page no. 19 of 68
CPx Range Users, Installation & Servicing Instructions Doc Ref M201 issue 2.9 Nov 2018.
Riello Burner Settings - 28sec Oil - Kerosene - Net CV (Hi = 47.00MJ/kg)
MODEL
Burner Type
Nozzle
High Fire
Low Fire
Burner Pressure
Fuel Input
Burner Pressure
Fuel Input
bar
psi
kg/h
bar
psi
kg/h
CPx30
RG1RKD
0.75 x 60S
10.0
140
2.70
7.0
100
1.89
CPx45
RG2D
1.25 x 60S
10.0
140
4.15
7.0
100
3.27
CPx60
RG2D
1.50 x 60S
10.0
140
5.36
7.0
100
4.07
CPx90
RG3D
2.50 x 60S
10.0
140
8.28
7.0
100
6.16
CPx120
RG3D
3.00 x 60S
10.0
140
10.91
7.0
100
8.50
CPx150
RG3D
3.75 x 60B
10.0
140
13.45
7.0
100
9.82
CPx175
RG4D
4.50 x 60B
10.0
140
16.45
7.0
100
11.60
CPx200
RG5D
2.5 + 2.0 x 60S
10.0
140
17.96
10.0
140
10.00
CPx250
RG5D
3.5 + 3.0 x 60S
10.0
140
23.69
10.0
140
13.10
CPx300
RL34 MZ TC
4.5x60B + 3x60S
tbc
tbc
tbc
tbc
tbc
tbc
Notes:
CO2
values and Nett flue gas temperatures are given for guidance and measured values will depend on site conditions.
* Air Pressure Switch settings are given for guidance and measured values will depend on site conditions.
MODEL
Head
Setting
no.
Combustion Air
Nominal CO2 (±0.5)
Nox
Smoke
Nett Flue Temp
High Fire
Low Fire
High Fire
Low Fire
High Fire
Low Fire
High Fire
Low Fire
No.
No.
No.
%
%
ppm
ppm
No.
°C
°C
CPx30
1.3
1.5
0.25
11.8
12.5
67.5
65.5
0-1
133
96
CPx45
0
1.1
0.25
12.5
12.6
70.3
65.3
0-1
209
138
CPx60
2
1.9
0.45
12.7
12.6
74.5
65.0
0-1
158
110
CPx90
0.5
0.8
0.2
12.5
12.5
80.3
68.2
0-1
214
138
CPx120
3
1.6
0.4
12.7
12.6
57.6
49.1
0-1
213
169
CPx150
5
2.9
0.8
12.7
12.2
65.3
49.9
0-1
182
139
CPx175
3
4.2
0.5
13.0
11.8
68.5
51.8
0-1
213
146
CPx200
6
4.0
0.4
12.4
12.1
91.2
65.8
0-1
157
79
CPx250
8
6.0
0.6
12.7
12.4
83.3
62.4
0-1
219
117
CPx300
tbc
tbc
tbc
tbc
tbc
tbc
tbc
tbc
tbc
tbc