![Powerware BPIV Скачать руководство пользователя страница 136](http://html1.mh-extra.com/html/powerware/bpiv/bpiv_installation-and-operation-manual_1592093136.webp)
10--8
Powerware BPIV (10 kVA--30 kVA) Installation and Operation
164201406 Rev. C 013004
10.13Options Cabinet Maintenance Bypass Transfer
To transfer the critical load to Maintenance Bypass, perform the following
procedure:
1.
Transfer critical load to bypass by performing procedure in paragraph 10.6.
2.
Manually set the Options Cabinet Maintenance Bypass Switch to
BYPASS
, by
turning slowly through the
TEST
position to
BYPASS
.
The input, output, battery and bypass backfeed contactors open and the PPU is
turned off. The maintenance bypass source supplies the critical load.
WARNING:
Power is present inside the UPS and Options cabinets
.
10.14
Using the Power Distribution Module
If the UPS system contains the optional Power Distribution Module, access to the
PDM circuit breakers can be gained by performing the following procedure.
1.
Slide the Options cabinet top cover latches to the rear of the cabinet.
2.
Lift and secure cover in the upright position using latching slide bar.
10.15
Using the LOAD OFF Pushbutton
An UPS Load Off is initiated by the red
LOAD OFF
pushbutton on the UPS Control
Panel. This pushbutton can be pressed to control the UPS output. The UPS
LOAD OFF
pushbutton de-energizes the critical load and powers down the UPS.
The UPS (including Bypass) remains off until restarted.
10.15.1To Use the LOAD OFF Pushbutton
1.
Press the
LOAD OFF
pushbutton.
The Unit Shutdown screen appears, providing a choice to proceed with the shutdown
or to abort the shutdown.
WARNING:
All power to the critical load is lost when
YES
is selected in the following step. You
should use this feature only when you want to de-energize the critical load.
2.
To shut down the UPS, select
YES
from the Unit Shutdown menu, and hold for
two seconds . To abort the shutdown, select
NO
.
When YES is selected and held for two seconds, the input, output, battery and
bypass backfeed contactors open and the PPU is turned off.
CAUTION:
Do not attempt to restart the system after Load Off until the cause of the
shutdown has been identified and cleared.
3.
To restart the UPS after pressing the
LOAD OFF
pushbutton, follow the
procedure, in paragraphs 10.2 or 10.3.
Содержание BPIV
Страница 1: ...www powerware com BPIV INSTALLATION OPERATION MANUAL UPS 10 15 kVA 20 30 kVA...
Страница 19: ...Powerware BPIV 10 kVA 30 kVA Installation and Operation 164201406 Rev C 013004 Section I Installation...
Страница 79: ...Powerware BPIV 10 kVA 30 kVA Installation and Operation 164201406 Rev C 013004 Section II Operation...
Страница 104: ...8 10 Powerware BPIV 10 kVA 30 kVA Installation and Operation 164201406 Rev C 013004 This Page Intentionally Left Blank...
Страница 128: ...9 24 Powerware BPIV 10 kVA 30 kVA Installation and Operation 164201406 Rev C 013004 This Page Intentionally Left Blank...
Страница 138: ...10 10 Powerware BPIV 10 kVA 30 kVA Installation and Operation 164201406 Rev C 013004 This Page Intentionally Left Blank...
Страница 142: ...11 4 Powerware BPIV 10 kVA 30 kVA Installation and Operation 164201406 Rev C 013004 This Page Intentionally Left Blank...
Страница 174: ...15 4 Powerware BPIV 10 kVA 30 kVA Installation and Operation 164201406 Rev C 013004 This Page Intentionally Left Blank...
Страница 262: ...W 2 Powerware BPIV 10 kVA 30 kVA Installation and Operation 164201406 Rev C 013004 This Page Intentionally Left Blank...
Страница 263: ......
Страница 264: ...164201406 Rev C 164201406C...