13--14
Powerware BPIV (10 kVA--30 kVA) Installation and Operation
164201406 Rev. C 013004
Inverter Version
0.97
Machine Control Version 0.99
Comm Server Version
0.98
Display Version
0.96
08/11/2000 14:13:03.000 STATUS: CSB Power Supply On
08/11/2000 14:13:03.043 NOTICE: Inverter Initializing
08/11/2000 14:13:05.721 STATUS: UPS Power Supply OK
08/11/2000 14:13:05.728 NOTICE: Input Under Voltage
08/11/2000 14:13:05.729 NOTICE: Output Under Voltage
08/11/2000 14:13:05.729 NOTICE: Bypass Under Voltage
08/11/2000 14:13:05.749 ALARM: Rectifier Under Voltage
08/11/2000 14:13:10.459 ALARM: Battery Under Voltage
08/11/2000 14:13:12.954 NOTICE: Battery Voltage Low
08/11/2000 14:13:13.165 NOTICE: Battery Not Present
08/11/2000 14:13:34.710 STATUS: PPU Shutdown
08/11/2000 14:13:57.773 NOTICE: Check Modem
08/11/2000 14:14:33.520 ALARM: Inverter Tripped
08/11/2000 14:14:33.520 ALARM: Check Inverter
08/11/2000 14:27:09.000 STATUS: CSB Power Supply On
08/11/2000 14:27:09.043 NOTICE: Inverter Initializing
08/11/2000 14:27:11.725 STATUS: UPS Power Supply OK
08/11/2000 14:27:11.733 NOTICE: Input Under Voltage
08/11/2000 14:27:11.733 NOTICE: Output Under Voltage
08/11/2000 14:27:11.733 NOTICE: Bypass Under Voltage
08/11/2000 14:27:11.754 ALARM: Rectifier Under Voltage
08/11/2000 14:27:16.464 ALARM: Battery Under Voltage
08/11/2000 14:27:18.954 NOTICE: Battery Voltage Low
08/11/2000 14:27:19.169 NOTICE: Battery Not Present
08/11/2000 14:27:40.714 STATUS: PPU Shutdown
08/11/2000 14:28:04.023 NOTICE: Check Modem
08/12/2000 14:15:09.000 STATUS: CSB Power Supply On
08/12/2000 14:15:09.043 NOTICE: Inverter Initializing
08/12/2000 14:15:11.725 STATUS: UPS Power Supply OK
08/12/2000 14:15:11.733 NOTICE: Input Under Voltage
08/12/2000 14:15:11.733 NOTICE: Output Under Voltage
08/12/2000 14:15:11.754 ALARM: Rectifier Under Voltage
08/12/2000 14:15:11.833 NOTICE: Maintenance Bypass On
08/12/2000 14:15:16.463 ALARM: Battery Under Voltage
08/12/2000 14:15:18.954 NOTICE: Battery Voltage Low
08/12/2000 14:15:19.169 NOTICE: Battery Not Present
08/12/2000 14:15:40.714 STATUS: PPU Shutdown
08/12/2000 14:16:04.023 NOTICE: Check Modem
08/12/2000 14:16:22.925 CMD: Bypass Mode Command
08/12/2000 14:16:23.443 STATUS: K5 (Backfeed) Closed
08/12/2000 14:16:23.586 STATUS: On Bypass
08/12/2000 14:16:24.860 NOTICE: Output Under Voltage OK
08/12/2000 14:17:20.900 NOTICE: Input Under Voltage OK
08/12/2000 14:17:23.606 ALARM: Rectifier Under Voltage OK
08/12/2000 14:17:25.557 ALARM: Battery Under Voltage OK
08/12/2000 14:19:01.899 CMD: PPU On Command
08/12/2000 14:19:04.089 STATUS: K1 (Input) Closed
Figure 13---19. Event History Log
Содержание BPIV
Страница 1: ...www powerware com BPIV INSTALLATION OPERATION MANUAL UPS 10 15 kVA 20 30 kVA...
Страница 19: ...Powerware BPIV 10 kVA 30 kVA Installation and Operation 164201406 Rev C 013004 Section I Installation...
Страница 79: ...Powerware BPIV 10 kVA 30 kVA Installation and Operation 164201406 Rev C 013004 Section II Operation...
Страница 104: ...8 10 Powerware BPIV 10 kVA 30 kVA Installation and Operation 164201406 Rev C 013004 This Page Intentionally Left Blank...
Страница 128: ...9 24 Powerware BPIV 10 kVA 30 kVA Installation and Operation 164201406 Rev C 013004 This Page Intentionally Left Blank...
Страница 138: ...10 10 Powerware BPIV 10 kVA 30 kVA Installation and Operation 164201406 Rev C 013004 This Page Intentionally Left Blank...
Страница 142: ...11 4 Powerware BPIV 10 kVA 30 kVA Installation and Operation 164201406 Rev C 013004 This Page Intentionally Left Blank...
Страница 174: ...15 4 Powerware BPIV 10 kVA 30 kVA Installation and Operation 164201406 Rev C 013004 This Page Intentionally Left Blank...
Страница 262: ...W 2 Powerware BPIV 10 kVA 30 kVA Installation and Operation 164201406 Rev C 013004 This Page Intentionally Left Blank...
Страница 263: ......
Страница 264: ...164201406 Rev C 164201406C...