24
MODE 4: Renewable Energy with AC Charger Backup Support
When Stackable Inverter enters to MODE 4, B2-09(AC IN DynaCur Limit)=0 (Disable) and
the value of B2-19 (MODE4: ACINCurrent Lmt)will be loaded to B2-05.
1. INVERTER Mode:
When the battery voltage is not lower than (B2-10) voltage value, inverter mode takes
priority to supply voltage to AC OUT for load consumption.
(INVERTER ON+ ATS OFF + AC CHARGER OFF)
Battery
Shore Pow er
Ready
Load
ATS OFF
A C IN
A C O U T
3A
5A
B2-05=5A
3A
45A
Solar
Charger
Solar Panel
or
2.
Power Control Mode:
When AC IN power is ready, INVERTER is active and battery is about to be exhausted,
battery voltage is lower than B2-10 voltage value and longer than the second time set in
B2-11, ATS will be switched on to ensure AC OUT to continuously the load. At the
moment, AC OUT will be supplied by AC IN power. At the same time, the power control
mode is active and will supply the extra AC IN power to charge the battery!
(INVERTER OFF + ATS ON + AC CHARGER ON + Power Control Mode ON)
Battery
Shore Power
Load
ATS ON
AC IN
AC OUT
2A
5A
B2-05=5A
3A
30A
Solar
Charger
Solar Panel
or
5A
Содержание PM-1500SI-12X
Страница 17: ...17 Battery Shore Power Max 5A Load ATS ON AC IN AC OUT 5A 2A 30A 5A B2 05 5A 3A ...
Страница 31: ...31 3 4 Battery Connection 3 4 1 Star Connection Schematic ...
Страница 32: ...32 3 4 2 Rail Connection Schematic ...
Страница 35: ...35 3 7 3 Phase System 15 Modules For the settings of MASTER FOLLOWERS and SLAVES see 3 5 and 3 6 ...
Страница 37: ...36 4 1 The following is the structure of user constants ...
Страница 38: ...37 ...
Страница 39: ...38 ...
Страница 40: ...39 ...