19
MODE 2: AC Generator Support with Dynmaic Power Shifting
(Example of
PM-3000SI
-242)
When Stackable Inverter enters to MODE 2, B2-09(AC IN DynaCur Limit)=1 (Enable) and
the value of B2-21 (MODE 2: ACINCurrent Lmt) will be loaded to B2-05.
1.
INVERTER Mode:
When AC IN=0 A, AC OUT load is completely supplied by INVERTER. It goes to the
inverter mode.
Battery
Grid,Shore,Generator
Power
Load
ATS OFF
AC IN
AC OUT
5A
5A
0A
75A
2.
Power Control Mode (a)
In this example:
All AC loads are off, with the “Stackable Inverter” constant B2-05=5A (AC IN Current
Limit),
the AC CHARGER will not take more than 5A with limits to battery charge current to
75A.
Battery
Shore Power
Max 5A
Load
ATS ON
AC IN
AC OUT
5A
5A
0A
75A
5A
B2-05=5A