6--2
Powerware BPIV (10 kVA--30 kVA) Installation and Operation
164201406 Rev. C 013004
6.2
To install an IRC:
1.
Be sure the UPS system is turned off and all power sources are removed.
(See the operation section of this manual for shutdown instructions.)
2.
Install the IRC into an open X-Slot on the rear panel of the UPS Cabinet.
Remove X-Slot cover panel to gain access to the X-Slot.
3.
Install wiring from the IRC to the monitoring equipment using ½-in. conduit
through the cable exit opening in the IRC (see Figure 6---1).
4.
Connect wiring between the the IRC and the monitoring equipment using
terminations shown in Table 6---1. See Figure 6---1 for plug-in terminal block
locations.
Table 6---1. IRC Wire Terminations
IRC Terminal
Function
Remarks
J2---1
NC
J2---2
COM
Normal Mode
J2---3
NO
J2---4
NC
J2---5
COM
Bypass Mode
J2---6
NO
J2---7
NC
J2---8
COM
Battery Mode
J2---9
NO
J2---10
NC
J2---11
COM
Alarm Mode
J2---12
NO
Maximum contact rating: 250 VAC, 30 VDC @ 5A
Wire Range: 16---24 AWG
5.
To check the operation of the IRC, ensure that the UPS system is supplying the
load via the inverter or bypass. If the indicators on the customer’s monitoring
equipment show the appropriate status, then it is operating correctly.
If the IRC is not operating correctly, check the wiring, the fuse on the IRC, and
the plug-in terminal blocks for proper seating. If all connections are secure but
the IRC still does not operate correctly, replace the fuse. If this does not
correct the problem, contact your local field service office for verification that
the IRC is working correctly.
Содержание BPIV
Страница 1: ...www powerware com BPIV INSTALLATION OPERATION MANUAL UPS 10 15 kVA 20 30 kVA...
Страница 19: ...Powerware BPIV 10 kVA 30 kVA Installation and Operation 164201406 Rev C 013004 Section I Installation...
Страница 79: ...Powerware BPIV 10 kVA 30 kVA Installation and Operation 164201406 Rev C 013004 Section II Operation...
Страница 104: ...8 10 Powerware BPIV 10 kVA 30 kVA Installation and Operation 164201406 Rev C 013004 This Page Intentionally Left Blank...
Страница 128: ...9 24 Powerware BPIV 10 kVA 30 kVA Installation and Operation 164201406 Rev C 013004 This Page Intentionally Left Blank...
Страница 138: ...10 10 Powerware BPIV 10 kVA 30 kVA Installation and Operation 164201406 Rev C 013004 This Page Intentionally Left Blank...
Страница 142: ...11 4 Powerware BPIV 10 kVA 30 kVA Installation and Operation 164201406 Rev C 013004 This Page Intentionally Left Blank...
Страница 174: ...15 4 Powerware BPIV 10 kVA 30 kVA Installation and Operation 164201406 Rev C 013004 This Page Intentionally Left Blank...
Страница 262: ...W 2 Powerware BPIV 10 kVA 30 kVA Installation and Operation 164201406 Rev C 013004 This Page Intentionally Left Blank...
Страница 263: ......
Страница 264: ...164201406 Rev C 164201406C...