Preferred JC-10D2 Скачать руководство пользователя страница 3

 

SDI-JC-10D2   rev 11-17-21

 

 

page 3  of  12 

Operation

 

Home 

Screen

 

The sensor/xmtr Process Value (PV) is displayed at the top. The bargraph height varies in 
proportion to the PV. The lines on the right side of the bargraph are the Alarm setpoints. 

 

The lower left button on all screens indicates one of these three words:  
                   

Silence   

or

  Alarms 

 or  

History

 

 

When a new Alarm occurs, 

Silence 

and the bargraph blink, and the Common Alarm Relay 

Output energizes. Touch 

Silence 

to stop the blinking and to de-energize the Alarm Relay. 

Alarms

 is displayed after silencing if an Alarm is still active. 

History

 is displayed when there are no active Alarms. 

 
If an alarm is configured as Manual Reset, the 

RESET

 button will be displayed after going into 

Alarm. When the PV is below the Setpoint, the RESET button must be touched to cancel the 
Alarm. 
 
 

Alarms 

Screen

 

From any other screen, touch the 

Alarms

 button to display the Active Alarms Screen. 

If there are no active Alarms, 

Alarms

 will not be displayed on the Main and Menu screens.  

  
All active Alarms are displayed on this screen: High Alarm, High-High Alarm, etc….   
 
The PV and time/date shown occurred when the Alarm time delay expired, and the alarm 

triggered. 

 
When the Alarms screen is displayed, 

History

 and 

Back

 are displayed.  

Touch 

History

 to display the History screen. 

Touch 

Home

 return to the Home screen.  

 
 

History 

Screen

 

Touch 

History

 to display the History screen. 

 

 
The History screen displays the Time/Date of the most recent 50 Alarms and Events. 
Events include: Peak Input Value,

 

Alarm Clear, Manual Reset, JC-10D2 power-up, etc.. 

 
Touch the 

Up

 or 

Down arrow

 to advance to the next page of History.  

Touch 

Date

 to enter a time/date and then to jump to the nearest History records. 

 
The 

Hide Events 

and 

Show Events

 removes or displays Events. 

 
The History memory is retained when powered down. The History can be extracted via the 
USB port using the free JC_D2Edit PC software. 

 

 

Menu

 Screens 

To set clock, Alarm Setpoints, and other initial Setup…..See Menu Map on page 6 

Home

History

High Flue Temp. SHUTDOWN

432 F RESET REQ’D

            16:30:02

    8/17 

High Flue Temp. Warning 

382 F WARNING

            16:23:59

    8/17

 Active Alarms

0

125

250

375

500

FL

UE

 G

AS

   

F

433

History

Alarms

R

E

S

E

T

Silence

Menu

High Flue Temp. Shutdown

197 F RESET

            17:21:12

     8/17 

High Flue Temp. Warning

375 F CLEAR

            16:48:01

     8/17

Peak Temp.

467F

            16:33:07

     8/17

High Flue Temp. Shutdown

432 F SHUTDOWN

            16:30:02

     8/17 

High Flue Temp. Warning 

382 F WARNING

            16:23:59

     8/17 

 History

Alarms

Silence

Home

Date

Hide 

Events

Show

Events

Содержание JC-10D2

Страница 1: ...50 pt Alarm Event History Time Date Stamped Only 4 7 8 deep fits in most existing burner control cabinets Plug in field wiring terminals Modbus TCP Ethernet Modbus RTU RS485 USB port for configuratio...

Страница 2: ...e PV value The alarm setpoints are indicated on the bargraph with tic marks If the PV exceeds a Hi or HiHi Setpoint for more than 30 seconds adjustable the bargraph blinks the High or High High Alarm...

Страница 3: ...e delay expired and the alarm triggered When the Alarms screen is displayed History and Back are displayed Touch History to display the History screen Touch Home return to the Home screen History Scre...

Страница 4: ...noisy and should be kept away from the thermocouple extension wire and also all other AC and DC wiring If the 4 20 mA output will not be used jumper terminal 40 to 41 to prevent the OUTPUT FAILURE er...

Страница 5: ...r Fuse JC 10D2 31 34 33 A D 2 Wire 4 20 mA Xmtr INPUT TYPE mA Thermistor Fuse 24V JC 10D2 Thermocouple and Thermistor Field Wiring Notes Do not run in conduits with AC wiring Do not run in conduits wi...

Страница 6: ...its Upper Range Display Lower Range Display Square Root Option Totalizer Setup Pasword Enter Change Logout Screen Settings Brightness Touch Buzzer Alarm Buzzer Totalizer Setup Totalizer Option Zero Bu...

Страница 7: ...abled HiHi Disabled Alarm 2 Type Disabled LoLo Lo Hi HiHi 12 Auto Manual Auto Alarm 2 Reset Type Auto Manual Configure Setup Analog Input Setup Parameter Default Max Min Goto Menu Configure Setup Anal...

Страница 8: ...0 0 0 Low Flow Cutoff Input Rates below this value will not be totalized Typically used to prevent false totalization due to Xmtr Zero Calibration drift Configure Setup Bargraph Range Parameter Defau...

Страница 9: ...on Modbus Communications RS485 Baud 4800 9600 19200 38400 57600 RS485 Parity Odd Even None Ethernet 10 100 Mb s Protocol RTU Address 1 247 Register Formats 16 bit signed Integer 32 bit signed Integer...

Страница 10: ...EL D4B Adapter Plate Panel Cutout 8 00 X 10 75 Specifications Mechanical Enclosure Nema 12 Faceplate Indoor Locations Bezel 3 7 8 w x 8 h x 1 d Rear Case 3 1 2 w x 7 9 16 h x 4 7 8 d Panel Cutout 3 6...

Страница 11: ...SDI JC 10D2 rev 11 17 21 page 11 of 12 Full Size Template 3 61 7 65 Edge of Faceplate outside of panel Mounting Bracket inside of panel JC 30D2 Panel Cutout...

Страница 12: ...SDI JC 10D2 rev 11 17 21 page 12 of 12 Preferred Utilities Mfg Corp Preferred Instruments div 31 35 South Street Danbury CT 06810 203 743 6741 www preferred mfg com...

Отзывы: