page no. 7 of 68
CPx Range Users, Installation & Servicing Instructions Doc Ref M201 issue 2.9 Nov 2018.
Model
30
45
60 90
(gas)
90
(oil)
120 150 175 200 250 300 360 440 590
Output
kW
30
45
60
90
90
120
150
175
200
250
290
366
440
586
Input (nett CV)
G20 Gas
kW
32.6
48.9
65.2
97.8
n/a
130.4 163.0 190.2 217.4 271.7 315.2 399.0 479.6 638.7
35sec Oil
kW
31.9
48.7
64.3
n/a
97.7
130.5 160.3 190.3 213.3 269.4 316.1 391.6 470.8
627
Old Powrmatic Reference
CP
100
150
200
300
300
400
500
600
700
800
1000
1250
1500
2000
Thermal Efficiencies (Nett CV)
%
Min 91.5%
Airflow
Volume
m
3
/s
0.97
0.86
1.01
2.11
1.50
2.30
3.15
3.36
3.84
4.49
5.76
6.49
7.88
10.5
Heads
UF / HF
No.
2
2
3
3
3
4
4
4
4
4
4
4
8
8
Size
mm
203
254
254
305
305
305/358 305/358
358
406
457
457
457
457
457
Throw
UF / HF
m
15
21
19
24
24
24
29
29
29
41
48
48
30
40
Fan Static
Standard
Pa
188
222
270
250
200
180
185
290
250
140
150
300
300
300
Up-rated
Pa
250
250
400
500
450
350
400
500
500
450
500
600
600
600
Electrics
Supply
Standard
V/ph/Hz
230/1/50
400/3/50
Optional
V/ph/Hz
400/3/50
230/1/50
n/a
Standard
Fan
Motor
kW
0.55
0.55
1.1
1.5
1.4
1.4
3.0
4.0
4.0
4.0
7.5
11.0
11.0
15.0
Run
amp
4.3
5.7
5.3
10.0
9.6
6.4
6.7
7.1
8.6
8.4
14.5
21.3
21.3
28.9
Start
amp
8.1
17.1
16.1
25.5
28.1
12.4
23.45
23.0
19.7
28.2
50.1
127.2 127.2 182.4
Uprated
Fan (L.H.P.)
Motor
kW
0.75
0.75
2.2
2.2
1.5
3.0
4.0
5.5
5.5
5.5
11.0
15.0
15.0
18.5
Run
amp
5.3
5.3
12.6
12.6
9.2
6.3
8.3
11.0
11.0
11.0
21.6
28.9
28.0
35.0
Start
amp
15.9
15.9
37.8
37.8
27.6
22.05 29.05
38.5
38.5
38.5
75.6
182.4 182.4 221.2
Fuel
Connection
Oil
BSP/Rc
⅜
”
⅜
”
⅜
”
n/a
⅜
”
⅜
”
⅜
”
⅜
”
⅜
”
⅜
”
⅜
”
⅜
”
⅜
”
½”
Gas
BSP/Rc
½”
½”
¾”
¾”
n/a
¾”
1”
1”
1”
1¼”
1¼”
1½”
1½”
1½”
Minimum
Inlet
Pressure
Nat Gas
mbar
17.5
n/a
17.5
LPG
mbar
37.0
n/a
37.0
Consumption
Standard
Outputs
Oil
l/h
3.16
4.83
6.38
n/a
9.70
12.95 15.90 18.89 21.17 26.73 31.36 38.82 47.45 63.62
Nat Gas
m
3
/h
3.45
5.17
6.89
10.34
n/a
13.79 17.23 20.11 22.99 28.73 33.33 41.41 50.61 67.86
LPG
m
3
/h
1.34
1.98
2.64
4.01
n/a
5.31
6.64
7.72
8.84
11.00 12.84 16.00 19.56 26.23
Overall
Dimensions
UF Upright
Freeblowing
Height
mm
2024
2072
2494
2585
2585
2821
2821
3054
3174
3307
3307
3657
4107
4407
Width
mm
669
669
744
744
744
904
904
904
904
1104
1104
1260
1330
1330
Depth
(Excludes
burner)
mm
732
732
927
927
927
1200
1200
1399
1399
1599
1599
1915
2165
2715
Installation
Clearances
UF Upright
Freeblowing
Front
mm
1000
1000
1000
1000
1000
1000
1000
1000
1000
1000
1000
1000
1000
1000
Side
mm
1000
1000
1000
1000
1000
1000
1000
1000
1000
1000
1000
1000
1000
1000
Blank Side
mm
150
150
150
150
150
150
150
150
150
150
150
n/a
n/a
n/a
Rear
mm
1000
1000
1000
1000
1000
1000
1000
1000
1000
1000
1000
1000
1000
1000
Flue Diameter
mm ø
125
125
150
150
150
150
175
175
175
200
200
250
300
300
Combustion Air Spigot
mm ø
150
150
150
150
150
150
150
150
150
150
150
150
175
175
Maximum Combustion Duct Length *
m
34
34
21
21
21
12
8
6
4
3
2
3
2
2
Noise Level (See Note Below)
dB(A)
56
61
61
63
63
70
62
73
74
75
77
78
80
82
Nett Weight (See Note Below)
kg
168
173
231
241
241
341
386
530
530
556
556
1012
1380
1720
Model
30
45
60 90
(gas)
90
(oil)
120 150 175 200 250 300 360 440 590
*
For extended combustion duct lengths please contact Powrmatic
Notes –
•
Fuel consumption and output figures based upon nett calorific values as follows
- Class D light distillate fuel oil nett CV 36.28 MJ/l
- Natural gas (G20) nett CV 34.02 MJ/m³
- Propane (G31) nett CV 88.00 MJ/m³
•
CPx heaters comply with the seasonal efficiency and NOx limits requirements of the Ecodesign regulation (EU) 2015/1188, Directive 2009/125/EC – Lot 21 Tier 1
•
Air handling data is assessed at room ambient conditions
•
Throw figures provide the distance to the point where the terminal velocity degrades to 0.25 m/s
•
Overall vertical heater height include heads or extended heads where appropriate
•
Standard height heads can be specified where site height is restricted
•
Blank and louvred lower side panels are interchangeable
•
Dimensions in table above refer to upright heaters only - for horizontal and counterflow heater dimensions refer to dimensions page
•
Noise levels are applicable to standard UF models and are measured 5m from appliance and in free field conditions
•
Motor kW, run and start amps apply to standard electrical supply as stated. For optional data contact sales office
•
Nett weight figures apply to standard upright CPx heaters only
•
It is the responsibility of the installing contractor to ensure that ductwork is correctly sized and balanced when installing a ducted unit.