Chapter 2 Standard specifications
8
Ch
ap
ter 2
PID feedback
signal
Including DC(0 to 10V), DC(0 to 20mA)
O
u
tp
u
t
S
ig
n
al
Running status
Motor status display, stop, ac/deceleration, constant speed,
program running status.
Fault output
Contact capacity :normally closed contact 3A/AC 250V
,
normally
open contact5A/AC 250V
,
1A/DC 30V.
Analog output
Two-way analog output, 16 signals can be selected such as
frequency, current, voltage and other, output signal range (0 to 10V
/ 0 to 20mA).
Output signal
At most 4-way output, there are 40 signals each way
Run function
Limit frequency, jump frequency, frequency compensation, auto-
tuning, PID control
DC current
braking
Built-in PID regulates braking current to ensure sufficient braking
torque under no overcurrent condition.
Running command
channel
Three channels: operation panel, control terminals and serial
communication port. They can be switched through a variety of
ways.
Frequency source
Total 10 frequency sources: digital, analog voltage, analog current,
multi-speed and serial port. They can be switched through a variety
of ways.
Input terminals
8 digital input terminals, compatible with active PNP or NPN input
mode, one of them can be for high-speed pulse input(0 to 100 kHz
square wave); 3 analog input terminals for voltage or current input.
Output terminals
2 digital output terminals, one of them can be for high-speed pulse
output(0 to 100kHz square wave); one relay output terminal; 2
analog output terminals respectively for optional range (0 to 20mA
or 0 to 10V), they can be used to set frequency, output frequency,
speed and other physical parameters.
Pr
o
te
ct
io
n
f
u
n
ct
io
n
Inverter protection
Overvoltage protection, undervoltage protection, overcurrent
protection, overload protection, overheat protection, overcurrent
stall protection, overvoltage stall protection, losting-phase
protection (optional), communication error, PID feedback signal
abnormalities, PG failure and short circuit to ground protection.
IGBT temperature
display
Displays current temperature IGBT
Inverter fan
control
Can be set
Instantaneous
power-down
restart
Less than 15 milliseconds: continuous operation.
More than 15 milliseconds: automatic detection of motor speed,
instantaneous power-down restart.
Speed start
tracking method
The inverter automatically tracks motor speed after it starts
Parameter
protection function
Protect inverter parameters by setting administrator Password and
decoding
D
isp
la
y
LED/O
LED
display
keyboa
rd
Running
informatio
n
Monitoring objects including: running frequency, set frequency,
bus voltage, output voltage, output current, output power, output
torque, input terminal status, output terminal status, analog AI1
value, analog AI2 value, motor Actual running speed
,
PID set
value percentage, PID feedback value percentage.
Error
message
At most save three error message, and the time, type, voltage,
current, frequency and work status can be queried when the failure
is occurred.