iHE
26
L
OCKOUT
D
ISPLAY
(
Table 2.0
)
The Display will show a if the appliance has locked
out. More information can be obtained by pressing the Info
button on the HMI display screen. Example screen:
INFO
00:02
Error
30:Flow sensor 1
The number on the display indicates the number of the
PCB that the fault has occurred on (See
fi
g 7.1 for help in
identifying PCB). In this example a
fl
ow sensor error has
occurred on the second heat engine (PCB 2).
D
IAGNOSTICS
The HMI can provide additional information in Engineer
Mode.
To enter Engineer Mode:
•
Press OK then hold down the Info button for more
than 3 seconds.
•
Select Engineer from the list using the Wheel, then
press OK.
•
Use the Wheel to scroll down to ‘Fault’ and press OK.
•
Step through the lines 6800 to 6995 to list the last 20
faults. The
fi
rst screen gives the general fault and the
time and date of its occurrence. Example screen:
•
Prog
No
6800
09:32
26.01.2012
Fault
History 1
133: Safety Time Exceeded
•
Page two of fault history records speci
fi
c details about
what the software and controls were doing at the pre-
cise moment the fault occurred. Example screen:
Prog
No
6805
625
Fault
SW diagnostic code 1
Burner control phase 1 3
A complete listing of displayed fault codes, and pos-
sible areas of resolution is given in table 3.0 on page
34. Please also refer to the “iHE users operating and
programming guide” for details not covered by this
manual.
FAULT FINDING
O
PERATION
S
EQUENCE
The appliance requires Mains on both the Live (L)
and Remote Enable connection to be able to run. It
is delivered with a link between them which can be
removed if a Timer or Remote Switch is used.
To run the Heater you must have a Mains supply,
Gas, and a Tank or Central Heating temperature
below their set point.
If all the above are correct then the Gas Ignition
Control starts the Ignition sequence:
1. The Fan runs as a pre-purge of the Heat
Exchanger
2. After a few seconds a spark is created at the
electrode and the burner is lit.
3. The
burner
fl
ame is sensed and the spark is
removed.
4. The Fan speed is then changed by the control
to suit the working conditions.
5. If it fails to light the burner the spark will stop
and the Fan will run on as a post-purge of the
Heat Exchanger.
6. The ignition sequence will be repeated up to
fi
ve
times, then the control will lockout and will require
a manual reset to start again.
L
OCKOUTS
If the Heat Engine is unable to light or detects a
safety condition, the control will lockout and that
Heat Engine will stop
fi
ring. The display will show
the symbol and the green LED on the
appropriate Control Board will
fl
ash. The fault will
have to be cleared before that Heat Engine will
function. Pressing the Info button will provide the
fault detail, see the Table 2.0 for the most common
lockouts. Press the RESET button and provided
the condition has been corrected the Heat Engine
will try to light.
A Lockout condition should not be repeatedly reset.
If the condition persists then a quali
fi
ed repair engi-
neer should be called.
10
Outside Sensor error (where
fi
tted)
20
Flow Sensor error.
28
Flue Gas Temperature Sensor error.
30
Flow Sensor error
40
Return Sensor error
50
DHW Temperature Sensor error
128
Loss of Flame during operation
133 Unsuccessful
Ignition
Table 2.0
Содержание iHE 100/300
Страница 1: ...M6500 M6500 ...
Страница 21: ...iHE 19 Fig 4 3 WIRING DIAGRAM PCB 1 ...
Страница 22: ...iHE 20 WIRING DIAGRAM PCB 2 3 Fig 4 4 ...
Страница 34: ...iHE 32 APPLIANCE COMPONENTS Fig 7 1 21 20 17 22 19 18 16 24 25 26 27 28 29 23 ...
Страница 35: ...iHE 33 APPLIANCE COMPONENTS Fig 7 2 2 3 5 4 6 14 13 12 7 11 8 10 1 15 9 31 32 34 35 36 30 37 33 ...
Страница 39: ...NOTES ...
Страница 40: ...Publication Date 01 09 12 ...