 x HR / HRmax
SSV90
norm
true sludge level in reactor after 90min of sedimentation
normalized / standardized to HRmax
0,95
factor for conversion of SSV30 to SSV90
(30 resp.90 min sedimentation
SSV30:
measurement of sludge level in reactor in 1+3 dilution after
30min sedimentation at current water level HR during service
HR:
current water level at service
HRmax:
max. reg. water level at full hydraulic load
(see table below)
Desludging is required when
SSV90
norm
= 700 ml/l
EXAMPLE
•
Type: EM2-35
•
HR at service: 1,16 m
•
HRmax according to table: 1,28 m
•
level in cylinder (30min): 130 ml (1+3)
(250ml 750ml clearwater)
•
SSV30 = 520 ml/l
(4x130)
•
SSV90
norm
= 0,95 x 520 x (1,16 / 1,28) ml/l
= 448 ml/l
➔
SSV90
norm
= 448 ml/l
➔
around 2/3 of total sludge storage volume capacity is currently filled