65
disabled (B2-06=0)
When the AC IN voltage drops due to the increasing charge current, the AC CHARGER
will take care that the voltage does not drop below this level.
B2-02=B2-01+offset voltage
For example: PM-1500SI-122, when B2-01=180V, B2-02=187V, offset voltage=7V
(187-180), B2-02 will automatically go to 197V(190+7) after B2-01 is changed to 190V.
B2-03: AC IN High Connect
This setting forms a pair with AC IN High Disconnect (B2-04). With this setting, one
determines the AC IN high voltage at which level the ATS will switch on. This should lie
below the AC IN High Disconnect (B2-04) level to prevent continuous switching of the
ATS when the voltage is fluctuating around that level.
In fact, the parameter which is changed is the difference between AC IN High Disconnect
(B2-04) and AC IN High Connect (B2-03).
The result of this is that when changing B2-04 level, this level (B2-03) also changes.
B2-03=B2-04
–
offset voltage
For example: PM-1500SI-122, when B2-03=265V, B2-04=270V, offset voltage=5V
(270-265), B2-03 will automatically go to 255V(260
–
5) after B2-04 is changed to 260V.
B2-04: AC IN High Disconnect
Use constant B2-04 to determine the AC IN voltage above which level the ATS will switch
off.
This voltage level will always lie above the AC IN High Connect (B2-03) level. In fact,
changing this level will also change the AC IN High Connect (B2-03) level.
B2-05: AC IN Current Limit
Use constant B2-05 to set the set the specific maximum AC input current. This value is very
important for both battery charger and inverter output power assist.
When using constant B2-05, the values determine the actual AC current limit.
※
Note: With Power Support enabled, there is a minimum value for the AC input current limit.
Please see the note at Power Support (page 71).
B2-06: AC IN Waveform Check
Use constant B2-06 to enable/disable the fast detection of input voltage wave shape.
Содержание PM-1500SI-12X
Страница 17: ...17 Battery Shore Power Max 5A Load ATS ON AC IN AC OUT 5A 2A 30A 5A B2 05 5A 3A ...
Страница 31: ...31 3 4 Battery Connection 3 4 1 Star Connection Schematic ...
Страница 32: ...32 3 4 2 Rail Connection Schematic ...
Страница 35: ...35 3 7 3 Phase System 15 Modules For the settings of MASTER FOLLOWERS and SLAVES see 3 5 and 3 6 ...
Страница 37: ...36 4 1 The following is the structure of user constants ...
Страница 38: ...37 ...
Страница 39: ...38 ...
Страница 40: ...39 ...