9116 UNIVERSAL CONVERTER
Safety Manual
13.3.7 Simulation (SIM)
It is possible to override the actual measured input signal by a simulated
value. In the REL.SIM menu it is posible to simulate the relay state with out
affecting the analogue output, by pressing
1
. Leaving the simulation menus,
or disconnecting the 4501 device, will disable the simulation mode and bring
the output back to correspond to the actual measured value. Simulation is
not possible in SIL-mode.
13.3.8 Safety integrity level (SIL)
See section 14 - Safe parameterisation - user responsibility
14 Safe parameterisation - user responsibility
14.1 Safety-related configuration parameters
14.1.1 Common parameters
Name
Function
IN.TYPE
Selected input type:
TEMP = Temperature
CURR = Current
VOLT = Voltage
LIN.R = Linear resistance
POTM = Potentiometer
I.RANGE
Selected fixed input range for current measurements (for
IN.TYPE = CURR):
0_20 = 0...20 mA (no sensor error detection!)
4_20 = 4...20 mA
V.RANGE
Selected fixed input range for voltage measurements
(for IN.TYPE = VOLT)
SENSOR
Selected temperature sensor type (for IN.TYPE = TEMP):
TC = Thermocouple
Ni = Ni RTD sensor
Pt = Pt RTD sensor
PENDING