SDI-JC-10D2 rev 11-17-21
page 7 of 12
Screen Settings
Parameter Default
Max.
Min.
Goto: Menu > Utilities > Screen Settings
1
Enable Enable Disable
Touch Buzzer Enable
Activates faceplate Tone when a screen item is touched
2
Disable Enable Disable
Alarm Buzzer Enable
Activates faceplate Tone when an Alarm is triggered.
Alarms
Parameter Default
Max.
Min.
Goto: Menu > Alarms
3
100.0
999999 -999999
Alarm 1 Setpoint
4
5
3600
0
Alarm 1 Delay Sec
5
1.0
99999
0
Alarm 1 Deadband
6
0.0
999999 -999999
Alarm 2 Setpoint
7
5
3600
0
Alarm 2 Delay Sec
8
1.0
99999
0
Alarm 2 Deadband
Alarm Types
Parameter Default
Max.
Min.
Goto: Menu > Alarms > Alarm Types
9
Disabled
HiHi
Disabled
Alarm 1 Type
Disabled, LoLo, Lo, Hi, HiHi
10
Auto
Manual
Auto
Alarm 1 Reset Type
Auto, Manual
11
Disabled
HiHi
Disabled
Alarm 2 Type
Disabled, LoLo, Lo, Hi, HiHi
12
Auto
Manual
Auto
Alarm 2 Reset Type
Auto, Manual
Configure / Setup Analog Input Setup
Parameter Default
Max.
Min.
Goto: Menu > Configure/Setup > Analog Input Setup
13
Input Name
User entered Text, Max. 12 characters
14
4-20 mA 2.3 Volt 4-20 mA
Input Type
4-20 mA, 10K Thermistor, Type J Thermocouple, Type K Thermocouple, 10 Volt, 5 Volt,
2.3 Volt
15
2.0
30.0
0.5
Smoothing Filter Seconds
Dampens (smooths) rapid signal variations.
Larger values = more damping. Smaller values = less damping.
16
Input Units
User entered Text, Max. 8 characters
17
F
C
F
Temperature F/C
F or C (Only used for T/C and Thermistor Input Types)
18
0.0
+15.0
-15.0
Temperature Adjust
(degrees)
The displayed value is offset from the measured value by this amount for all temperatures.
Used to calibrate out minor temperature differences due to sensor errors. The units are F or C,
as selected above. (Only used for T/C and Thermistor Input Types)