Preferred JC-10D2 Скачать руководство пользователя страница 8

 

SDI-JC-10D2   rev 11-17-21

 

 

page 8  of  12 

Configure / Setup     mA/Vdc Scaling 

 

Parameter  Default 

Max. 

Min. 

Goto: Menu > Configure/Setup > Analog Input Setup > mA/Vdc Scaling 

NOTE:

 None of these Parameters are used for T/C and Thermistor Input Types 

19 

20.0 

23.5 

-0.5 

Upper Range mA/Vdc 

 

20 

4.0 

23.5 

-0.5 

Lower Range mA/Vdc 

 

21 

Display Decimal Digits

 

 

22 

100.0 

999999  -999999 

Upper Range Scaled Display    

 . 

23 

0.0 

999999  -999999 

Lower Range Scaled Display

 

  

24 

Disabled  Enabled  Disabled 

Square Root Option

 

Disabled, Enabled 

 

Configure / Setup     Totalizer Setup 

 

Parameter  Default 

Max. 

Min. 

Goto: Menu > Configure/Setup > Analog Input Setup > mA/Vdc Scaling > Totalizer Setup 

NOTE:

 None of these Parameters are used for T/C and Thermistor Input Types

 

25 

Disabled  Enabled  Disabled 

Totalizer Option 

 

26 

Disabled  Enabled  Disabled 

Zero Button Option 

Totalized values can be reset to zero when User presses this button. 

27 

/Hour 

/Day 

/Minute 

Rate Time Base

 

/Minute, /Hour, /Day    Examples: gpm, use /Minute \ gph, use /Hour \ gal/day, use /Day 

28 

x1 

x1000000 

x1 

Rate Multiplier   

x1 x10,x100,x1000,x10000,x100000,x1000000  Example: 0-5 kscf/hr & x1000, 1 count = 1scf  

29 

 

 

 

Totalized Units

 

User entered Text,

 

Max. 8 characters 

30 

0.0 

99999.0 

0.0 

Low Flow Cutoff

 

Input Rates below this value will not be totalized. 
Typically used to prevent false totalization due to Xmtr Zero Calibration drift. 

 

Configure / Setup    Bargraph Range  

Parameter  Default 

Max. 

Min. 

Goto: Menu > Configure/Setup > Bargraph 

31 

Bargraph Tick Dec Pt

 

 

32 

100.0 

999.9 

-999.9 

Bargraph Top 

This is the temperature value at the top of the bargraph. 
The units are F or C, as selected above. 

33 

0.0 

999.9 

-999.9 

Bargraph Bottom 

This is the temperature value at the bottom of the bargraph. 
The units are F or C, as selected above. 

 
Configure / Setup    4-20 mA Output 

Parameter  Default 

Max.  Min. 

Goto: Menu > Configure/Setup > 4-20 Output 

34 

100.0 

99999.9  -99999.9 

20 mA = 

This is the scaled Input value for 20 mA output.

 

35 

0.0 

99999.9  -99999.9 

4 mA =      

This is the scaled Input value for  4 mA output.

 

 

Configure / Setup    Discrete Inputs  

Parameter  Default 

Max. 

Min. 

Goto: Menu > Configure/Setup > Discrete Inputs 

36 

Disabled 

Totalizer 

Disable 

Disabled 

AC DIN 1 Function

 

Disabled, Alarm Silence, Totalizer Enable, Totalizer Disable 

37 

Disabled 

Totalizer 

Disable 

Disabled 

AC DIN 2 Function 

Disabled, Alarm Silence, Totalizer Enable, Totalizer Disable 

38 

Disabled 

Totalizer 

Disable 

Disabled 

DC DIN 1 Function 

Disabled, Alarm Silence, Totalizer Enable, Totalizer Disable 

39 

Disabled 

Totalizer 

Disable 

Disabled 

DC DIN 2 Function

 

Disabled, Alarm Silence, Totalizer Enable, Totalizer Disable

 

Содержание JC-10D2

Страница 1: ...50 pt Alarm Event History Time Date Stamped Only 4 7 8 deep fits in most existing burner control cabinets Plug in field wiring terminals Modbus TCP Ethernet Modbus RTU RS485 USB port for configuratio...

Страница 2: ...e PV value The alarm setpoints are indicated on the bargraph with tic marks If the PV exceeds a Hi or HiHi Setpoint for more than 30 seconds adjustable the bargraph blinks the High or High High Alarm...

Страница 3: ...e delay expired and the alarm triggered When the Alarms screen is displayed History and Back are displayed Touch History to display the History screen Touch Home return to the Home screen History Scre...

Страница 4: ...noisy and should be kept away from the thermocouple extension wire and also all other AC and DC wiring If the 4 20 mA output will not be used jumper terminal 40 to 41 to prevent the OUTPUT FAILURE er...

Страница 5: ...r Fuse JC 10D2 31 34 33 A D 2 Wire 4 20 mA Xmtr INPUT TYPE mA Thermistor Fuse 24V JC 10D2 Thermocouple and Thermistor Field Wiring Notes Do not run in conduits with AC wiring Do not run in conduits wi...

Страница 6: ...its Upper Range Display Lower Range Display Square Root Option Totalizer Setup Pasword Enter Change Logout Screen Settings Brightness Touch Buzzer Alarm Buzzer Totalizer Setup Totalizer Option Zero Bu...

Страница 7: ...abled HiHi Disabled Alarm 2 Type Disabled LoLo Lo Hi HiHi 12 Auto Manual Auto Alarm 2 Reset Type Auto Manual Configure Setup Analog Input Setup Parameter Default Max Min Goto Menu Configure Setup Anal...

Страница 8: ...0 0 0 Low Flow Cutoff Input Rates below this value will not be totalized Typically used to prevent false totalization due to Xmtr Zero Calibration drift Configure Setup Bargraph Range Parameter Defau...

Страница 9: ...on Modbus Communications RS485 Baud 4800 9600 19200 38400 57600 RS485 Parity Odd Even None Ethernet 10 100 Mb s Protocol RTU Address 1 247 Register Formats 16 bit signed Integer 32 bit signed Integer...

Страница 10: ...EL D4B Adapter Plate Panel Cutout 8 00 X 10 75 Specifications Mechanical Enclosure Nema 12 Faceplate Indoor Locations Bezel 3 7 8 w x 8 h x 1 d Rear Case 3 1 2 w x 7 9 16 h x 4 7 8 d Panel Cutout 3 6...

Страница 11: ...SDI JC 10D2 rev 11 17 21 page 11 of 12 Full Size Template 3 61 7 65 Edge of Faceplate outside of panel Mounting Bracket inside of panel JC 30D2 Panel Cutout...

Страница 12: ...SDI JC 10D2 rev 11 17 21 page 12 of 12 Preferred Utilities Mfg Corp Preferred Instruments div 31 35 South Street Danbury CT 06810 203 743 6741 www preferred mfg com...

Отзывы: