21
17: External output isolation transformer connection
Interface
Setting
Parameter 2:
External output isolation transformer
connection (the UPS output voltage will rise at higher loads
to compensate for transformer regulation)
ENA:
An external output isolation transformer is connected.
DIS:
An external output isolation transformer is not
connected. (Default)
18: Display setting for autonomy time
Interface
Setting
Parameter 2:
Set up the display setting for autonomy time
EAT:
If EAT is selected, it will display the remaining
autonomy time. (Default)
RAT:
If RAT is selected, it will show accumulated autonomy
time so far.
19: Acceptable input voltage range setting
Interface
Setting
Parameter 2:
Set the acceptable high voltage point and
acceptable low voltage point for input voltage range by
pressing the Down key or Up key.
HLS:
Input high voltage point
280/290/300:
setting the high voltage point in parameter
2. (Default: 300Vac)
LLS:
Input low voltage point
110/120/130/140/150/160:
setting the low voltage
point in parameter 2. (Default: 110Vac)
00: Exit setting
Interface
Setting
Exit the setting mode.