15 - en
en - english
photovoltaic inverters
Note:
Perform the following operations ONLY if the "Germany" has been or will be selected as Nation (for details of the Nation
selection, see section 10.1).
The VDEW directive (applicable in Germany) requires that in a three-phase system the maximum imbalance between the
phases is 4600 W.
For PVI-6000-TL-OUTD models which have a nominal output power greater than this limit, a series of steps are required to
ensure the limitation of the power in the event of phase imbalance.
Bridge the “Alarm” and “Remote”
contacts as in the fi gure at right.
Wire the inverters together in one of the
ways indicated in the fi gures at right.
Wiring via terminals
Wiring via RJ45 connectors
note about the use of the “alarm” terminal block: the alarm terminal block makes the contacts of a relay
available to indicate confi gurable alarm conditions (for information on the possibility and confi guration modes of
the “Alarm” function, see the user manual on the CD that comes in the package). The alarm contact is available under
normally open (N.O.) or normally closed (N.C.) operation compared to the common terminal (C). The maximum
rating for voltage / current that the relay can support is 230V / 1A.
“alarm” terminal block in
pVi-3.0/3.6/4.2-tl-outd
“alarm” terminal block in
pVi-5000/6000-tl-outd
“alarm” terminal block in
pVi-10.0/12.5-tl-outd
functional diagram
for the alarm contact
Содержание Aurora PVI-10.0-TL-OUTD