www.predig.com
PD9000
Multivariable Controller
28
Ethernet Communications
Device:
Lantronix Xport-05
Protocol:
Modbus TCP/IP (Default)
Modbus UDP/IP
Modbus RTU Over TCP/IP
Modbus RTU Over UDP/IP
Port Settings (Do Not Change):
Protocol: RS-232
Baud Rate: 9600
Data Bits: 8
Flow Control: None
Parity: None, Stop Bits: 1
Network Stack:
IPv4
Ethernet Mac/Phy:
10/100 Mbps
Additional Specifications:
Refer to the Lantronix Webpage
https://www.lantronix.com/products/xport
Ethernet Port Configuration:
Use the System menu for basic
Ethernet configuration or download the Lantronix DeviceIntaller
software to fully configure the Ethernet port.
https://www.lantronix.com/products/xport
See the
for instructions.
Conso Software
System Requirements:
Windows
®
7, 10
Compatibility:
The software and firmware versions must be
matched.
Do not write configuration files created using older versions of the
firmware and software to controllers with Add-On features enabled
(Ver. 2.1 & up). This can create undesirable results, especially with
the function keys F1-F4.
Connection:
Standard USB A to Micro-USB type B (cable included).
Configuration:
Configure inputs and outputs, channels, totals,
timers, alarms, etc. Configure bargraph and panel colors for normal
operation, and colors for alarm indication. Save controller settings
file on PC for programming other controllers or to restore settings.
Sample Data Log File