DESCRIPTION:
DRAWING NO:
5 of 6
INSTALLATION NOTES
SHEET:
164201373---1
A---6
Powerware 9315 Parallel Capacity/Redundant System with PHP SSBM
164201373 Rev. A
092402
12.
The 100% rated bypass input overcurrent protection and bypass input disconnect switch
are to be provided by the user. Table E lists the maximum rating for output circuit breakers
satisfying the criteria for both. Rating is based on 100% of output current for a 100%
breaker.
Table E. Maximum Bypass Input Circuit Breaker Ratings
Powerware 9315 Switchboard System Bypass module
SSBM Model
Powerware 9315 Switchboard System Bypass module
2500
3000
4000
SSBM Bypass
2500
3000
4000
SMB Bypass
2500
3000
4000
13.
The breakers CBS, CBP, FBP, MBP (optional) and MIS (optional) have AT trip ratings and a
maximum Amp Interrupting Capability (KAIC) as shown in Table F.
Table F. SSBM Breaker Trip Ratings and Amp Interrupting Capability
P
9315 S it hb
d S t
B
SSBM Model
Powerware 9315 Switchboard System Bypass
module
2500
3000
4000
All Models
module
Trip Rating
KAIC
SSBM and SMB
N/A
3000
4000
65
SSBM and SMB
2500
3000
4000
100
14.
The 100% rated output overcurrent protection and output disconnect switch are to be
provided by the user. Table G lists the maximum rating for output circuit breakers
satisfying the criteria for both. Rating is based on 100% of output current for a 100%
breaker.
Table G. Maximum Output Circuit Breaker Ratings
Powerware 9315 Switchboard System Bypass module
SSBM Model
Powerware 9315 Switchboard System Bypass module
2500
3000
4000
SSBM
2500
3000
4000
SMB
2500
3000
4000
15.
In the Parallel Capacity/Redundant System, each UPS module, Switchboard System
Bypass Module (SSBM), SSBM breakers, and optional equipment are crated separately
for shipping.
16.
Do not tilt cabinets more than
¦
10
˚
during handling.
17.
Dimensions are in millimeters (inches).