Powrmatic CPx 120 Скачать руководство пользователя страница 48

page no. 48 of 68      

    

CP

x Range   Users, Installation & Servicing Instructions  Doc Ref M201 issue 2.9 Nov 2018. 

FAULTS

POSSIBLE CAUSES

SOLUTION

The burner doesn’t 

start when the limit 

thermostat closes.

Lack of electrical supply.

Check presence of voltage in the L1-N clamps of the 7 pin 

plug.
Check the condition of the fuses.
Check that safety thermostat is not lock out.

Lack of gas

Check the manual cock opening
Check that the valves charge over to the opening position 

and there are not short circuits.

The gas pressure switch does not close its 

contact.

Adjust them.

The connections in the control box are wrongly 

inserted.

Check and connect all the plugs

The air pressure switch is changed over to the 

operational position.

Replace the pressure switch

Burner tends to pull 

the flame when 

switching from 1st 

to 2nd stage.

Output ratio between 1st and 2nd stage 

greater than 1:2.

Restore correct maximum ratio of 1:2, making sure 1st stage 

output is no less than the operating range’s minimum.

High air excess in 1st stage

Restore the correct air excess value (λ min. = 1.3) see manual

The burner runs  

normally in the 

prepurge and 

ignition cycle and 

locks out after 

about 3 seconds.

Phase and neutral connection is inverted.

Invert them.

The earth connection lacks or is inefficient.

Make the earth connection efficient.

The ionization probe is earthed or not in 

contact with the flame, or its wiring to the 

control box is broken, or there is a fault on its 

insulation to the earth.

Check the right position and if necessary set it according to 

the instructions.
Reset the electrical connection.
Replace the faulty connection.

The burner starts 
with an ignition 
delay.

The ignition electrodes is wrongly positioned.

Adjust it according to the instructions.

Air output is too high.

Set the air output according to the instructions.

Valve brake is too close with insufficient gas 
output.

Adjust it.

The burner doesn’t 
change over the 
2nd stage.

The air damper is locked.

Check the right working.
Check the right electrical connection

The 2nd stage gas valve doesn’t pull in.

Failed valve: replace it.
The air damper doesn’t close completely and therefore it 
doesn’t pull in the 2nd stage valve micro: check the micro 
working.

The burner locks 
out after the 
prepurge phase 
due to flame failure.

The solenoid valves is passing too little gas.

Check the pressure in the network and/or adjust the solenoid 

valve according to the instructions of this manual.

The solenoid valves are defective.

Change them

The ignition arc is irregular or has failed.

Check the right insertion of the connectors.
Check the right position of the electrode according to the 

instructions of this manual.

The pipe has not been purged from the air.

Carry out a complete breathing of the line of gas-supply.

The burner locks 
out during the 
prepurge phase.

The air pressure switch does not change over 

to the operational position.

The pressure switch is faulty, change it.
The air pressure is too low, (the head is bad adjusted).

The flame exists.

Faulty valves: replace them.

The pressure test point is badly positioned.

Place it in the right position according to the instructions.

The burner 
continues to repeat 
the starting cycle 
without going on 
lock-out.

The gas pressure in the gas main lies very close 

to the value to which the gas pressure switch 

has been set. The sudden falling off pressure at 

the opening of the valve causes the opening 

of the pressure switch. However this only 

temporarily, because the valve immediately 

closes again, so then does the pressure switch, 

because the pressure builds up again, causing 

the cycle to be repeated over and over.

Lower and set the pressure switch.

Содержание CPx 120

Страница 1: ...w w w p o w r m a t i c c o u k CPx User Installation Servicing Manual Issue 2 9 November 2018 Doc Ref M201 Issue 2 9 Nov 2018 ErP COMPLIANT S E P T E M B E R 2 0 1 8...

Страница 2: ...heater must have been installed by a competent qualified installer and in accordance with the manufacturer s instructions building regulations and local regulations 2 The heater has been professional...

Страница 3: ...ation 2 1 Fitting the unit 27 2 2 Fitting the flue 29 2 3 General Identification of Items 29 2 4 Electrical Cable Installation 30 2 5 Wiring Diagrams 33 2 6 Commissioning and Testing 36 2 7 Servicing...

Страница 4: ...i e Summer The heater fan alone will run at the dictate of the external controls to provide air movement Winter The heater will operate normally If the heater has not been left operational proceed as...

Страница 5: ...t annually and preferably at the end of the heating season IMPORTANT Free access must be maintained to and around the heater for servicing purposes and the air supply to the heater must not be restric...

Страница 6: ...ow CPx EA Style Casing is extended to enclose the burner The heater is fully weatherproof and designed for external applications only Available in TD HD RT and SD variants Variant types are UF Upright...

Страница 7: ...04 904 904 904 1104 1104 1260 1330 1330 Depth Excludes burner mm 732 732 927 927 927 1200 1200 1399 1399 1599 1599 1915 2165 2715 Installation Clearances UF Upright Freeblowing Front mm 1000 1000 1000...

Страница 8: ...mm 1535 1535 1661 1661 1923 1923 2021 2021 2021 2021 G All mm 864 864 944 944 1122 1122 1122 1122 1122 1122 H Gas mm 276 276 252 280 280 280 300 300 300 508 Oil mm 196 202 202 228 228 228 228 247 247...

Страница 9: ...All mm 125 125 150 150 150 175 175 175 200 200 E All mm 150 150 150 150 150 200 200 200 240 240 F All mm 1535 1535 1661 1661 1923 1923 2021 2021 2021 2021 G All mm 864 864 944 944 1122 1122 1122 1122...

Страница 10: ...G All mm 864 864 944 944 1122 1122 1122 1122 1122 1122 L Duct Spigot mm 632 632 824 824 1100 1100 1299 1299 1499 1499 M mm 569 569 644 644 804 804 804 804 1004 1004 N All mm 125 125 125 125 150 150 1...

Страница 11: ...B M F C E H Model 360 440 590 A All mm 1915 2165 2715 B All mm 1260 1330 1330 C All mm 2615 3065 3365 D All mm 250 300 300 E All mm 865 965 1265 F All mm 1550 1900 1900 G Gas mm 508 580 840 Oil mm 508...

Страница 12: ...80 840 Oil mm 468 468 680 H All mm 830 865 865 L Duct Spigot mm 1815 2065 2615 M mm 1160 1230 1230 Head Plan 3b 4 4 Notes The Heat Exchanger and Fan Section can be split on the Section Split Line Flue...

Страница 13: ...1900 G All mm 650 650 950 H All mm 2565 2815 3665 L Duct Spigot mm 1815 2065 2615 M mm 1160 1230 1230 P All mm 760 860 1160 Notes The Heat Exchanger and Fan Section can be split on the Section Split...

Страница 14: ...50 650 950 H All mm 2565 2815 3665 L Duct Spigot mm 1815 2065 2615 M mm 1160 1230 1230 Notes The Heat Exchanger and Fan Section can be split on the Section Split Line Primary flue and cowl provided as...

Страница 15: ...838 865 965 1265 F All mm 627 627 677 677 775 775 775 775 775 775 n a n a n a G All mm 585 585 640 640 738 738 738 738 738 738 765 865 1165 H All mm 527 527 577 577 675 675 675 675 675 675 n a n a n a...

Страница 16: ...alues and Nett flue gas temperatures are given for guidance and measured values will depend on site conditions Air Pressure Switch settings are given for guidance and measured values will depend on si...

Страница 17: ...tt flue gas temperatures are given for guidance and measured values will depend on site conditions Air Pressure Switch settings are given for guidance and measured values will depend on site condition...

Страница 18: ...1 6 0 4 12 7 12 5 57 6 49 1 0 1 213 169 CPx150 5 2 9 0 8 12 7 12 2 65 3 49 9 0 1 182 139 CPx175 3 4 2 0 5 13 0 11 8 68 5 51 8 0 1 213 146 CPx200 6 4 0 0 4 12 4 12 1 91 2 65 8 0 1 157 79 CPx250 8 6 0...

Страница 19: ...RL34 MZ TC 4 5x60B 3x60S tbc tbc tbc tbc tbc tbc Notes CO2 values and Nett flue gas temperatures are given for guidance and measured values will depend on site conditions Air Pressure Switch settings...

Страница 20: ...d UF HF Weight CPx Weight CPX NCA Weight CPx EA Std Motor Uprated m s m h qty mm m Pa Pa dB A kg kg kg CPx30 0 97 3492 2 203 15 188 250 67 7 168 tbc tbc CPx45 0 86 3096 2 254 21 222 250 35 8 173 tbc t...

Страница 21: ...Px300 7 5 3 1500 140002251 160x1 SPA 142001619 1610 38 142003655 3 381 x 381 x2 1402CFAN510 T 2DECK Drive Data Standard Motor Fan Pulley e Fan Pulley TaperLock f Belt s g Fuse Contactor Relay Soft Sta...

Страница 22: ...CK CPx300 11 0 3 1500 140002610 140x2 SPA 142001013 2012 42 142201242 3 381 x 381 x2 1402CFAN510 T 2DECK Fan Pulley e Fan Pulley TaperLock f Belt s g Fuse Contactor Relay Soft Start Overload Size Pt n...

Страница 23: ...the heater is located particularly where special risks are involved such as areas where petrol vehicles are housed where cellulose spraying is carried out in wood working departments etc IMPORTANT He...

Страница 24: ...ode 1 3 7 Gas Fired Heaters 1 3 7 1 Related Documents All Oil Fired CPx heaters comply with the following European Directives Energy Related Product Directive 2009 125 EC Electromagnetic Compatibility...

Страница 25: ...rectly from the room and connected to a flue that evacuates the products of combustion directly from the room additional provision for natural or mechanical ventilation is required These being Natural...

Страница 26: ...iction in ductwork All ducting must be independently supported of the air heater All delivery and return air ducts including air filters jointing and any insulation or lining must be constructed entir...

Страница 27: ...0 1650 B Rear mm 1000 C Above mm 1000 D Side Blank panel mm 150 E Side Louvred mm 1000 To the front The depth of the heater To the rear 1 0m To the side having louvred lower panels 1 0m To the side ha...

Страница 28: ...ing must be observed NOTE CPx 250 CPx 300 heaters have louvred lower panels on both sides The minimum clearance of 0 15m is increased to 0 5m NOTE Smaller heaters are supplied with one blank side pane...

Страница 29: ...s Use of a chimney system having joint seals will minimise any leakage from the flue system The heater tee is provided with a collection tray and the outlet from this should be run to a drainage point...

Страница 30: ...control circuit 230V via a room thermostat time clock etc and if applicable the remote low level lockout reset Reference must be made to Section 1 2 to ascertain the electrical loading of the unit s...

Страница 31: ...terminals both mains input and controller are located on the electrical chassis panel behind the bottom front panel of the heater which firstly has to be removed L N E L3 N E L2 L1 Mains input of eith...

Страница 32: ...terminal strip They are as follows 2 4 Electrical Cable Installation terminal 7 230V Heat Demand terminal 8 230V Main Fan Only terminal 9 Lockout indication 230V Output terminal 10 Burner reset Neutr...

Страница 33: ...10v 0 10v SEN 2 COM SEN 1 F Gr Yellow 0 5 Br 0 5 Blu 0 5 Red 0 5 Yel 0 5 2 Core Cable Br 0 75 Blu 0 75 Or 0 5 Or 0 5 Or 0 5 Or 0 5 RIELLO GULLIVER Link removed by Powrmatic POWRMATIC LTD Powrmatic Ltd...

Страница 34: ...Yel 0 5 Yel 0 5 Vi 0 5 6 5 4 2 3 1 10 9 11 8 7 NO COM NC R S TRP N L Wh 0 5 Wh 0 5 Blk 0 5 Blu 0 5 Blk 0 5 Yel 0 5 J Br 0 5 Blu 0 5 11 12 L Br 0 5 5 Core Cable MC200 fuelsaver Cabinet Unit L E N Fan...

Страница 35: ...Grey 1 5 Br 1 5 Blk 1 5 Grey 1 5 LIMIT FAN c E 5 Core Cable Gr Yellow 1 0 O N Plug socket on kit form heaters only Plug socket on split form heaters only D b4 s3 N L t2 t1 b4 s3 N L t2 t1 Wiring Legen...

Страница 36: ...d e g by adjustment of duct outlet nozzles and balancing of the duct system Conversely if the duct system resistance is greater than the available air pressure of the heater supplied the system resist...

Страница 37: ...ernor adjustment is within 50 to 75 of its range Clockwise negative anti clockwise positive 5 Check that the Low Fire burner gas pressure agrees with that stated on the heater data plate and in sectio...

Страница 38: ...is provides information on how to adjust the burner system checks and fault finding detail IMPORTANT DO NOT use burner settings from the burner instruction booklet The burners are specifically adjuste...

Страница 39: ...re by rotating the high fire adjustment screw clockwise positive anticlockwise negative Check that the Low Fire pump pressure agrees with that stated on the heater data plate and in section 1 2 If nec...

Страница 40: ...6 6 Fan Limit Stat Ensure that the limit settings are as follows Thermostat settings Fan Off 86 F 30 C Fan On 122 F 50 C Limit CPx 30 90 150 175 212 F 100 C CPx 120 230 F 110 C CPx 200 300 248 F 120 C...

Страница 41: ...mbly 2 7 3 Heat Exchanger Cleaning 1 Removing the upper rear panel of the heater exposes the heat exchanger rear clean out panel 2 Removing the fan limit thermostat s as described in section 2 6 6 4 d...

Страница 42: ...stment of the second stage air damper position is carried out by setting the air damper indicator 3 Slightly loosen locknut clockwise and adjust by turning screw till the required setting is shown lev...

Страница 43: ...ST STAGE ADJUSTMENT By adjusting the micrometric screw cam I regulates the position of the 1st stage air damper default value 25 SECOND STAGE ADJUSTMENT Cam II regulates the position of the 2nd stage...

Страница 44: ...y loosen locknut clockwise and adjust by turning screw till the required setting is shown level with the locknut Once the setting is achieved tighten locknut anticlockwise may require re adjust when t...

Страница 45: ...ect drive fan units 1 Remove the lower panels of the heater to gain access to the fan section 2 Disconnect the fan motor electrical leads from the terminal strip see section 2 5 or the accompanying wi...

Страница 46: ...minals by pushing a small screwdriver into the clamp release holes adjacent to the clamps 4 Remove the 2 screws securing the thermostat to the heater panel and withdraw thermostat 5 Reassemble new uni...

Страница 47: ...signal lamp is steady on The control box has a diagnostic function that can identify the likely causes of any malfunctions indicator RED LED In order to be able to use this function press and hold the...

Страница 48: ...according to the instructions Air output is too high Set the air output according to the instructions Valve brake is too close with insufficient gas output Adjust it The burner doesn t change over th...

Страница 49: ...dirty Clear it The photoresistance is defective Change it Flame moves away or fails Check pressure and output of the fuel Check air output Change nozzle Check the coil of solenoid valve 1st stage Burn...

Страница 50: ...37150 141937150 Riello 35s Oil Burner c w Nozzle Lead BNR030CPxO MK3 ERP BNR045CPxO MK3 ERP BNR060CPxO MK3 ERP BNR090CPxO MK3 ERP BNR120CPxO MK3 ERP Nozzle 35 sec 28 sec 141521059 141522381 141522600...

Страница 51: ...937150 141937082 141937150 142992790 142992790 Riello 35s Oil Burner c w Nozzle Lead BNR150CPxO MK3 ERP BNR175CPxO MK3 ERP BNR200CPxO MK3 ERP BNR250CPxO MK3 ERP BNR300CPxO HILO MK3 Nozzle 35 sec 28 se...

Страница 52: ...223 17 x CPx0900223 23 x CPx1500223 n a MC200 Controller MC200CAB Control Panel Std On Off CPX3 90 CP MK3 CPX3 90 CP MK3 CPX3 90 CP MK3 CPX3 90 CP MK3 CPX12 175 CP MK3 20mm x 3mm Plain Tape Gasket 6m...

Страница 53: ...ler MC200CAB Control Panel Std On Off CPX3 90 CP MK3 CPX3 90 CP MK3 CPX3 90 CP MK3 CPX3 90 CP MK3 CPX12 175 CP MK3 20mm x 3mm Plain Tape Gasket 6m x 170272210 7m x 170272210 10mm x 3mm Sponge Strip Ga...

Страница 54: ...2991 142992990 Sensor Probe Gas 142992989 142992987 Photocell Oil 141979531 Electrode Oil 142924310 142924311 HT Lead Gas Oil 142992998 142992999 Probe Lead 142992986 Speed Gear Pump 141979551 Coil 1...

Страница 55: ...Electrode Oil 142924311 142992793 HT Lead Gas Oil 142992998 142992999 142992998 142993000 142993001 142993002 Probe Lead 142992986 145604654 Speed Gear Pump 141979551 141979552 142992633 Coil 1 Coil 2...

Страница 56: ...2000602 n a 142000602 n a 142001689 142001689 142001675 Motor T lock Standard LPH n a 142003350 n a 142003350 n a 142003360 142003360 142003360 Fan Pulley Standard LPH n a 142001689 n a 142001675 n a...

Страница 57: ...0601 142000602 142000602 Motor T lock Standard LPH n a 142003360 n a 142003856 142003856 142161028 142003856 142003856 Fan Pulley Standard LPH n a 142002604 n a 142001825 142001825 142001825 142001689...

Страница 58: ...001619 142001013 Motor T lock Standard LPH 142003856 142003655 142161028 142003655 142003655 142201242 Fan Pulley Standard LPH 142001619 142001619 142002604 142002604 142002494 142001823 Fan T lock St...

Страница 59: ...base of the nozzle holder whilst un doing and removing the original nozzle 6 Fit replacement nozzle again by holding the base of the nozzle holder with a spanner whilst tightening nozzle 7 Refit all...

Страница 60: ...essure agrees with that stated on the heater data plate and in section 1 2 If necessary adjust the pump pressure by rotating the burner adjustment screw clockwise positive anticlockwise negative If an...

Страница 61: ...x200 2 5 2 0 x 60S CPX200HL 28 10 0 145 10 0 101 5 CPx250 3 5 3 0 x 60S CPX250HL 28 10 0 145 10 0 101 5 CPx300 tbc CPX300HL 28 tbc tbc tbc tbc Riello Burner Settings 35sec Oil Diesel Net CV Hi 42 69MJ...

Страница 62: ...crew and remove the screws 5 pull out the head assembly support 6 turning it slightly to the right taking care not to change the setting position on the elbow bracket during dismantling 4 Remove the N...

Страница 63: ...3 5 CPx150 CPX150HL LPG 10 6 4 4 CPx175 CPX175HL LPG tbc tbc CPx200 CPX200HL LPG 6 9 3 9 CPx250 CPX250HL LPG 10 0 4 7 CPx300 CPX300HL LPG tbc tbc Propane LPG to Natural Gas Conversion Data Nominal Inl...

Страница 64: ...cont 150 175 200 250 300 Rated Heat Capacity kW 150 0 175 0 200 0 250 0 tbc Low Heat Input Nett CV kW 94 8 122 0 152 8 183 3 tbc Minimum Heat Capacity kW 91 1 116 5 145 5 175 9 tbc Useful Efficiency1...

Страница 65: ...nce factors for individual components are as follows Segmented 90 bend 0 5 45 Elbow 0 4 Cowl 1 0 Qm Mean Density of the column of exhaust gas in kg m3 97000 300 Tm Where the mean temperature of the co...

Страница 66: ...page no 66 of 68 CPx Range Users Installation Servicing Instructions Doc Ref M201 issue 2 9 Nov 2018 Notes...

Страница 67: ...page no 67 of 68 CPx Range Users Installation Servicing Instructions Doc Ref M201 issue 2 9 Nov 2018 Notes...

Страница 68: ...t Dublin 24 tel 353 0 1452 1533 fax 353 0 1452 1764 e mail info powrmatic ie web www powrmatic ie Getting In Touch Powrmatic pursues a policy of continues improvement in both design and performance of...

Отзывы: