8.2 mechanical checKs
Make sure the cable glands are mounted properly. The cable glands must be adequately locked and
prevent any movement of the cable. Also make sure the cable glands are solidly fixed to the inverter’s
chassis.
Make sure that the gasket on the front panel has been correctly mounted. The gasket must completely
cover the red line on the front of the inverter.
Reference line
correct mounting
incorrect mounting
Fasten the inverter’s front panel by screwing the screws on the panel with the Torx T20 wrench provided.
Warning! To ensure the inverter is waterproof, the front panel screws must be tightened to a torque wrench
setting of at least 1.5 Nm (13.2 in-lbs).