Item
Action Needed
Maintenance Intervals
(time/hours – whichever comes first)
Remarks
Every
day
Every 6
months
or 4000
Every
year or
8000
Every 2
years or
16000
Every 3
years or
24,000
Every 4
years or
32,000
Every 5
years or
40,000
Electronic Drain Valve
Check outlet connection is
not-restricted
●
Clean solenoid valve body
and housing
●
Replace valve
Oil cooler Intercooler
aftercooler
Clean the fins
●
Cooling fan
Clean blades and motor
body
●
Check fan motor assembly
●
Replace if
malfunctioning
Piping
Check for leaks or looseness
●
Tighten if loose,
replace if leaking
Replace O-rings, gaskets
Oil Mist Catcher
Check for presence of oil in
condensate discharge
●
Investigate reason
for oil content
Replace element
Y type strainers
Clean
●
Replace if damaged
or clogged
Inlet valve
Switching diaphragm
replacement
Replace
Operating diaphragm
Replace
Valve and spring clean and
inspect
●
Replace if damaged
Valve and spring replace
Slide bearing replacement
Shaft Inspect
●
Replace if damaged
or worn
Temperature sensors
Verify sensors are operating
and indicating a reasonable
temperature
●
Replace if reading is
always low or if
intermittent
Pressure sensors
Verify sensors are operating
and indicating a reasonable
temperature
●
Replace if reading is
incorrect
Thermal overload
(manually trip and
reset)
Verify trip condition is
recognized on alarm
●
Replace if trip is not
possible or if not
possible to reset
Contactor
Verify no chattering or signs
of heat damage
●
Replace if
malfunction or
damage
Control relays
Verify no chattering or signs
of heat damage
●
Replace if
malfunction or
damage
Maintenance Schedule table continued on next page