Preferred JC-10D2 Скачать руководство пользователя страница 4

 

SDI-JC-10D2   rev 11-17-21

 

 

page 4  of  12 

Installation 

 

JC-10D2 Indicator Mounting: 

The JC-10D2 Indicator is designed for flush mounting in an 

enclosure located in an indoor NEMA 12 environment.  

 
The JC-10D2 should not be subjected to excessive vibration. 

Continuous operation is guaranteed over the 32-131 F  
(0-55C) ambient operating range.  

 
See Full Size Cutout Template on the last page 
 

 
Wiring: 

Warning 

Disconnect all sources of power before installing or servicing this equipment. Multiple Disconnects may be required. 
Burner interface wiring must be performed by an experienced burner service technician.  

 

All wiring must comply with all local and national electrical codes. Tighten all terminals to 4.4 in-lb. Wire must be stranded copper, 
12-24 ga., 150V / 75 C insulation minimum. AC and DC wiring must be separated to prevent electrical noise coupling. Do not run 
AC and DC wires in the same conduits. Use shielded cables where shown, connect shields only where shown, insulate all other 
shields to prevent accidental grounding. Ignition transformer and motor VFD wiring are particularly electrically noisy and should be 
kept away from the thermocouple extension wire, and also all other AC and DC wiring. 

 

If the 4-20 mA output will not be used, jumper terminal 40 to 41 to prevent the OUTPUT FAILURE error message. 

 

Relay contacts are shown with power removed from the JC-10D2.  

 

All DC wiring is isolated from Ground. All DC wiring '-' terminals are connected together internally.  

 

RS485 is electrically Isolated from all other DC and AC wiring. 

 

Terminals 1-9 are Line Voltage AC. Terminals 31-50 are low voltage DC. 

 

 An external Line Voltage supply switch or circuit breaker, marked as the disconnect for this instrument, suitably located 
and easily reached, and complying with IEC 60947-1 and -3 must be provided. 

 

Fuse:

 

3.15 amp Slo-Blo, 250 V, 5x20mm (Littlefuse 02153.15HXP, Belfuse 5ST 3.15-R, Preferred Utilities 16740-3.15S) 

Caution

: To reduce the risk of fire, only replace fuse with the same type. 

 
 

 

 

JC-10D2   Monitor

40
41

-

 

+

 4-20 mA

L1

N

N

H

120 Vac

26 VA

50/60 Hz

Optional

Contact

Closure

Inputs

45
47
49

RS485 +
RS485 -
Common

Ethernet

43

(24 Vdc)

7 ACDIN 1
8 ACDIN 2

31 +24V
32 +2.5Vref
34 AIN 1
33 DC -

44 DCDIN 1

46 DCDIN 2

DC -

(24 Vdc)

(120 Vac)

1
2
3

Relay 1

6

5

4

Relay 2

Sensor or

Transmitter

Input

(see next page)

Panel Cutout

3.61 x 7.65

3.88

8.00

Touch

Screen

8.74

Pl

ug

-in

 T

er

m

in

al

s

1.00

4.88

Pl

ug

-in

 T

er

m

in

al

s

Содержание JC-10D2

Страница 1: ...50 pt Alarm Event History Time Date Stamped Only 4 7 8 deep fits in most existing burner control cabinets Plug in field wiring terminals Modbus TCP Ethernet Modbus RTU RS485 USB port for configuratio...

Страница 2: ...e PV value The alarm setpoints are indicated on the bargraph with tic marks If the PV exceeds a Hi or HiHi Setpoint for more than 30 seconds adjustable the bargraph blinks the High or High High Alarm...

Страница 3: ...e delay expired and the alarm triggered When the Alarms screen is displayed History and Back are displayed Touch History to display the History screen Touch Home return to the Home screen History Scre...

Страница 4: ...noisy and should be kept away from the thermocouple extension wire and also all other AC and DC wiring If the 4 20 mA output will not be used jumper terminal 40 to 41 to prevent the OUTPUT FAILURE er...

Страница 5: ...r Fuse JC 10D2 31 34 33 A D 2 Wire 4 20 mA Xmtr INPUT TYPE mA Thermistor Fuse 24V JC 10D2 Thermocouple and Thermistor Field Wiring Notes Do not run in conduits with AC wiring Do not run in conduits wi...

Страница 6: ...its Upper Range Display Lower Range Display Square Root Option Totalizer Setup Pasword Enter Change Logout Screen Settings Brightness Touch Buzzer Alarm Buzzer Totalizer Setup Totalizer Option Zero Bu...

Страница 7: ...abled HiHi Disabled Alarm 2 Type Disabled LoLo Lo Hi HiHi 12 Auto Manual Auto Alarm 2 Reset Type Auto Manual Configure Setup Analog Input Setup Parameter Default Max Min Goto Menu Configure Setup Anal...

Страница 8: ...0 0 0 Low Flow Cutoff Input Rates below this value will not be totalized Typically used to prevent false totalization due to Xmtr Zero Calibration drift Configure Setup Bargraph Range Parameter Defau...

Страница 9: ...on Modbus Communications RS485 Baud 4800 9600 19200 38400 57600 RS485 Parity Odd Even None Ethernet 10 100 Mb s Protocol RTU Address 1 247 Register Formats 16 bit signed Integer 32 bit signed Integer...

Страница 10: ...EL D4B Adapter Plate Panel Cutout 8 00 X 10 75 Specifications Mechanical Enclosure Nema 12 Faceplate Indoor Locations Bezel 3 7 8 w x 8 h x 1 d Rear Case 3 1 2 w x 7 9 16 h x 4 7 8 d Panel Cutout 3 6...

Страница 11: ...SDI JC 10D2 rev 11 17 21 page 11 of 12 Full Size Template 3 61 7 65 Edge of Faceplate outside of panel Mounting Bracket inside of panel JC 30D2 Panel Cutout...

Страница 12: ...SDI JC 10D2 rev 11 17 21 page 12 of 12 Preferred Utilities Mfg Corp Preferred Instruments div 31 35 South Street Danbury CT 06810 203 743 6741 www preferred mfg com...

Отзывы: