Troubleshooting
This product is a highly sophisticated instrument with
an extensive list of features and capabilities. If the
CapTouch buttons are used to program the meter, it
can be a difficult task to keep everything straight. That
is why we strongly recommend the use of the free
software for all programming activities.
A cable is provided to use the MeterView XL software
for programming the meter.
If you have programmed the meter with the CapTouch
buttons and it is not working as intended, try
re-programming the meter using the MeterView XL
software.
Reset Meter to Factory Defaults
When the parameters have been changed in a way
that is difficult to determine what’s happening, it might
be better to start the setup process from the factory
defaults. This can be accomplished using MeterView
XL software or with the CapTouch buttons.
To load factory defaults:
1. Press the
Menu
button to enter
Programming Mode
.
2. Press the
Right-Arrow
button
twice
and
press
Enter
to access the
Advanced
menu.
3. Press the
Up-Arrow
button and press
Enter
to access the
System
menu.
4. Press the
Right-Arrow
button and press
Enter
to access the
Default
menu.
5. Press
Enter
twice in quick succession. The
meter will load default settings and restart.
Determining Software Version
To determine the software (firmware) version of a
meter:
1. Press the
Menu
button to enter
Programming Mode
.
2. Press the
Up-Arrow
button
twice
and press
Enter
to access the
Advanced
menu.
3. Press the
Up-Arrow
button and press
Enter
to access the
System
menu.
4. Press the
Up-Arrow
button
twice
and press
Enter
to access the
Info
menu.
5. Press the
Right-Arrow
button to cycle
through the meter information. When done,
press the
Menu
button to return to the
previous menu or press & hold
Menu
to exit
to Run mode.