9116QA01
LERBAKKEN 10, 8410 ROENDE DENMARK
Revision date:
2010-02-12
Version Revision
V5 R0
Prepared by:
PB
Page:
2/4
Terminal 51-52, 51-53
Terminal 51-52, 51-53
Ui
30 V
Ui
30 V
Ii
120 mA
Ii
120 mA
Pi
900 mW
Pi
900 mW
Ci
3 nF
Ci
3 nF
Li
1
μ
H
Li
1
μ
H
Uo
28 V
IIC
80 nF
4 mH 54
μ
H/
Ω
Uo
21.4 V
IIC
0.16
μ
F
4 mH 54
μ
H/
Ω
Io
93 mA
IIB
640 nF
16 mH 218
μ
H/
Ω
Io
93 mA
IIB
1.13
μ
F
16 mH 218
μ
H/
Ω
Po
650 mW
IIA
2.1
μ
F
32 mH 436
μ
H/
Ω
Po
650 mW
IIA
4.15
μ
F
32 mH 436
μ
H/
Ω
Uo
28 V
IIC
80 nF 1000 mH 4 mH/
Ω
Uo
21.4 V
IIC
0.16
μ
F 1000 mH 4 mH/
Ω
Io
1.1 mA
IIB
640 nF 1000 mH 17 mH/
Ω
Io
1.1 mA
IIB
1.13
μ
F 1000 mH 17 mH/
Ω
Po
8 mW
IIA
2.1
μ
F 1000 mH 35 mH/
Ω
Po
8 mW
IIA
4.15
μ
F 1000 mH 35 mH/
Ω
Uo
8.3 V
IIC
7
μ
F 1000 mH 100 mH/
Ω
Uo
8.3 V
IIC
7
μ
F 1000 mH 100 mH/
Ω
Io
0.2 mA
IIB
73
μ
F 1000 mH 400 mH/
Ω
Io
0.2 mA
IIB
73
μ
F 1000 mH 400 mH/
Ω
Po
0.4 mW
IIA
1000
μ
F 1000 mH 800 mH/
Ω
Po
0.4 mW
IIA
1000
μ
F 1000 mH 800 mH/
Ω
Uo
8.3 V
IIC
7
μ
F
207 mH
1 mH/
Ω
Uo
8.3 V
IIC
7
μ
F
207 mH
1 mH/
Ω
Io
13.1 mA
IIB
73
μ
F
828 mH
5 mH/
Ω
Io
13.1 mA
IIB
73
μ
F
828 mH
5 mH/
Ω
Po
27.3 mW
IIA
1000
μ
F 1000 mH 10 mH/
Ω
Po
27.3 mW
IIA
1000
μ
F 1000 mH 10 mH/
Ω
Module 9116B2
Terminal 51-54, 52-54
Group
Module 9116B2
Terminal 51-53
Co
Group
Lo
Lo/Ro
Co
Lo
Lo/Ro
Lo/Ro
Lo
Module 9116B1
Terminal 41,42,43,44
Module 9116B1
Terminal 51-52
Group
Group
Module 9116B2
Terminal 41,42,43,44
Group
Lo/Ro
Lo/Ro
Module 9116B2
Terminal 51-52
Group
Group
Co
Lo
Lo/Ro
Co
Co
Lo
Lo/Ro
Co
Lo
Module 9116B1
Module 9116B2
Module 9116B1
Terminal 51-54, 52-54
Group
Module 9116B1
Terminal 51-53
Co
Lo
Lo/Ro
Co
Lo
Installation notes:
For installation in Zone 2, the module must be installed in an outer enclosure having an IP protection
of at least IP54 conforming to the requirements of EN60079-15.
For installation on Power Rail in Zone 2, only Power Rail type 9400 supplied by Power Control Unit
type 9410 (Type Examination Certificate KEMA 07ATEX0152 X) is allowed.
In type of protection “intrinsic safety iD” the parameters for intrinsic safety for gas group IIB are
applicable.
Do not separate connectors when energized and an explosive gas mixture is present.
Do not mount or remove modules from the Power Rail when an explosive gas mixture is present.
If the sensor circuits or loop supply circuits have been installed in a type of protection other than
“Intrinsic Safety”, the module shall not be reinstalled in type of protection “Intrinsic Safety”