SAFETY 

 

 

DANGER

 

Electric Shock Hazard

 

Multiple power sources may be present.  

Disconnect all electric power sources, local and remote, before servicing 

 

WARNING 

This product is intended for use in Commercial and Industrial installations,  

it is NOT intended for Residential use. 

This product is intended to be used by Trained Operators.  

 

Installation, start-up, and troubleshooting is intended to be done by  

Experienced Technicians familiar with Industrial Safety Codes  

and all Safety Codes specific to burners and boilers. 

  

This product is NOT a Primary Safety Interlock rated device.  

The Shutdown Relay Output should only be used as an  

additional auxiliary Operating limit and should not replace or bypass 

 any Primary Safety Interlock devices required by Safety Codes.  

 

Incorrect wiring connections to burner/boiler Flame Safeguard controls  

can cause Equipment Damage, Injury, or Death 

 

 
 

 
 

Alarm Sequence 

The Bargraph and Numeric display continuously indicate the AIN Process Variable (PV) value. The alarm setpoints are indicated 
on the bargraph with tic marks. If the PV exceeds a Hi (or HiHi)  Setpoint for more than 30 seconds (adjustable), the bargraph 
blinks, the High (or High-High) Alarm message appears, the Common Alarm Relay energizes, and the current PV is logged with 
a time/date stamp. Similarly for a Lo or LoLo Alarm. Pressing the ALARM SILENCE button de-energizes a Common Alarm 
output ROUT or 24 Vdc sinking DOUT.   
 
The Common Alarm output can be used to activate an external bell or horn. If the 

JC-10D2

 is alarm is configured as Auto Reset, 

the Alarm Output and Common Alarm output de-energize automatically when the PV drops below the (Alarm setpoint - the user 
set Deadband). Alternately, pressing the 

JC-10D2 

Alarm Silence pushbutton, or energizing an Alarm Silence input or sending a 

Modbus command will de-energize the Common Alarm Relay in order to silence an audible alarm.  
 
The Lo and LoLo alarms work in a similar manner. When PV drops below the SP the alarm is triggered. When PV rises above  
(SP + user set Deadband), the Alarm is cleared. 
 
If the Manual Reset option is selected, an alarm will not clear BOTH the PV returns to normal AND the user presses the RESET 
“button” on the touchscreen.

 

 

 

Содержание JC-10D2

Страница 1: ...50 pt Alarm Event History Time Date Stamped Only 4 7 8 deep fits in most existing burner control cabinets Plug in field wiring terminals Modbus TCP Ethernet Modbus RTU RS485 USB port for configuratio...

Страница 2: ...e PV value The alarm setpoints are indicated on the bargraph with tic marks If the PV exceeds a Hi or HiHi Setpoint for more than 30 seconds adjustable the bargraph blinks the High or High High Alarm...

Страница 3: ...e delay expired and the alarm triggered When the Alarms screen is displayed History and Back are displayed Touch History to display the History screen Touch Home return to the Home screen History Scre...

Страница 4: ...noisy and should be kept away from the thermocouple extension wire and also all other AC and DC wiring If the 4 20 mA output will not be used jumper terminal 40 to 41 to prevent the OUTPUT FAILURE er...

Страница 5: ...r Fuse JC 10D2 31 34 33 A D 2 Wire 4 20 mA Xmtr INPUT TYPE mA Thermistor Fuse 24V JC 10D2 Thermocouple and Thermistor Field Wiring Notes Do not run in conduits with AC wiring Do not run in conduits wi...

Страница 6: ...its Upper Range Display Lower Range Display Square Root Option Totalizer Setup Pasword Enter Change Logout Screen Settings Brightness Touch Buzzer Alarm Buzzer Totalizer Setup Totalizer Option Zero Bu...

Страница 7: ...abled HiHi Disabled Alarm 2 Type Disabled LoLo Lo Hi HiHi 12 Auto Manual Auto Alarm 2 Reset Type Auto Manual Configure Setup Analog Input Setup Parameter Default Max Min Goto Menu Configure Setup Anal...

Страница 8: ...0 0 0 Low Flow Cutoff Input Rates below this value will not be totalized Typically used to prevent false totalization due to Xmtr Zero Calibration drift Configure Setup Bargraph Range Parameter Defau...

Страница 9: ...on Modbus Communications RS485 Baud 4800 9600 19200 38400 57600 RS485 Parity Odd Even None Ethernet 10 100 Mb s Protocol RTU Address 1 247 Register Formats 16 bit signed Integer 32 bit signed Integer...

Страница 10: ...EL D4B Adapter Plate Panel Cutout 8 00 X 10 75 Specifications Mechanical Enclosure Nema 12 Faceplate Indoor Locations Bezel 3 7 8 w x 8 h x 1 d Rear Case 3 1 2 w x 7 9 16 h x 4 7 8 d Panel Cutout 3 6...

Страница 11: ...SDI JC 10D2 rev 11 17 21 page 11 of 12 Full Size Template 3 61 7 65 Edge of Faceplate outside of panel Mounting Bracket inside of panel JC 30D2 Panel Cutout...

Страница 12: ...SDI JC 10D2 rev 11 17 21 page 12 of 12 Preferred Utilities Mfg Corp Preferred Instruments div 31 35 South Street Danbury CT 06810 203 743 6741 www preferred mfg com...

Отзывы: