27
CAPACITY*
1000VA/1000W
INPUT
Voltage
Range
Low Line Transfer
160VAC/140VAC/120VAC/110VAC ± 5 %
( based on load percentage 100% - 80 % / 80 % - 70 % / 70 - 60 % / 60 % - 0)
Low Line
Comeback
175VAC/155VAC/135VAC/125VAC ± 5 %
High Line Transfer
300 VAC ± 5 %
High Line
Comeback
290 VAC ± 5 %
Frequency Range
40Hz ~ 70 Hz
Phase
Single phase with ground
Power Factor
≧
0.99 @ full load
THDi
≦
5% @ 205-245VAC
THDU < 1.6% @ input and full linear load condition
OUTPUT
Output voltage
200/208/220/230/240VAC
AC Voltage Regulation
± 1% (Batt. Mode)
Frequency Range
(Synchronized Range)
47 ~ 53 Hz or 57 ~ 63 Hz
Frequency Range
50 Hz ± 0.1 Hz or 60Hz ± 0.1 Hz (Batt. Mode)
Current Crest Ratio
3:1
Harmonic Distortion
≦
2 % THD (Linear Load) ; 4 % THD (Non-linear Load)
Transfer
Time
AC Mode to Batt.
Mode
Zero
Inverter to Bypass
< 4 ms
Waveform (Batt. Mode)
Pure Sinewave
EFFICIENCY
AC Mode
≧
89% @ full charged battery
ECO Mode
≧
96% @ full charged battery
Battery Mode
≧
88%
BATTERY
Battery Type
12V/9AH
Numbers
4
Recharge Time
3 hours recover to 95% capacity for internal battery@ 2A charging current
Charging Current
200/208/220/230/240 VAC models: default 2A, max. 12A adjustable
Charging Voltage
54.7 VDC ± 1%
PHYSICAL
Dimension, D X W X H (mm)
510 x 438 x 88
Net Weight
(kgs)
With battery
19.5
Without battery
9.4
ENVIRONMENT
Operation Humidity
20-95 % RH @ 0- 40°C (non-condensing)
Noise Level
Less than 20dBA @ 1 Meter (With fan speed control). Excluding Alarms
MANAGEMENT
HID USB
Supports power interface on Windows and MAC O/S
Smart RS-232 or USB
ViewPower Supports Windows® 2000/2003/XP/Vista/2008/7/8/10, Linux, Unix and MAC
Optional SNMP
Power management from SNMP manager and web browser
* Derate capacity to 80% of maximum when the output voltage is adjusted to 200VAC or 208VAC. Derate capacity by 10% of maximum for
every 2°C above 30°C ambient temperature.
** Product specifications are subject to change without further notice.
7.