14
(optional).
6.
The BTS, voltage sensor and remote control panel (RCP) must be connected to
Master.
7.
The cables for each appliance must be equal in length (AC and DC)
1.6.6 3-Phase Operation
The product can also be used in a 3-phase system, see page 33. The batteries must be
connected in accordance with page 33. The following condition conditions should be
complied with in the case of 3-1phase operation:
1.
Only identical models should be used.
2.
Ensure sufficient battery capacity is available.
3.
Position the products close to each other but ensure there is adequate clearance for
ventilation minimum 20 cm.
(For the better ventilation environment, it is highly recommended to install the fan
cover in the air-in on the right side of Stackable Inverter.
4.
The BTS, voltage sensor should preferably be connected all three units (1 Master
unit and 2 Follower units).
5.
Only a single remote control can be connected.
1.7 Grounding
When the input voltage of the Stackable Inverter is not switched through, the neutral of “AC
OUT” is connected to ground by means of a relay. This function can be disabled by constant
B2-07 (B2-07=0 Disconnect)
1.8
Remote Control Panel (RCP-4)
The product can be operated remotely from remote port with the aid of a remote control
panel. For connection of a remote control panel, see page 28.
Note: The display panel and operation flow of the remote control panel is exactly the same as
the upper-front display panel.
Содержание PM-1500SI-12X
Страница 17: ...17 Battery Shore Power Max 5A Load ATS ON AC IN AC OUT 5A 2A 30A 5A B2 05 5A 3A ...
Страница 31: ...31 3 4 Battery Connection 3 4 1 Star Connection Schematic ...
Страница 32: ...32 3 4 2 Rail Connection Schematic ...
Страница 35: ...35 3 7 3 Phase System 15 Modules For the settings of MASTER FOLLOWERS and SLAVES see 3 5 and 3 6 ...
Страница 37: ...36 4 1 The following is the structure of user constants ...
Страница 38: ...37 ...
Страница 39: ...38 ...
Страница 40: ...39 ...