9--5
Powerware 9315 Parallel Capacity/Redundant System with PHP SSBM
164201373 Rev. A
092402
9.6
Using the Menu Options
The UPS
menus
allow you to display data in the information area to help you
monitor and control UPS operation. The following menus and options are
available:
•
Meters
Displays performance meters for the system or critical load.
•
Events
Displays the list of Active System Events and a historical log of
system events.
•
Statistics
Displays statistical information about UPS operations for the
battery, load, or line.
•
Graphics
Displays a real-time graphic representation of the flow of current
through the internal UPS components.
•
Setup
Allows you to configure the UPS communications port and set
the date and time for the time stamp.
9.6.1
System Meters Screen
Figure 9---3 shows the LCD screen as it appears when you first start the UPS. The
Meters menu is displayed in the menu box, with the System option highlighted. In the
information area, the system meters show their current readings.
Uninterruptible Power System
System Normal
Meters
System
Load Amps
Events Statistics Graphics Setup
Input
Output
Bypass
Battery
VAB
480
VBC
VCA
KW
379
KVA
399
IA
IB
IC
FREQ
60.0
PF
0.95
V
540
I
18
Meters
480
480
480
480
480
VAB
480
VBC
VCA
480
480
IA
IB
IC
361
361
361
IN
000
VAB
480
VBC
VCA
480
480
FREQ
60.0
KVA
300
KW
240
PF
0.80
Battery
48.5
Minutes
Versions
+
ALARM:
NONE
NOTICES: NONE
15 JUL 1998
09:25:42
Figure 9---3. System Meters Screen
(Typical for Powerware 9315---300 480/480V Unit)
The Input area shows the phase-to-phase voltage, frequency, and phase current of the
incoming utility, followed by the KVA, KW, and power factor measurements. The output
area shows the same information for the power being output by the UPS.
The Bypass area shows the phase-to-phase voltage of the bypass source. The Battery
area displays the DC voltage (V) and the DC current (I).