CPx Range Users, Installation & Servicing Instructions Doc Ref M201 issue 2.9 Nov 2018.
Natural Gas to Propane (LPG) Conversion Data
Nominal Inlet Pressure = 37mbar, Minimum Inlet Pressure = 37mbar
Burner Pressure
High Fire
Low Fire
MODEL
Conversion Kit part number
mbar
mbar
CPx30
CPX30HL/LPG
5.0
2.7
CPx45
CPX45HL/LPG
10.2
3.9
CPx60
CPX60HL/LPG
8.2
3.5
CPx90
CPX90HL/LPG
5.5
2.6
CPx120
CPX120HL/LPG
7.6
3.5
CPx150
CPX150HL/LPG
10.6
4.4
CPx175
CPX175HL/LPG
tbc
tbc
CPx200
CPX200HL/LPG
6.9
3.9
CPx250
CPX250HL/LPG
10.0
4.7
CPx300
CPX300HL/LPG
tbc
tbc
Propane (LPG) to Natural Gas Conversion Data
Nominal Inlet Pressure = 20mbar, Minimum Inlet Pressure = 17.5mbar
Burner Pressure
High Fire
Low Fire
MODEL
Conversion Kit part number
mbar
mbar
CPx30
CPX30HL/NG
3.4
1.5
CPx45
CPX45HL/NG
6.4
2.5
CPx60
CPX60HL/NG
5.8
2.5
CPx90
CPX90HL/NG
4.2
1.9
CPx120
CPX120HL/NG
6.0
2.6
CPx150
CPX150HL/NG
9.1
3.3
CPx175
CPX175HL/NG
8.3
3.5
CPx200
CPX200HL/NG
6.9
4.1
CPx250
CPX250HL/NG
9.3
5.8
CPx300
CPX300HL/NG
tbc
tbc