Page 9
For technical questions, please call 1-888-866-5797.
ITEM 59205
SAFETY
SETU
p
Op
ERA
TION
M
AINTENANCE
Initial Tool Set Up/Assembly
Read the ENTIRE IMpORTANT SAFETY INFORMATION section at the beginning of this
manual including all text under subheadings therein before set up or use of this product.
TO pREVENT SERIOUS INJURY:
Operate only with proper spark arrestor installed.
Operation of this equipment may create sparks that can start fires around dry vegetation.
A spark arrestor may be required. The operator should contact local fire agencies
for laws or regulations relating to fire prevention requirements.
At high altitudes, the engine’s carburetor, governor, and any other parts that control the fuel-
air ratio will need to be adjusted by a qualified mechanic to allow efficient high-altitude use
and to prevent damage to the engine and any other devices used with this product.
Note:
For additional information regarding the parts listed in the following pages,
refer to the Assembly Diagram near the end of this manual.
NOTICE:
This Generator is not intended to power sensitive electronic equipment without the addition of an
appropriate line conditioner and surge protector (both not included).
Sensitive electronic equipment includes,
but is not limited to, audio/video equipment, some television sets, computers, and printers.
Sensitive
electronic equipment should be operated on approved inverter-type generators or pure sine wave generators.
Wheel Kit, #64788 (sold separately) can be used with this Generator.
Grounding
The Generator must be properly grounded in accordance with all relevant electrical codes and
standards before operation. In many locations, local code will not require this generator to be
grounded when used with cord and plug equipment plugged directly into the receptacles on the
generator. However, your local regulations may require the generator to be grounded. Contact a
licensed electrician or consult local authorities regarding local grounding requirements. If grounding
is required, have the unit grounded by a qualified electrician if you are not qualified to do so.
General grounding instructions are as follows:
Use one of the following as the grounding electrode:
pipe or conduit
, minimum ¾ in. diameter, minimum 8 ft. long. If steel, it must have anti-corrosion coating.
Rod
, stainless steel or copper- or zinc-coated steel, minimum 5/8 in. diameter, minimum 8 ft. long.
1. Drive electrode at least 8 ft. vertically into the ground.
a. If rock layer prevents vertical entry, drive at an angle not exceeding 45 degrees from vertical.
b. If rock layer prevents angle entry, bury electrode in horizontal trench at least 30 in. deep.
2. The upper end of electrode must be protected if above ground level.
3. Connect a #6 AWG grounding wire (not included) from the Grounding Terminal
on the Generator Control Panel to the buried electrode.
For additional information on grounding methods, please see the National Electrical Code.
NOTICE:
There is a permanent conductor between the portable generator
stator winding (Neutral Conductor) and the frame.