PDW90 Point to Multi-Point Wireless Instruction Manual
17
Modbus RTU Serial Communications
The PDW90 field units act as simple pass-throughs for Modbus communications. As such, multiple Mod-
bus enabled devices may be transmitted wirelessly using a wireless field unit.
Note: Modbus Master must be connected to Base Station.
Figure 17. Field Unit Three- and Five-Wire RS-485 Modbus Connection
Figure 18. Field Unit Multiple Device RS-485 Modbus Connection
Notes:
1. Termination resistors are optional and values depend on the cable length and characteristic im-
pedance. Consult the cable manufacturer for recommendations.
2. Use shielded cable, twisted-pairs plus ground. Connect ground shield only at one location.
Shield
Twisted-Pair
Shield
Twisted-Pair
(PDW90 Field Unit)
(PDW90 Field Unit)
R
R
R
R
Shield
Twisted-Pair
(PDW90 Field Unit)
R
R
www.
.com
1.800.561.8187