Trident Model PD765 Universal Input Meter         Instruction Manual 

37

 

Setting the Relay Operation (

rely

This menu allows you to set up the operation of the relays: 

1. Relay 

action 

a.  Automatic reset only (non-latching) 
b.  Aut manual reset at any time (non-latching) 
c.  Latching (manual reset only) 
d.  Latching with Clear (manual reset only after alarm condi-

tion has cleared) 

e.  Pump alternation control (automatic reset only) 
f. 

Off (relay and status LED disabled) 

2. Set 

point 

3. Reset 

point 

4. Fail-safe 

operation 

a. On 

(enabled) 

b. Off 

(disabled) 

5. Time 

delay 

a.  On delay (0-199 seconds) 
b.  Off delay (0-199 seconds) 

6.  Break Condition Behavior 

a. Off 

(non-alarm 

condition) 

b.  On (alarm condition) 

 

Refer to page 25 for a 
description of 

Display 

Functions and Messages

rLY1

rLY2

FLSF

rELY

dLAY

Act1

SEt1

rSt1

FLS1

FLS2

dLy1

dLY2

Same

Functions as

Relay 1

From Setup

Menu

Press 

Enter/Ack 

button to access any menu

Press 

Menu 

button to exit at any time

brek

brk1

brk2

www.

GlobalTestSupply

.com

Find Quality Products Online at:

[email protected]

Содержание PD765-6X0-00

Страница 1: ...nimum Display Type 4X NEMA 4X IP65 Front Universal Power Supply 85 265 VAC 12 36 VDC 12 24 VAC Power Option Two Relays and 4 20 mA Output Option 24 VDC Transmitter Power Supply Options USB RS 232 RS 485 Serial Communication Adapters Options Free Modbus RTU Protocol Copy Meter Settings to Other Meters Free MeterView Software Configuration Data Acquisition www GlobalTestSupply com nd Quality Product...

Страница 2: ...l Corporation All rights reserved INTRODUCTION The Trident is a multipurpose easy to use digital panel meter It accepts current voltage thermocouple and RTD signals The four front panel buttons make the setup and programming an easy task The isolated 24 VDC transmitter power optional can be used to power the input transmitter the 4 20 mA output or other devices The two relays optional can be used ...

Страница 3: ...X2 00 2 relays PD765 6X2 10 2 relays 24 V transmitter supply PD765 6X3 00 PD765 7X3 00 4 20 mA output PD765 6X3 10 4 20 mA output 24 V supply PD765 6X3 20 4 20 mA output dual 24 V supplies PD765 7X5 00 2 relays 4 20 mA output PD765 6X5 10 2 relays 4 20 mA output 24 V supply Accessories Model Description PDA7232 RS 232 serial adapter with PDA7420 included PDA7420 Trident meter copy cable 7 2 1 m PD...

Страница 4: ...ctions 16 Signal Connections 16 Serial Communication 20 Relays and 24 V Output Connections 20 Switching Inductive Loads 20 4 20 mA Output Input Signal Connections 22 SETUP AND PROGRAMMING 23 Front Panel Buttons and Status LED Indicators 24 Display Functions and Messages 25 Main Menu 28 Setting Numeric Values 28 Setting Up the Meter setu 29 Setting the Input Signal inpt 30 Setting the Decimal Point...

Страница 5: ...j 53 Noise Filter fltr 53 Noise Filter Bypass byps 54 Serial Communications serl 54 Protocol Selection Menu Prot 54 Select Menu SElc 55 Linear or Square Root Function linr or Sqrt 55 Low Flow Cutoff cutF 56 Display Intensity inty 56 Meter Copy Function Copy 57 Internal Calibration ICal 59 OPERATION 62 Front Panel Buttons Operation 62 Maximum Minimum Readings 63 MOUNTING DIMENSIONS 64 TROUBLESHOOTI...

Страница 6: ...onnections 17 Figure 8 Thermocouple Input Connections 18 Figure 9 Three Wire RTD Input Connections 18 Figure 10 Two Wire RTD Input Connections 19 Figure 11 Four Wire RTD Input Connections 19 Figure 12 Relay 24 V Output Connections 20 Figure 13 AC and DC Loads Protection 20 Figure 14 Low Voltage DC Loads Protection 21 Figure 15 4 20 mA Output Input Signal Powered by Meter 22 Figure 16 4 20 mA Outpu...

Страница 7: ...RD Programmable password restricts modification of settings NON VOLATILE MEMORY All programmed settings are stored in non volatile memory for a minimum of ten years if power is lost POWER OPTIONS 85 265 VAC 50 60 Hz 90 265 VDC 20 W max or 12 36 VDC 12 24 VAC 6 W max See table for power consumption X number depends on option Model Watts PD765 6RX 0 8 PD765 6RX 1 2 20 PD765 7RX 0 6 FUSE Required fus...

Страница 8: ...table 20 mADC 0 20 4 20 mA and 10 VDC 0 5 1 5 0 10 V ACCURACY 0 05 of span 1 count square root 10 100 FS FUNCTION Linear or square root LOW FLOW CUTOFF 0 9999 0 disables cutoff function TEMPERATURE DRIFT 0 to 65 C ambient 40 to 0 C ambient Current 0 20 FS 50 PPM C Voltage 0 02 FS 1 7 PPM C Current 0 80 FS Voltage 0 06 FS DECIMAL POINT Up to three decimal places for process inputs d ddd dd dd ddd d...

Страница 9: ... 700 0 F 180 0 to 371 0 C 1 8 F 1 0 C 13 F 7 2 C Type E 58 to 1578 F 50 to 870 C 2 F 1 C 11 F 6 C 100 Ω RTD 328 to 1382 F 200 to 750 C 1 F 1 C 5 F 3 C COLD JUNCTION REFERENCE Automatic fixed no user calibration needed OFFSET ADJUSTMENT Programmable to 19 9 This parameter allows the user to apply an offset value to the temperature being displayed INPUT IMPEDANCE Greater than 100 kΩ SENSOR BREAK DET...

Страница 10: ...via front panel buttons or PC Automatic reset only non latching Automatic manual reset at any time non latching Manual reset only at any time latching Manual reset only after alarm condition has cleared latching Automatic reset Relays will automatically reset when the in put passes the reset point Manual reset Front panel ACK button Pressing ACK re sets all manually resettable relays TIME DELAY 0 ...

Страница 11: ...mA 40 mA max 2 option EXTERNAL LOOP POWER SUPPLY 35 VDC maximum OUTPUT LOOP RESISTANCE Power supply Minimum Maximum 24 VDC 10 Ω 700 Ω 35 VDC external 100 Ω 1200 Ω Serial Communications METER ADDRESS PDC protocol 0 99 Modbus protocol 1 247 BAUD RATE 300 19 200 bps TRANSMIT TIME DELAY Programmable between 0 and 199 ms DATA 8 bit 1 start bit 1 stop bit PARITY None 1 or 2 stop bits even or odd Modbus ...

Страница 12: ... Emissions Class A IMMUNITY EN 61326 1 2013 Measurement control and laboratory equipment EN 61000 6 2 2005 EMC heavy industrial generic immunity standard RFI Amplitude Modulated 80 1000 MHz 10 V m 80 AM 1 kHz 1 4 2 0 GHz 3 V m 80 AM 1 kHz 2 0 2 7 GHz 1 V m 80 AM 1 kHz Electrical Fast Transients 2kV AC mains 1kV other Electrostatic Discharge 4kV contact 8kV air RFI Conducted 10V 0 15 80 MHz 1kHz 80...

Страница 13: ...ions designed to optimize EMC performance Declaration of Conformity available at www predig com SAFETY INFORMATION CAUTION Read complete instructions prior to instal lation and operation of the meter WARNING Risk of electric shock WARNING Hazardous voltages exist within enclosure Installa tion and service should be performed only by trained service personnel www GlobalTestSupply com nd Quality Pro...

Страница 14: ...4 102 mm behind the panel for wiring Panel thickness 0 04 0 25 1 0 mm 6 4 mm Recommended minimum panel thickness to maintain Type 4X rating 0 06 1 5 mm steel panel 0 16 4 1 mm plastic panel Remove the two mounting brackets provided with the meter back off the two screws so that there is 6 4 mm or less through the bracket Slide the bracket toward the front of the case and remove Insert meter into t...

Страница 15: ...d to the meter shows the location of all con nectors available with requested configuration It also identifies the loca tion of the RTD TC selector switch The below two images are common connector configurations for the PD765 Note that the connector in the upper left of the diagram has two different configurations based on the model Figure 2 Labeling for 2 Relay Analog Out 24 V Supply Model Figure...

Страница 16: ...al connector labeled SIGNAL on Figure 2 The COM common terminal is the return for all types of input signals Current and Voltage Connections The following figures show examples for current and voltage connections There are no switches or jumpers to set up for current and voltage inputs Setup and programming is performed through the front panel buttons Figure 5 Transmitter Powered by Ext Supply or ...

Страница 17: ...y may or may not show a fault condition depending on the nature of the overload The fuse limits the current to a safe level when it detects a fault condi tion and automatically resets itself when the fault condition is removed Figure 7 Voltage Input Connections The meter is capable of accepting any voltage from 10 VDC to 10 VDC www GlobalTestSupply com nd Quality Products Online at sales GlobalTes...

Страница 18: ...to accept the selected temperature input The input type is selected using the Setup menu Selected thermocouple input must correspond to thermocouple sensor and wire type used Figure 8 Thermocouple Input Connections Figure 9 Three Wire RTD Input Connections The meter accepts two three or four wire RTDs The three wire RTD connection has built in lead wire compensation www GlobalTestSupply com nd Qua...

Страница 19: ...djustment Adj page 53 Figure 11 Four Wire RTD Input Connections The four wire RTD connection is similar to the three wire One of the leads of a four wire RTD is not connected and may be clipped off The three wire connection provides sufficient lead wire compensation to provide accurate readings even with long leads www GlobalTestSupply com nd Quality Products Online at sales GlobalTestSupply co ...

Страница 20: ...e confused with the COM common terminal of the SIGNAL connector The 24 VDC output is available at the connector la beled 24V OUT next to the relays connector Figure 12 Relay 24 V Output Connections Switching Inductive Loads The use of suppressors snubbers is strongly recommended when switching in ductive loads to prevent disrupting the microprocessor s operation The suppres sors also prolong the l...

Страница 21: ...relay screw terminals An RC network may also be installed across the load Experiment for best results Figure 14 Low Voltage DC Loads Protection RC Networks Available from Precision Digital RC networks are available from Precision Digital and should be applied to each relay contact switching an inductive load Part number PDX6901 Note Relays are de rated to 1 14th HP 50 watts with an inductive load ...

Страница 22: ...nal power supply optional or from an external power supply Figure 15 4 20 mA Output Input Signal Powered by Meter Figure 16 4 20 mA Output Powered Externally COM SIGNAL CONNECTOR mA 2 1 3 5 4 V T EXC 2 Wire 4 20 mA Transmitter I mA OUT P2 P1 4 5 3 1 2 P2 P1 24V OUT 6 I Remote Display Chart Recorder etc External Power Supply I mA OUT 5 6 I Remote Display Chart Recorder etc www GlobalTestSupply com ...

Страница 23: ...d and Factory Values There is no need to recalibrate the meter when first received from the fac tory The meter is factory calibrated prior to shipment for all input types in milliamps volts and degrees respectively The calibration equipment is certified to NIST standards Overview There are no jumpers involved in the setup process of the meter The RTD TC selector switch located between the SIGNAL a...

Страница 24: ... the Right arrow button to move to the next digit during digit programming Press the Up arrow button to scroll through the menus decimal point or to increment the value of a digit Press the Enter Ack button to access a menu or to accept a setting Press the Right arrow and Menu button simultaneously or hold the Menu button for approximately 3 seconds to access the Advanced Features Menu of the mete...

Страница 25: ...pha 385 Set α 0 00385 European curve 100Ω RTD A392 Alpha 392 Set α 0 00392 American curve 100Ω RTD tC TC Set meter for TC input 0 J 0 J Type J 1 k 1 K Type K 2 T 2 T Type T 3 t 0 3 T 0 Type T 0 1 resolution 4 E 4 E Type E f C F or C Set temperature scale F F Set meter to Fahrenheit C C Set meter to Celsius dec p Decimal point Set decimal point prog Program Enter the Program menu scal Scale Enter t...

Страница 26: ...r pump alternation control oFF Off Disable relay and front panel status LEDs Disable relay s fail safe operation Set1 Set 1 Program set point 1 rSt1 Reset 1 Program reset point 1 RLY2 Relay 2 Setup relay 2 Act2 Action 2 Set relay 2 action automatic latching etc Set2 Set 2 Program set point 2 RSt2 Reset 2 Program reset point 2 FLSF Fail safe Enter Fail safe menu FLS1 Fail safe1 Set relay 1 fail saf...

Страница 27: ...ior Aout Analog output Enter the Analog output menu Scal Scale Enter the Scale menu Dis1 Display 1 Program display 1 value out1 Output 1 Program output 1 value e g 4 mA Dis2 Display 2 Program display 2 value out2 Output 2 Program output 2 value e g 20 mA SEbr Sensor break Program TC or RTD sensor break value for analog out pass Password Enter the Password menu unlC Unlocked Program password to loc...

Страница 28: ...ext menu every time a setting is ac cepted by pressing Enter Ack Setting Numeric Values The numeric values are set using the Right and Up arrow buttons Press Right arrow to select next digit and Up arrow to increment digit value The digit being changed is displayed brighter than the rest Press the Enter Ack button at any time to accept a setting or Menu button to exit without saving changes The de...

Страница 29: ...Ack button to access any menu or press Up arrow but ton to scroll through choices Press the Menu button to exit at any time RTD TC Note Selecting RTD or TC mode from the Input menu will include the Fahrenheit Celsius menu in the setup menu structure RTD will allow the selection of a decimal point location after this menu and TC has a fixed decimal point loca tion and will not allow the selec tion ...

Страница 30: ...either 0 00385 A385 European curve or 0 00392 A392 American curve The display then shows the decimal point menu DEc P Select the decimal point resolution as shown on page 31 If TC is selected scroll through the thermocouple types and select the type matching the TC sensor The input signal must be connected to the appropriate input terminals and the RTD TC selector switch must be set see Figure 8 o...

Страница 31: ... point for thermocouple inputs is fixed Pressing the Up arrow moves the decimal point one place to the right until no decimal point is displayed it then moves to the leftmost position Setting the Temperature Scale F C The meter can be set to display temperature in degrees Fahrenheit or Celsius Press Up arrow to change selection Press Enter Ack to accept dec p dddd Next Select Decimal Point Previou...

Страница 32: ...menu to scale process inputs e g 4 20 mA A cali brated signal source is not needed to scale the meter For thermocouple and RTDs just connect the sensor to the proper terminals and turn the power on No calibration needed when the meter is first received from the factory The Program menu contains the Calibrate and the Scale menus Process inputs may be calibrated or scaled to any display within the r...

Страница 33: ...nd corresponding display values For instructions on how to program numeric values see Setting Numeric Values page 28 Note The Scale menu is not available for temperature inputs dis1 00 0 Press Enter to Accept Setting inp2 Scale Input 2 inp1 Set Input 1 Value scal 04 00 Set Display 1 Value Press Up to Set Digit Value Press Right to Select Next Digit Press Menu to Exit at any Time www GlobalTestSupp...

Страница 34: ... signal is not connected to the proper terminals or it is con nected backwards 2 Wrong signal selection in Setup menu 3 Minimum input span requirements not maintained 4 Input 1 signal inadvertently applied to calibrate input 2 Minimum Input Span The minimum input span is the minimum difference between input 1 and in put 2 signals required to complete the calibration or scaling of the meter Input r...

Страница 35: ...rate the meter Recalibrating Temperature Inputs Cal Remember the meter is calibrated at the factory prior to shipment Re calibration is recommended at least every twelve months The Calibration CAL menu is used to recalibrate the thermocouple and RTD inputs Allow at least 30 minutes warm up time before performing recalibration proce dure to ensure specified accuracy inp1 dis1 04 00 Set Display 1 Va...

Страница 36: ...nnect signal to the meter using the appropriate wire e g type J thermocouple wire to recalibrate type J input see page 18 2 Set up the meter to accept the selected input e g type J T C see page 30 3 Set up the meter to display temperature in degrees Fahrenheit see page 31 4 Apply signal corresponding to input 1 32 F and program display 1 to 32 see page 35 5 Apply signal corresponding to input 2 11...

Страница 37: ...t only f Off relay and status LED disabled 2 Set point 3 Reset point 4 Fail safe operation a On enabled b Off disabled 5 Time delay a On delay 0 199 seconds b Off delay 0 199 seconds 6 Break Condition Behavior a Off non alarm condition b On alarm condition Refer to page 25 for a description of Display Functions and Messages rLY1 rLY2 FLSF rELY dLAY Act1 SEt1 rSt1 FLS1 FLS2 dLy1 dLY2 Same Functions...

Страница 38: ...action setup relay 2 is set up in a similar fashion Programming Set and Reset Points High alarm indication program set point above reset point Low alarm indication program set point below reset point The deadband is determined by the difference between set and reset points Minimum deadband is one display count If set and reset points are programmed the same relay will reset one count below set poi...

Страница 39: ... for each relay be tween 0 and 199 seconds The relays will transfer only after the condi tion has been maintained for the corresponding time delay The On time delay is associated with the set point The Off time delay is associated with the reset point FLSF FLS1 FLS2 on oFF Press Enter Ack button to accept setting Press Menu button to exit at any time on oFF Program On Time Delay Program Off Time D...

Страница 40: ...dition may be programmed for each relay as On alarm or Off non alarm The relays will enter these states when a sensor break is detected for RTD or thermocouple inputs These set tings have no effect when current or voltage inputs are selected www GlobalTestSupply com nd Quality Products Online at sales GlobalTestSupply co ...

Страница 41: ...trate the operation of the relays status LEDs and ACK button High Alarm Operation Set Reset For Manual reset mode ACK can be pressed anytime to turn off relay For relay to turn back on signal must go below set point and then go above it www GlobalTestSupply com nd Quality Products Online at sales GlobalTestSupply co ...

Страница 42: ...l 42 Low Alarm Operation Set Reset For Manual reset mode ACK can be pressed anytime to turn off relay For relay to turn back on signal must go above set point and then go below it www GlobalTestSupply com nd Quality Products Online at sales GlobalTestSupply co ...

Страница 43: ...he time delay has elapsed If the signal drops below the set point high alarm before the time delay has elapsed the On time delay timer resets and the relay does not change state The same principle applies to the Off time delay Note The LED is not affected by Time Delay when Automatic or Manual reset mode is selected Rather the LED follows the set and reset points www GlobalTestSupply com nd Qualit...

Страница 44: ...anual 44 High Alarm with Fail Safe Operation Set Reset Fail safe operation relay coil is energized in non alarm condition In case of power failure relay will go to alarm state www GlobalTestSupply com nd Quality Products Online at sales GlobalTestSupply co ...

Страница 45: ...Manual 45 Low Alarm with Fail Safe Operation Set Reset Fail safe operation relay coil is energized in non alarm condition In case of power failure relay will go to alarm state www GlobalTestSupply com nd Quality Products Online at sales GlobalTestSupply co ...

Страница 46: ...Trident Model PD765 Universal Input Meter Instruction Manual 46 Pump Alternation Control Operation www GlobalTestSupply com nd Quality Products Online at sales GlobalTestSupply co ...

Страница 47: ...is menu is enabled or disabled at the factory via the Advanced Features menu For more information on the Advanced Features Menu see page 50 The Analog Output menu is used to program 1 4 20 mA output based on display values 2 Sensor break value in mA For instructions on how to program numeric values see Setting Numeric Values page 28 out1 04 00 Press Enter to Accept Setting dis2 Scale Output 2 dis1...

Страница 48: ...cal output signal range is 1 00 to 23 00 mA e g If sensor break value is programmed to 0 00 the actual output will not be greater than 1 00 mA Analog Output when Display is Out of Range The analog output reflects the display out of range conditions as follows Input Condition Display Analog Output Underrange Flashing 1999 3 00 mA Overrange Flashing 9999 21 00 mA Open TC or RTD Flashing open Sensor ...

Страница 49: ... how to program numeric values see Setting Numeric Values page 28 Record the password for future reference If appropriate it may be rec orded in the space provided Model Serial Number Password __ __ __ __ Unlocking the Meter If the meter is password protected the correct password must be en tered in order to make changes to the parameter settings pass unlC 0000 Program Password loCd Run Mode pass ...

Страница 50: ...ss the Password menu add 2 to the noted reading and enter that number as the password e g display reading 1 23 password 0125 Advanced Features Menu To simplify the setup process functions not needed for most applica tions are located in the Advanced Features menu Press the Right arrow and Menu button simultaneously or hold the Menu button for approximately 3 seconds to access the Advanced Fea ture...

Страница 51: ...e timeout silent time Modbus only Copy Copy Enter copy function send Send Send meter settings to another meter done Done Copy function completed Selc Select Enter the Select menu function cutoff out Func Function Select linear or square root function Linr Linear Set meter for linear function Sqrt Square root Set meter for square root extraction cutF Cutoff Set low flow cutoff out Output Set meter ...

Страница 52: ...alibrate high voltage input diag Diagnostics Display parameter settings led LED Test display CJC CJC Display cold junction compensation voltage Cfg CFG Display meter configuration pts Points Display calibration points for process inputs RELY Relays Display relay settings Aout Analog output Display analog output settings GoFF Gain offset Display gain and offset for process inputs SErL Serial Displa...

Страница 53: ...e 2 below for important limitations Notes 1 Offset adjustment is available only when TC or RTD input is se lected 2 If adjustment value is greater than 11 C and the temperature scale is changed to Fahrenheit the maximum applied adjust ment will be 19 9 F Noise Filter fltr Most applications do not require changing this parameter It is intended to help attain a steady display with an unsteady noisy ...

Страница 54: ...ion Protocol The Modbus RTU protocol is included on all models after 5 1 2010 To communicate with a computer or other data terminal equipment an RS 232 or RS 485 adapter option is required see Ordering Information on page 3 for de tails When using more than one meter in a multi drop mode each meter must be provided with its own unique address The address may be pro grammed from 00 to 99 for PDC pr...

Страница 55: ...linr or Sqrt Meters are set up at the factory for linear function The linear function provides a display that is linear with respect to the input signal The square root function is used to linearize the signal from a differential pressure transmitter and display flow rate in engineering units Note Depending on meter model the Select menu will display either out or Aout In either case the output se...

Страница 56: ...om 0 to 9999 Below the cutoff value the meter will display zero Programming the cutoff value to zero disables the cutoff Display Intensity inty The Display Intensity function allows the selection of eight levels of in tensity for various lighting conditions Next Menu Item inty Select Display Intensity Level Func int3 SELc Press Enter to Accept Setting Press Up to Select Value Press Menu to Exit at...

Страница 57: ...ected to communicate with MeterView Meter Copy Function Copy The Copy function is used to copy or clone all the settings from one meter to other meters requiring exactly the same setup and program ming i e type of input scaling decimal point filter bypass etc Figure 17 Meter Copy Connection Copy Function Requirements To successfully copy settings from one me ter to another both meters must have 1 ...

Страница 58: ...opy function using Up arrow button then press Enter Ack 5 The meter displays the message Send Press Enter Ack the dis play flashes while sending data The message done is displayed when copying is completed 6 The Clone meter displays the memory address being programmed then the message done when copying is completed The meter ini tializes and returns to Run Mode using the same settings as the Maste...

Страница 59: ...t type must be recalibrated separately if meter will be used with all input types Notes If meter is in operation and it is intended to accept only one input type e g 4 20 mA recalibration of other inputs is not necessary Allow the meter to warm up for at least 15 minutes before performing the internal cali bration procedure The Internal calibration menu is part of the Advanced Features Menu 1 Pres...

Страница 60: ...e to the next digit 6 Set the display value to correspond to the input signal being cali brated 7 The display moves to the high input calibration I Hi Apply the high input signal and press Enter Ack 8 Set the display for the high input calibration in the same way as it was set for the low input calibration For instructions on how to pro gram numeric values see Set ting Numeric Values page 28 The g...

Страница 61: ...ts to input 1 allow ing the appropriate input signals to be applied The error message might be caused by any of the following conditions 1 Input signal is not connected to the proper terminals or it is con nected backwards 2 Wrong signal selection in Setup menu 3 Minimum input span requirements not maintained Minimum Input Span The minimum input span is the minimum difference between input 1 and i...

Страница 62: ...e and temperature units F or C selected RTD and Type T thermocouple in puts can be displayed with either 1 or 0 1 resolution Front Panel Buttons Operation Button Symbol Description Press to enter or exit Programming Mode view settings or exit Max Min readings Hold to enter Advanced features menu Press to reset Max Min readings Press to display Max Min readings alternately Press to display Max Min ...

Страница 63: ...k to hold Max Min display reading the meter will continue to track new Max Min readings 4 If Enter Ack is not pressed the Max Min display reading will time out after ten seconds and the meter will return to display the actual reading 5 Press Right arrow Reset button to reset Max Min while reading is being displayed Max Min display readings are reset to actual reading 2468 Hi lo Actual Reading 9846...

Страница 64: ... Instruction Manual 64 MOUNTING DIMENSIONS Figure 18 Meter Dimensions Side View Figure 19 Case Dimensions Top View 1 76 45mm 0 59 15mm 3 2 81mm 2 45 62mm 3 6 91mm www GlobalTestSupply com nd Quality Products Online at sales GlobalTestSupply co ...

Страница 65: ...ge 50 It provides an easy way to view the programmed parameter settings for troubleshooting purposes Press the Enter Ack button to view the set tings and the Menu button to exit at any time For a description of the diagnostics messages see Advanced Features Menu Display Messages page 51 Determining Software Version To determine the software version of a meter 1 Go to the Diagnostics menu diAG and ...

Страница 66: ...dvanced Features Menu page 50 2 Press Up arrow to go to Diagnostics menu 3 Press and hold Right arrow Reset for five seconds press Enter Ack when display flashes reset Note If Enter Ack is not pressed within three seconds display re turns to Diagnostics menu 4 The meter goes through an initialization sequence same as on power up and loads the factory default settings rset diag Press Simultaneously...

Страница 67: ...ings to other meters Model ______________ S N _______________ Date _________ Parameter Display Default Setting User Setting Input type inpt 4 20 mA Decimal point dd dd 2 places Programming prog Input 1 InP1 4 00 mA Display 1 Dis1 4 00 Input 2 InP2 20 00 mA Display 2 Dis2 20 00 Relay 1 Rly1 Action 1 Act1 Automatic Set 1 Set1 7 00 Reset 1 RSt1 6 00 Relay 2 Rly2 Action 2 Act2 Automatic Set 2 Set2 10 ...

Страница 68: ...delay trde 10 ms Function Func Linear Cutoff value CutF 0 00 disabled Output option out Aout Factory set only Display intensity inty Level 8 Modbus defaults N A Address addr 247 Parity prty Even Byte to byte timeout tbyt 0 01 sec Note The byte to byte timeout setting might be updated automatically de pending on the baud rate selected and the previous timeout setting The minimum timeout allowed is ...

Страница 69: ...nu to exit Max Min display readings Display response is too slow Check filter and bypass values Inaccurate temperature reading Check 1 Temperature units F or C 2 TC type or RTD curve selected 3 Offset adjustment 4 TC wire used 5 Calibration If the display locks up or the meter does not respond at all Cycle the power to restart the microprocessor Relay operation is reversed Check 1 Fail safe in Set...

Страница 70: ...ype E F C F or C To Program Locked Unlocked TC or RTD Yes No Relays Relay 1 Relay 2 Failsafe Delays Action Set point Reset point Auto Auto Manual Latch Latch w Clear Pump Alt Off To Set point Failsafe 1 Failsafe 2 To Delays Delay 1 Delay 2 On Off Analog output Scale Sensor break To Password RTD or Type T No Yes Calibrate Scale TC or RTD Yes No Program To Relays www GlobalTestSupply com nd Quality ...

Страница 71: ... to the current value Press Menu or wait 10 seconds to return to Run Mode Pressing Enter Ack will disable the 10 second timeout and continuously display Max or Min Press Right arrow and Menu to access Advanced Features Menu When the meter is locked Adjust Filter and Bypass can only display their settings and the Copy and ICAL functions are not available Adjust Filter Bypass Serial Copy Send TC or ...

Отзывы: