16--2
Powerware 9315 Parallel Capacity/Redundant System with PHP SSBM
164201373 Rev. A
092402
16.3
SSBM Output
Output Voltage
(UPM Dependent)
208 VAC nominal (60 Hz only)
220 VAC nominal (60 Hz only)
380 VAC nominal (50/60 Hz)
400 VAC nominal (50/60 Hz)
415 VAC nominal (50/60 Hz)
480 VAC nominal (60 Hz only)
600 VAC nominal (60 Hz only)
Output Frequency Range
¦
3 Hz of nominal (50 Hz or 60 Hz)
Output Current
Model 2500:
2500 Amps
Model 3000:
3000 Amps
Model 4000:
4000 Amps
Overload Capability
Alarm only. Trip Delay customer adjustable in
accordance with breaker manufacturer
specifications.
16.4
Environmental Specifications
Operating Temperature
0 to 25
˚
C without derating. The recommended
operating temperature is 25
˚
C.
Operating Altitude
Maximum 1500m (5000 ft) at 40
_
C without
derating
Storage Temperature
---20 to +70
˚
C (prolonged storage above 40
˚
C
will cause rapid battery self-discharge)
Relative Humidity
(operating and storage)
95% maximum noncondensing
Acoustical Noise
N/A
EMI Suppression
Meets FCC Regulation 47, Part 15, Subpart J, for
class A devices
Electrostatic Discharge (ESD)
Immunity
Meets IEC 801---2 specifications. Withstands up
to 25 kV without damage and with no disturbance
or adverse effect to the critical load.