P
RO
V
U
PD6210 Analog Input Batch Controller Instruction Manual
15
RC Networks Available from Precision Digital
RC networks are available from Precision Digital and should be applied to each relay contact switching an
inductive load. Part number: PDX6901.
Note: Relays are de-rated to 1/14th HP (50 watts) with an inductive load.
F4 Digital Input Connections
A digital input, F4, is standard on the meter. This digital input connected with a normally open closure
across F4 and COM, or with an active low signal applied to F4.
Figure 13: F4 Digital Input Connections
4-20 mA Output Connections
Connections for the 4-20 mA transmitter output are made to the connector terminals labeled MA OUT.
The 4-20 mA output may be powered internally or from an external power supply.
Figure 14: 4-20 mA Output Connections
Analog Output Transmitter Power Supply
The internal 24 VDC power supply powering the analog output may be used to power other devices, if the
analog output is not used. The I+ terminal is the +24 V and the R terminal is the return.
12-35 VDC
Power
Supply
+
4-20 mA
Input Meter
-
+
R
I-
I+
1
3
2
RELAY1
3
2
1
24 V
-
4-20 mA Input
Remote Display,
Chart Recorder, Etc.
-
+
R
I-
I+
MA OUT
1
3
2
RELAY1
3
2
1
24 V
MA OUT