POWER WIRING INSTALLATION NOTES
164201406---1
A---13
Powerware BPIV (10 kVA--30 kVA) Installation and Operation
164201406 Rev. C 013004
Table Q. Power Cable Conduit Requirements Powerware BPIV (20 kVA--30 kVA)
Powerware
System
Voltage
Terminal
Number of
Wires in
Conduit
Minimum
Conduit
Trade Size
(inches)
Number of
Conduits
AC Input to UPS
(A, B, C, Gnd)
4
1-1/4
1
BPIV
---
30/20
208
AC
AC Input to Bypass
(A, B, C, Neut, Gnd)
5
1-1/4
1
AC
Output
(A, B, C, Neut, Gnd)
5
1-1/4
1
AC Input to UPS
(A, B, C, Gnd)
4
3/4
1
BPIV
---
30/20
480
AC
AC Input to Bypass
(A, B, C, Neut, Gnd)
5
3/4
1
C
Output
(A, B, C, Neut, Gnd)
5
3/4
1
AC Input to UPS
(A, B, C, Gnd)
4
1/2
1
BPIV---30/20
600
AC
AC Input to Bypass
(A, B, C, Neut, Gnd)
5
1/2
1
C
Output
(A, B, C, Neut, Gnd)
N/A
N/A
N/A
BPIV
---
30/20
288
DC
External Battery DC Source
(Positive, Negative, Gnd)
3
1
1
AC Input to UPS
(A, B, C, Gnd)
4
1-1/4
1
BPIV---30/25
208
AC
AC Input to Bypass
(A, B, C, Neut, Gnd)
5
1-1/4
1
C
Output
(A, B, C, Neut, Gnd)
5
1-1/4
1
AC Input to UPS
(A, B, C, Gnd)
4
3/4
1
BPIV---30/25
480
AC
AC Input to Bypass
(A, B, C, Neut, Gnd)
5
3/4
1
C
Output
(A, B, C, Neut, Gnd)
5
3/4
1
AC Input to UPS
(A, B, C, Gnd)
4
3/4
1
BPIV---30/25
600
AC
AC Input to Bypass
(A, B, C, Neut, Gnd)
5
3/4
1
C
Output
(A, B, C, Neut, Gnd)
N/A
N/A
N/A
BPIV---30/25
288
DC
External Battery DC Source
(Positive, Negative, Gnd)
3
1
1
Содержание BPIV
Страница 1: ...www powerware com BPIV INSTALLATION OPERATION MANUAL UPS 10 15 kVA 20 30 kVA...
Страница 19: ...Powerware BPIV 10 kVA 30 kVA Installation and Operation 164201406 Rev C 013004 Section I Installation...
Страница 79: ...Powerware BPIV 10 kVA 30 kVA Installation and Operation 164201406 Rev C 013004 Section II Operation...
Страница 104: ...8 10 Powerware BPIV 10 kVA 30 kVA Installation and Operation 164201406 Rev C 013004 This Page Intentionally Left Blank...
Страница 128: ...9 24 Powerware BPIV 10 kVA 30 kVA Installation and Operation 164201406 Rev C 013004 This Page Intentionally Left Blank...
Страница 138: ...10 10 Powerware BPIV 10 kVA 30 kVA Installation and Operation 164201406 Rev C 013004 This Page Intentionally Left Blank...
Страница 142: ...11 4 Powerware BPIV 10 kVA 30 kVA Installation and Operation 164201406 Rev C 013004 This Page Intentionally Left Blank...
Страница 174: ...15 4 Powerware BPIV 10 kVA 30 kVA Installation and Operation 164201406 Rev C 013004 This Page Intentionally Left Blank...
Страница 262: ...W 2 Powerware BPIV 10 kVA 30 kVA Installation and Operation 164201406 Rev C 013004 This Page Intentionally Left Blank...
Страница 263: ......
Страница 264: ...164201406 Rev C 164201406C...