Configure / Setup mA/Vdc Scaling
Parameter Default
Max.
Min.
Goto: Menu > Configure/Setup > Analog Input Setup > mA/Vdc Scaling
NOTE:
None of these Parameters are used for T/C and Thermistor Input Types
19
20.0
23.5
-0.5
Upper Range mA/Vdc
20
4.0
23.5
-0.5
Lower Range mA/Vdc
21
1
3
0
Display Decimal Digits
22
100.0
999999 -999999
Upper Range Scaled Display
.
23
0.0
999999 -999999
Lower Range Scaled Display
24
Disabled Enabled Disabled
Square Root Option
Disabled, Enabled
Configure / Setup Totalizer Setup
Parameter Default
Max.
Min.
Goto: Menu > Configure/Setup > Analog Input Setup > mA/Vdc Scaling > Totalizer Setup
NOTE:
None of these Parameters are used for T/C and Thermistor Input Types
25
Disabled Enabled Disabled
Totalizer Option
26
Disabled Enabled Disabled
Zero Button Option
Totalized values can be reset to zero when User presses this button.
27
/Hour
/Day
/Minute
Rate Time Base
/Minute, /Hour, /Day Examples: gpm, use /Minute \ gph, use /Hour \ gal/day, use /Day
28
x1
x1000000
x1
Rate Multiplier
x1 x10,x100,x1000,x10000,x100000,x1000000 Example: 0-5 kscf/hr & x1000, 1 count = 1scf
29
Totalized Units
User entered Text,
Max. 8 characters
30
0.0
99999.0
0.0
Low Flow Cutoff
Input Rates below this value will not be totalized.
Typically used to prevent false totalization due to Xmtr Zero Calibration drift.
Configure / Setup Bargraph Range
Parameter Default
Max.
Min.
Goto: Menu > Configure/Setup > Bargraph
31
0
3
0
Bargraph Tick Dec Pt
32
100.0
999.9
-999.9
Bargraph Top
This is the temperature value at the top of the bargraph.
The units are F or C, as selected above.
33
0.0
999.9
-999.9
Bargraph Bottom
This is the temperature value at the bottom of the bargraph.
The units are F or C, as selected above.
Configure / Setup 4-20 mA Output
Parameter Default
Max. Min.
Goto: Menu > Configure/Setup > 4-20 Output
34
100.0
99999.9 -99999.9
20 mA =
This is the scaled Input value for 20 mA output.
35
0.0
99999.9 -99999.9
4 mA =
This is the scaled Input value for 4 mA output.
Configure / Setup Discrete Inputs
Parameter Default
Max.
Min.
Goto: Menu > Configure/Setup > Discrete Inputs
36
Disabled
Totalizer
Disable
Disabled
AC DIN 1 Function
Disabled, Alarm Silence, Totalizer Enable, Totalizer Disable
37
Disabled
Totalizer
Disable
Disabled
AC DIN 2 Function
Disabled, Alarm Silence, Totalizer Enable, Totalizer Disable
38
Disabled
Totalizer
Disable
Disabled
DC DIN 1 Function
Disabled, Alarm Silence, Totalizer Enable, Totalizer Disable
39
Disabled
Totalizer
Disable
Disabled
DC DIN 2 Function
Disabled, Alarm Silence, Totalizer Enable, Totalizer Disable