Chapter 5 Function parameter
41
Ch
ap
ter 5
251.
F7.48 Dormancy frequency
0.00Hz to awakens frequency(F7.46)
0.00Hz
☆
252.
F7.49 Dormancy delay time
0.0s to 6500.0s
0.0s
☆
253.
F7.50
AI1 input voltage
protection lower limit
0.00V to F7.51
3.1V
☆
254.
F7.51
AI1 input voltage
protection upper limit
F7.50 to 10.00V
6.8V
☆
255.
F7.52~
F7.53
Reserve
256.
F7.54 Jog mode setting3
Bits:
0: forward
1: reverse
2: determine the direction from the
main termina
Ten bits:
0: restore to the previous state after
jogging
1: stop running after jogging
Hundred bits:
0:recover to the previous deceleration
time after jogging
1: keep the deceleration time the
sameafter jogging
002
☆
5-1-10.
F8 Group - Fault and protection
No.
Code
Parameter name
Setting range
Factory
setting
Chang
e
257. F8.00 Overcurrent stall gain
0 to 100
20
☆
258. F8.01
Overcurrent stall
protection current
100% to 200%
150%
☆
259. F8.02
Motor overload protection
selection
0: Invalid 1: Enable
1
☆
260. F8.03
Motor overload protection
gain
0.20 to 10.00
1.00
☆
261. F8.04
Motor overload pre-alarm
coefficient
50% to 100%
80%
☆
262. F8.05 Over-voltage stall gain
0 to 100
0
☆
263. F8.06
Over-voltage stall
protection voltage / energy
consumption brake
voltage
120% to 150%
130%
☆
264. F8.07 Input phase loss protection Units digit:Input phase loss
11
☆