page no. 39 of 68
CPx Range Users, Installation & Servicing Instructions Doc Ref M201 issue 2.9 Nov 2018.
WARNING:
If continued unsuccessful ignition attempts
are made it is possible to accumulate a
significant quantity of oil and oil mist in the
combustion chamber which, if the burner then fires, can
result in a dangerous situation. Any such accumulation
of oil must be removed by safe means before any further
attempt to light the burner.
1. Ensure the oil gauge is connected. Remove the sample
point cover plug from the outlet flue length and insert a
CO2 measuring instrument.
2. Turn ON the main electricity supply and check that the
following sequence of events occur. i) Burner fan runs. ii)
Ignition spark is heard. iii) Main flame is established.
2.6.5.2.2.1.1 CPxO30 to CPx175 inc
Low Fire
Pressure
Adjustment
High Fire
Pressure
Adjustment
Gauge
Connection
Check that the High Fire burner pump pressure agrees
with that stated on the heater data plate and in section
1.2. If necessary adjust the pump pressure by rotating
the high fire adjustment screw clockwise (+ positive),
anticlockwise (- negative)
Check that the Low Fire pump pressure agrees with that
stated on the heater data plate and in section 1.2. If
necessary adjust the pump pressure by rotating the low
fire adjustment screw clockwise (+ positive), anticlockwise
(- negative)
If any adjustments have been made, re-check both high
and low fire once more.
2.6.5.2.2.1.2 CPx200 & CPx250 inc
Burner
Pressure
Adjustment
Gauge
Connection
Hi/Low operation works on the basis that either a single
or both nozzles are open. Check that the burner pump
pressure agrees with that stated on the heater data plate
and in section 1.2. If necessary adjust the pump pressure
by rotating the burner adjustment screw clockwise (+
positive), anticlockwise (- negative)
If any adjustments have been made, re-check both high
and low fire once more.
2.6.5.2.2.1.3 CPx300
Burner
Pressure
Adjustment
Gauge
Connection
Hi/Low operation works on the basis that either a single
or both nozzles are open. Check that the burner pump
pressure agrees with that stated on the heater data plate
and in section 1.2. If necessary adjust the pump pressure
by rotating the burner adjustment screw clockwise (+
positive), anticlockwise (- negative)