Configure / Setup    Discrete Outputs   

Parameter  Default 

Max. 

Min. 

Goto: Menu > Configure/Setup > Discrete Outputs 

40 

Disabled  AIN Error  Disabled 

ROUT 1 Function 

Disabled, Alarm 1, Alarm 2, Common Alarm, Horn, AIN Error 

41 

Disabled  AIN Error  Disabled 

ROUT 2 Function 

Disabled, Alarm 1, Alarm 2, Common Alarm, Horn, AIN Error. 

42 

Disabled  AIN Error  Disabled 

DOUT 1 Function 

Disabled, Alarm 1, Alarm 2, Common Alarm, Horn, AIN Error 

43 

Disabled  AIN Error  Disabled 

DOUT 2 Function 

Disabled, Alarm 1, Alarm 2, Common Alarm, Horn, AIN Error

 

NOTE:

   “Horn” is Off after Alarm(s) are silenced. 

 

“AIN Error” means mA/Vdc Out of Range, T/C Open, Thermistor Shorted, or other A/D malfunction

 

 
 
 
 
 
 

Modbus Communications 

 
RS485 Baud: 

4800, 9600, 19200, 38400, 57600 

RS485 Parity: 

Odd, Even, None  

Ethernet: 

10/100 Mb/s 

Protocol: 

RTU 

Address: 

1-247 

Register Formats: 

16 bit signed Integer, 32 bit signed Integer, 32 bit Floating Point 

Modbus Commands:   01 Read Coils, 03 Read Registers, 05 Write Single Coil, 06 Write Single Register,  
                                    16 Write Multiple Registers (2 registers max) 

Max Poll Size: 

120 coils or registers (except Code 16) 

 

Coil 

 

0 =

 

1 =

 

Description

 

98 

WO 

 

Alarm Silence 

Remote Alarm Silence 

99 

RO 

No Alarm 

Alarm 

Common Alarm 

101 

RO 

No Alarm 

Alarm 

Alarm 1 

102 

RO 

No Alarm 

Alarm 

Alarm 2 

 

 

 

 

 

Register 

 

Type 

 

Description 

40100 

RO 

FLOAT 

 

Process Variable 

40102 

RO 

FLOAT 

 

Alarm 1 Setpoint 

40104 

RO 

UINT8 

Enumeration 

Alarm1 Type: 

0=Disabled, 1=LoLo, 2=Lo, 3=Hi, 4=HiHi 

40105 

RO 

FLOAT 

 

Alarm 2 Setpoint 

40107 

RO 

UINT8 

Enumeration 

Alarm 2 Type: 

0=Disabled, 1=LoLo, 2=Lo, 3=Hi, 4=HiHi 

40108 

RO 

UINT32 

 

Totalizer Count 

 
 

 

 

Содержание JC-10D2

Страница 1: ...50 pt Alarm Event History Time Date Stamped Only 4 7 8 deep fits in most existing burner control cabinets Plug in field wiring terminals Modbus TCP Ethernet Modbus RTU RS485 USB port for configuratio...

Страница 2: ...e PV value The alarm setpoints are indicated on the bargraph with tic marks If the PV exceeds a Hi or HiHi Setpoint for more than 30 seconds adjustable the bargraph blinks the High or High High Alarm...

Страница 3: ...e delay expired and the alarm triggered When the Alarms screen is displayed History and Back are displayed Touch History to display the History screen Touch Home return to the Home screen History Scre...

Страница 4: ...noisy and should be kept away from the thermocouple extension wire and also all other AC and DC wiring If the 4 20 mA output will not be used jumper terminal 40 to 41 to prevent the OUTPUT FAILURE er...

Страница 5: ...r Fuse JC 10D2 31 34 33 A D 2 Wire 4 20 mA Xmtr INPUT TYPE mA Thermistor Fuse 24V JC 10D2 Thermocouple and Thermistor Field Wiring Notes Do not run in conduits with AC wiring Do not run in conduits wi...

Страница 6: ...its Upper Range Display Lower Range Display Square Root Option Totalizer Setup Pasword Enter Change Logout Screen Settings Brightness Touch Buzzer Alarm Buzzer Totalizer Setup Totalizer Option Zero Bu...

Страница 7: ...abled HiHi Disabled Alarm 2 Type Disabled LoLo Lo Hi HiHi 12 Auto Manual Auto Alarm 2 Reset Type Auto Manual Configure Setup Analog Input Setup Parameter Default Max Min Goto Menu Configure Setup Anal...

Страница 8: ...0 0 0 Low Flow Cutoff Input Rates below this value will not be totalized Typically used to prevent false totalization due to Xmtr Zero Calibration drift Configure Setup Bargraph Range Parameter Defau...

Страница 9: ...on Modbus Communications RS485 Baud 4800 9600 19200 38400 57600 RS485 Parity Odd Even None Ethernet 10 100 Mb s Protocol RTU Address 1 247 Register Formats 16 bit signed Integer 32 bit signed Integer...