Installation Checklist
All packing materials and restraints have been removed from each cabinet.
Each cabinet in the UPS system is placed in its installed location.
All cabinets (except stand-alone cabinets) are bolted together.
A ground bond is installed between all cabinets that are bolted together.
All switch boards, conduits, and cables are properly routed to the UPS and auxiliary
cabinets.
Power cables are terminated on bypass terminals
on 460V systems, El
El 5
on all other systems).
Power cables are terminated on the
input breaker (El
on 460V systems,
on all other systems).
A ground conductor is properly installed.
N is used, no other N-G bonds exist downstream from the UPS.
Battery
cables
and harness are terminated on the
battery contactor E4 and
Internal battery cabinet connections have been completed (bus bars, plugs, etc.)
Air conditioning equipment is installed and operating correctly.
The area around the
UPS system is clean and dust free. (It is recommended
that:the UPS be installed on a sealed concrete pad on a seated concrete floor.)
Adequate workspace exists around the UPS and other cabinets.
Adequate lighting is
around all UPS equipment
A
o&t is
within 26 feet of the UPS equipment.
Each Remote Monitor Panel (RMP) is mounted in its installed location. (OPTIONAL)
The
wiring for each RMP is terminated inside the UPS cabinet.
(OPTIONAL)
The Remote Emergency Power Off (REPO) device is mounted in its installed location
and its wiring terminated inside the UPS cabinet. (OPTIONAL)
Summary alarms and/or building
are wired
(OPTIONAL)
A Relay interface Module (RIM) mounted in
installed location and its
is
terminated inside the UPS cabinet. (OPTIONAL)
A Remote
Disconnect control is mounted in its installed location and its wiring
is terminated inside the UPS and Battery Cabinet.
Plus UPS Installation
9
Содержание Plus 80
Страница 1: ...0 Powerware Plus 80 Unintemqtibk Power Supply Operation 164200252 Rev A...
Страница 55: ...a 1 a Pe WNP U N I N T E R R U P T I B L E P O W E R S Y S T E M S I i b I EXlDE ELECTRONICS...
Страница 72: ...I I I I I I U N I N T E 4 f RRUPTIB Z a L E P O W E R SYSTEMS P 10 I I I I I I I L INS I HIDE fLECTRONICS...
Страница 88: ...I I I I I I IO I I I I b I I NOTES 10 Powemam Plus 60 UPS ln stallation Manual...
Страница 146: ...1111111111111111 llllllllllllllll 1111111111111111 llllllllllllllll A 12 Pawemare Plus 80 UPS hstallation Manual...
Страница 147: ...2 I FRONT Powerware Plus 80 UPS installation Manual A 13...
Страница 153: ...5 61 CRE47Eo By L ORLANDO RMWON A ONE B 269r Powemare Plus 90 UPS lnstailation Manual A 19...
Страница 157: ...19 0 FLUSH MOUNT 750 I A t 00 00 iI I F 190 5 7 50 Relay Interface Module DEScX p RELAY INTERFACE MODULE 33 _...