Copy
(515, 535, 555, 575, 615)
The time switching program for one day can be copied and assigned to another or
several other days.
Note
: Day blocks cannot be copied.
Default values
(516, 536, 556, 576, 616)
Setting of the default values given in the setting table
8.4.5 Holiday programs
The heating circuits may be set to a selectable operation level with the holiday
program during a certain holiday period.
Preselection
(641, 651, 661)
8 vacation periods can be selected with this preselection.
Start of holiday
(642, 652, 662)
Entering the holiday start
End of holiday
(643, 653, 663)
Input of holiday end
Operatin level
(648, 658, 668)
Selection of the operation level (reduced setpoint or frost protection) for the holi-
day program.
Note:
A holiday period ends each time on the last day at 12:00 AM (00:00). The
holiday programs are only activated in the operation mode
Automatic
.
8.4.6 Heating circuits
Comfort setpoint
(710, 1010, 1310)
Setting the maximum comfort setpoint in the heating phases. Without room sen-
sor or with the room influence (prog.no. 750, 1050, 1350), this value is used for
calculation of the flow temperature, to theoretically reach the set room tempera-
ture.
Reduced setpoint
(712, 1012, 1312)
Setting of the desired room temperature during the reduced heating phase. With-
out room sensor or with the room influence (prog.no. 750, 1050, 1350), this value
is used for calculation of the flow temperature, to theoretically reach the set
room temperature.
Frost protection setpoint
(714, 1014, 1314)
Setting of the desired room temperature during the frost protection operation.
Without room sensor or with the room influence (prog.no. 750, 1050, 1350), this
value is used for calculation of the flow temperature, to theoretically reach the
set room temperature. The heating circuit remains turned off until the flow tem-
perature drops so far that the room temperature falls below the frost protection
temperature.
Heating curve slope
(720, 1020, 1320)
Using the heating curve, the flow temperature setpoint is formed, which is used
for control of the heating circuit, based on the outside temperature. The slope of
the curve indicates by how much the flow temperature changes with changing
outside temperature.
Programming
7308536-02 06.13
Condensing gas boiler Eurocondense three125-300 kW
81
Содержание EC three 125
Страница 25: ...Wiring plan Before installation 7308536 02 06 13 Condensing gas boiler Eurocondense three125 300 kW 25 ...
Страница 27: ...Wiring plan Before installation 7308536 02 06 13 Condensing gas boiler Eurocondense three125 300 kW 27 ...
Страница 29: ...Wiring plan Before installation 7308536 02 06 13 Condensing gas boiler Eurocondense three125 300 kW 29 ...
Страница 33: ...4 8 Legend Before installation 7308536 02 06 13 Condensing gas boiler Eurocondense three125 300 kW 33 ...
Страница 147: ...Space for notes 7308536 02 06 13 Condensing gas boiler Eurocondense three125 300 kW 147 ...