SPECIFICATIONS
Except where noted all specifications apply to operation at 25°C (77°F)
General
Display:
Color; QVGA (320x240 pixels), 5.7" (145 mm) diagonally,
white backlight; Bargraph: Twenty divisions Numerical: Up to 15
digits (±999,999,999,999,999); Feet & Inches Format: 99,999' 11.9"
Screen Bargraph
: Enable/disable: Channels, totals, timers
Bargraph scale: 0 – 100%, independent of channel scale. Twenty
divisions: 5% each. Screen: Select to show bargraph or not.
Color Selection:
65 colors selection, Customize bargraph, panel
background, and text for normal and alarm conditions.
Decimal Point:
0 to 15 decimal places, user selectable
Engineering Units:
User selectable units or custom units
Time, Distance, Volume, Pressure, Weight, Temperature, Current,
Voltage, Percent, Amps, Volts, Counts, Logic, and Custom, Any
unit/unit of time or other units
Feet & Inches Units:
Data entry format: Decimal (e.g. 50.58 feet)
Display format: 50' 6.96"
Units Conversion:
Units’ conversion is supported for channels,
totals, timers, and any function using those parameters. Channel
scaling must be in the intended base units (e.g. Gallons/min)
Display Update Rate:
User selectable: 0.1 to 0.5 sec
(10 updates/sec to 2 updates/sec)
Programming Method:
Front panel buttons, external buttons, or
Conso Software
Number of Alarms:
Up to 64 high or low, Logic AND & OR
Automatic (non-latching) or latching
On & Off time delays
Can be assigned to one or more relays.
Note: Alarms are independent from relays.
Alarm Types:
Single Source: One input
Multi-Source: Two or more inputs
Interval: Enter time interval and On Time
Day & Time: Select day of the week & time
Alarm OR: Any active input alarm triggers the OR alarm
Alarm AND: All alarms must be active to trigger the AND alarm
Alarm Ack & Reset:
Automatic only (Non-latching)
Automatic and manual
Manual only (Latching)
Manual with Ack only after alarm is cleared (Latching with Clear)
Alarm Indication:
1. Bargraph, panel, and text can be set up to
change color on alarm
2. Enable internal buzzer
3. Assign external relay to drive a horn
Internal Buzzer:
60 dBA @ 24 inches (61 cm) Enable/disable in
System – General menu. Associated with alarm Horn setting
External Horn (Sold separately):
Assign any relay to the Horn
function to activate an external horn when alarm condition is
detected.
Live Channel Calibration:
Live calibration of channels is
independent of the input calibration used for scaling.
Input & Output Cards:
Max Number of I/O Cards: 7
Analog Inputs: 4/card, Pulse Inputs: 4/card, Analog Outputs: 5/card,
Relays: 5/card
Number of Screens:
Up to 20 screens with 1 to 8 PVs or items per
screen. Enable or disable screen title, channel #, and bargraph
Automatic or manual scanning Scan time: 1 to >1000 sec,
independent for each screen. F1-F4 keys are assigned per screen
Function Keys:
User programmable (See defaults below)
F1 = Previous
←
F2 = Next
→
F3 = Scan/Stop F4 = Ack
Number of Channels:
Up to 99 channels
Input Source: 4-20 mA, Pulse, Digital, Modbus, another Channel,
Total, Timer, Alarm, Date & Time, mA Output, Relay Output, Digital
Output, or Modbus Output
Channel Functions:
There is an extensive number of functions
that can be applied to the inputs
Password:
Programmable password restricts modification of
programmed settings. View and Setup menus are password
protected, function keys and digital inputs are not protected.
Simulation Mode:
Inputs, channels, totals, timers, and alarms can
be simulated from the View menu or from a function key.
Simulation mode is not saved on power down. Alert! message is
provided for simulated items.
Manual Control:
Analog outputs and relays can be controlled
manually from the View menu or from a function key.
Manual control mode is not saved on power down. Alert! message
is provided for outputs in manual control.
Note: If it is necessary to turn relays off and maintain the condition
through power cycle, configure the relays to Always Off.
Non-Volatile Memory:
Settings stored for a minimum of 10 years.
Power (User Selectable Based on Wiring):
Three-terminal
connector (L, N, GND), AC: 80-264 VAC, 47 to 63 Hz, 60 W max
DC: 113-370 VDC, 60 W max (L, N)
Two-terminal connector (G, 24V) DC: 24 VDC ±10%, 60 W max
Backup Power Supply:
If AC and DC power are connected, the
24 VDC can be used as backup power in case of AC power failure.
Note: DC supply must be 24 V or less; otherwise the system runs
on DC power.
Fuse:
Unit is protected internally with auto-resettable fuse.
AC: 1.25 A max, DC: 3.7 A max
External Fuse:
Recommended external fuse slow-blow
120 VAC: 2.0 A, 240 VAC: 1.0 A, 24 VDC: 4 A
Isolation & Grounding:
1500 V Analog inputs/outputs-to-power
line, 500 V Analog input-to-input, input-to-output, analog output-to-
output
All analog inputs and analog outputs are isolated from each other.
Note: DC Power is not isolated. DC- is connected to Earth Ground.
Digital I/O, USB, and Ethernet are grounded.
Environmental:
Operating temperature range: -40 to 60°C
(-40 to 140°F)
Storage temperature range: -40 to 60°C (-40 to 140°F)
Relative humidity: 0 to 90% non-condensing
* All functions operate down to -40°C (-40°F.) If the LCD response
is slower, increase the display refresh setting.
Internal Fan:
Automatic temperature-controlled fan turns on if the
inside temperature reaches 50°C and increases the speed as the
temperature rises to 60°C.
Internal Heater:
Automatic temperature-controlled heater located
behind the LCD turns on at 0°C, delivering the minimum power.
If the temperature drops below -10°C, the heater delivers its
maximum power.
Connections:
Removable screw terminal blocks
Inputs/Outputs: 12 to 24 AWG wire, Digital I/O: 16 to 30 AWG,
RS-485: 12 to 24 AWG wire RJ45 Ethernet connection,
USB ports: Micro-USB used for programming, cable included.
USB Host: Type A, used with Data Logger Add-On feature.
Tightening Torque:
Screw terminal connectors: 5 lb-in (0.56 Nm)
Digital I/O terminals: 2.5 lb-in (0.28 Nm)
Enclosure:
Enclosure Body: Thermoplastic Polyester,
Color: Gray,
Display Window: Clear Polycarbonate, GE LEXAN HP12W
Front Panel Keys: Silicone rubber
Mounting:
Panel-mounting frame and twelve screws (provided)
Cutout: 10.0" x 10.0" ±0.05" (254 mm x 254 mm ±1.3 mm) (H x W)
Panel thickness: 0.07" – 0.35" (1.8 mm – 8.9 mm)
Clearance behind panel: 6" (152 mm)
Overall Dimensions:
10.85" x 10.85" x 4.87"
(276 mm x 276 mm x 124 mm) (H x W x D)
Weight:
Ex: PD9000-XY-4PI-8AI-10AO-10RY
7.4 lb (3.4 kg) approx.
Warranty:
3 years parts and labor. See Warranty Information and
Terms & Conditions on